APD0830 / 2021 / ISSUE 3
INSTALLATION GUIDE
SOTERIA UL
SWITCH MONITOR INPUT/OUTPUTMODULE
GENERAL
The Switch Monitor I/O Module is a loop-powered device that incorporates a monitored input circuit for
connection to a remote switch alongside a 240 Volt-free relay output. It is mounted with a plastic fascia
plate for use with a UL listed 4" electrical box or dual gang.
Please Note:
The Switch Monitor I/O Module is designed for indoor dry use only .
•
•
The unit must be installed in a dedicated suitable UL listed enclosure, employing only power limited
circuit.
CONTROL PANEL COMPATIBILITY
The Switch Monitor I/O Module has been approved by UL, LLC. For details of compatible panels
contact Apollo America Inc. For relay compatibility contact the Panel manufacturer
TECHNICAL INFORMATION
All data is supplied subject to change without notice. Specifications are typical at 24V, 25°C and 50% RH
unless otherwise stated.
Part Number
Replacement Part Number
Type
Dimensions
Temperature Range
Humidity
Signal Line Circuit (SLC)
Operating Voltage
Modulation Voltage
Supervisory Current
LED Current
Maximum Loop Current
Approvals
Material
Max Standby Current (Pulsing LED)
Max Surge Alarm Current (LEDs on)
Wire Range
SA4705-703APO
55000-859, 55000-785, 55000-820
Switch Monitor Input/Output Module
4.9" width x 4.9" height x 1.175" depth
32°F to 120°F (0°C to 49 °C)
0 to 95% RH (Non-Condensing)
Supervised
17-28 V DC
5-9 V (peak to peak)
<700 µA
1.6 mA per LED
1A
UL, ULC, CSFM, FM
UL 94 V-0
2.96 mA
4.8 mA
12-24 AWG
1