Apollo SOTERIA UL Installation Manual

Switch monitor input/output module

Advertisement

Quick Links

APD0830 / 2021 / ISSUE 3
INSTALLATION GUIDE
SOTERIA UL
SWITCH MONITOR INPUT/OUTPUTMODULE
GENERAL
The Switch Monitor I/O Module is a loop-powered device that incorporates a monitored input circuit for
connection to a remote switch alongside a 240 Volt-free relay output. It is mounted with a plastic fascia
plate for use with a UL listed 4" electrical box or dual gang.
Please Note:
The Switch Monitor I/O Module is designed for indoor dry use only .
The unit must be installed in a dedicated suitable UL listed enclosure, employing only power limited
circuit.
CONTROL PANEL COMPATIBILITY
The Switch Monitor I/O Module has been approved by UL, LLC. For details of compatible panels
contact Apollo America Inc. For relay compatibility contact the Panel manufacturer
TECHNICAL INFORMATION
All data is supplied subject to change without notice. Specifications are typical at 24V, 25°C and 50% RH
unless otherwise stated.
Part Number
Replacement Part Number
Type
Dimensions
Temperature Range
Humidity
Signal Line Circuit (SLC)
Operating Voltage
Modulation Voltage
Supervisory Current
LED Current
Maximum Loop Current
Approvals
Material
Max Standby Current (Pulsing LED)
Max Surge Alarm Current (LEDs on)
Wire Range
SA4705-703APO
55000-859, 55000-785, 55000-820
Switch Monitor Input/Output Module
4.9" width x 4.9" height x 1.175" depth
32°F to 120°F (0°C to 49 °C)
0 to 95% RH (Non-Condensing)
Supervised
17-28 V DC
5-9 V (peak to peak)
<700 µA
1.6 mA per LED
1A
UL, ULC, CSFM, FM
UL 94 V-0
2.96 mA
4.8 mA
12-24 AWG
1

Advertisement

loading

Summary of Contents for Apollo SOTERIA UL

  • Page 1 CONTROL PANEL COMPATIBILITY The Switch Monitor I/O Module has been approved by UL, LLC. For details of compatible panels contact Apollo America Inc. For relay compatibility contact the Panel manufacturer TECHNICAL INFORMATION All data is supplied subject to change without notice. Specifications are typical at 24V, 25°C and 50% RH unless otherwise stated.
  • Page 2: Installation

    100 Ω max End-of-Line resistors* 47k Ω Note: *A UL listed end-of-line resistor is available at Apollo, Part no. 44251-146 Remarque: * Une résistance de fin de ligne répertoriée UL est disponible chez Apollo, réf. 44251-146 Analogue Values Without Ground Fault...
  • Page 3: Wiring Instruction

    Fig. 1 Fig. 2 WIRING INSTRUCTION Remarque: "X" désigne les terminaux inutilisés. Note: ‘X’ denotes unused terminals. CAUTION – • When Making Installation, Route Field Wiring Away From Sharp Projections, Corners, and Internal Components • A minimum of 1/4 inch space is required between Power Limited and Non-Power Limited circuits while wiring.
  • Page 4 Class B | Fig. 4* Note:* A UL listed end of Line resistor is required in Class B Remarque: * Une résistance de fin de ligne répertoriée UL est requise en classe B Continuité fonctionnelle de la terre. Ne vous connectez pas au backbox. Le blindage doit être scotché...
  • Page 5: Address Setting

    ADDRESS SETTING Steps The dip switch used to address your device has 10 individual switches (Figure 6). Address setting is done by dip switches 1-8 (see page 6 for address matrix). In XP/Discovery Protocol, only dip switch 1-7 are used, dip switch 8 is used to enable ground fault analogue value.
  • Page 6 All information in this document is given in good faith but Apollo America Inc. cannot be held responsible for any omissions or errors. The company reserves the right to change the specifications of products at any time and without prior notice.
  • Page 7 All information in this document is given in good faith but Apollo America Inc. cannot be held responsible for any omissions or errors. The company reserves the right to change the specifications of products at any time and without prior notice.
  • Page 8 All information in this document is given in good faith but Apollo America Inc. cannot be held responsible for any omissions or errors. The company reserves the right to change the specifications of products at any time and without prior notice.

This manual is also suitable for:

Sa4705-703apo