PowerGATE™ Power Input / Output Panel
Installation
– Output Panels (continued)
6. Continue with connections, beginning with the rear of the
cabinet and working forward
7. Complete the Phase (hot) connections
Proper connection (See Figure 10):
A. Grasp connector jacket and firmly Insert cam connector
into cam plug
B. Push on cam connector jacket until connector fully seats in
cam plug
C. Rotate cam connector jacket counterclockwise until it
stops
Step 7: Close and lock lower chamber door, allowing cables
to exit through smaller cable door (See Figure 11)
Step 8: Powering Up
WARNING
Power MUST BE supplied from a source wired to a Transfer
Switch
1. Toggle the transfer switch, diverting power from building
loads to load bank
Disconnecting Circuits
Step 9: Disconnecting Circuits
WARNING
DO NOT ATTEMPT DISCONNECTING WHILE CIRCUITS ARE
LIVE
– Open lower chamber door
– Order of disconnect
1. Disconnect the Phase (hot) connections, beginning with the
closest to the front door to the right.
10
Contact Lex Products: 800.643.4460 info@lexproducts.com
- Output Panels (continued)
Proper disconnection (See Figure 12):
A. Grasp connector jacket firmly and rotate cam connector
counter clockwise until it stops
B. Firmly pull on connector until it separates from the plug
C. Set aside
3. Continue with ALL Phase (hot) connections, beginning with
the front of the cabinet and working from front to back
4. Complete disconnect of ALL Hot connections prior to
proceeding
5. Disconnect the Neutral (white) connections, beginning with
the closest to the front door
Proper disconnection (See Figure 12):
A. Grasp connector jacket firmly and rotate cam connector
counter clockwise until it stops
B. Firmly pull on connector until it separates from the plug
C. Set aside
6. Continue with ALL Neutral (white) connections, beginning
with the front of the cabinet and working from front to back
7. Complete disconnect of ALL Neutral connections prior to
proceeding
Proper disconnection (See Figure 12):
A. Grasp connector jacket firmly and rotate cam connector
counter clockwise until it stops
B. Firmly pull on connector until it separates from the plug
C. Set aside
8. Continue with ALL Ground (green) connections, beginning
with the front of the cabinet and working rearward
9. Complete disconnect of ALL Neutral connections prior to
proceeding
Proper disconnection (See Figure 10):
A. Grasp connector jacket firmly and rotate cam connector
counter clockwise until it stops
B. Firmly pull on connector until it separates from the plug
C. Set aside
Step 10: Secure the three (3) key locks to complete
procedure