TFS-1181R / TFS-1181W
Intelligent Addressable Sounder With Built-
in Isolator
Installation Manual
Warnings
General
✓ Read this manual carefully before operating the device and retain it for future reference
✓ Pay attention to all warnings and precautions described in the manual.
✓ Keep devices away from water and moisture utunuz.
Service
Do not attempt to repair the device by yourself, you may be exposed to electric shock if you open the device
cover.
In the event of any malfunction, contact your dealer or authorized service. Technical intervention to the device
must be performed by qualified service personnel.
Attention: Do not attempt to remove the card from its plastic housing. Completely closed for
your safety. Users must avoid Intervention.
Fault Conditions Requiring Service
In the event of any malfunction or in the following cases, contact your authorized service or dealer.
✓ When the power cord or plug is damaged,
✓ When any liquid flows into the device or the object falls,
✓ When exposed to water and rain,
✓ If the device has been dropped or the housing has been damaged
✓ If the device has noticeable performance changes,
✓ If the device does not operate normally according to the operating instructions specified
Call for service as incorrect operations can cause other malfunctions.
Maintenance on your own
Do not try to fix the device on your own. Removal of cover may end up with electricity shock. In case of any
defect or malfunction, contact with your dealer or with authorized service. All the technical interventions have
to be done by technicians of company. Device must be cleaned up with a dry fabric. No-chemicals are allowed
for cleaning.
Transportation
Device must be carefully transported avoiding all physical bump, stroke and possible fluid entry. Malfunctions
that caused by improper transportation is not under warranty.
Human and Environmental Health
This device contains no chemical or biological elements that could harm human condition.
Technical Features
Power
Current Consumption
Alarm Consumption
Release Date: 05/01/2021
Sound Level
Rev:01
Sound Tone
Sounder Type
Piezo
Heart LED
Protection Class
Operating Temperature Range
Usage
Humudity
Dimentions (mm)
Body Material
Cable Selection
Weight (With Base)
Isolator
Avarage Consumption @24V
Vmax.
Vnom.
Vmin.
Vso_max.
Vso_min.
Vsc_max.
Vsc_min.
Ic_max.
Is_max.
IL_max.
Zc_max.
Indicator Lights
The device is in normal working
condition (can be off through CP)
Alarm Condition
Shortcircuit
Terminals
1 -
2 -
3 -
4 -
15VDC – 32VDC (Nom.27VDC)
~90 µA ( @ 27VDC )
~Min.=5.16mA, Nom.=7.86 mA, Max.=11.23mA. (27VDC )
89.4 / 94.3 / 97 dB±2 dB (@ 27VDC, at 1 meter)
42 Different Tone
Type A
Piezo with sealing
20sec White LED
IP21C
-10C ~ 55C
Internal Usage / Siren Type : Type A
Between %0 - %95 at +40°C
Ø:110mm, h:55mm (Include Base Bracket)
Red / Transparent, ABS
0.8mm ² ~ 1.5mm ²
207.7Gr.
15uA
32V
28V
15V
18V
9V
5V
0,7V
0,5A
3A
0,026A
0,026Ω
White Led
RED / White LEDs
(7 pcs)
20s Flashing
x
X
x
X
X
Loop (-) IN
Loop (-) OUT
Loop (+) IN, OUT
20sec RED LED
Yellow LEDs
X
X
Constant Lit
Need help?
Do you have a question about the TFS-1181R and is the answer not in the manual?
Questions and answers