No.
Item
5
(Optional)
Power cable of
the tracking
system
Note a: The value is valid only if the conductors of the PE cable and AC power cable use the same
material. If the materials are different, ensure that the conductor cross-sectional area of the PE
cable produces a conductance equivalent to that of the area S/2. The specifications of the PE cable
are subject to this table or calculated according to IEC 60364-5-54.
Note b: You are advised to use a soft cable to prevent poor terminal contact due to the bending
stress of the cable.
Note c: For some models, the outer diameter of a single-core cable ranges from 14 mm to 36 mm
based on the label in the maintenance compartment.
Note d: For some models, when the OT/DT terminal is crimped as shown in the following figure
and the rubber baffle plate of the AC wiring terminal is 112 mm, the maximum conductor cross-
sectional area of the single-core cable can be 400 mm
Specifications of the Crimped OT/DT Terminal
Specification of the Rubber Baffle Plate
Type
Three-core outdoor
copper cable with
dual-layer
protection
Specifications
Conductor cross-
sectional area: 10
mm
2
Cable outer diameter:
15–18 mm
.
2
8
Description
-