Selec RPS480-24-CE Operating Instruction

Advertisement

Quick Links

SPECIFICATION

selec
FEATURES
Ø
AC 100-240V Wide-range Input.
Ø
Active PFC
Ø
Cost optimized without compromising quality or reliability.
0
0
Ø
Full power between -25C and +50C.
Ø
DC-OK Relay contact.
Ø
Compact size.

INTENDED USE

This device is designed for installation in an enclosure and is intended for the
general professional use such as in instrumentation equipment, office,
industrial control and communication .
Do not use this power supply in equipment where malfunction may cause
severe personal injury or threaten human life.
SAFETY INSTRUCTION
RPS480-24-CE

INPUT SPECIFICATIONS

Operating Instruction
INPUT VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY(TYP.)
AC CURRENT(TYP.)
INRUSH CURRENT(TYP.)
POWER FACTOR
START UP TIME

OUTPUT SPECIFICATIONS

OUTPUT VOLTAGE
OUTPUT CURRENT
RIPPLE AND NOISE
LINE AND LOAD REGULATION
HOLD UP TIME
DC-OK CONTACT
SERIES OPERATION
Ripple & Noise measured at 20MHz of bandwidth by using 0.1uF & 10uF parallel capacitor.
*

PROTECTIONS

INPUT FUSED
OUTPUT OVER LOAD
OUTPUT SHORT CIRCUIT
OUTPUT OVER VOLTAGE
OVER TEMPERATURE

ENVIRONMENT

OPERATING TEMPERATURE
STORAGE TEMPERATURE
HUMIDITY
ALTITUDE
SAFETY & EMC
SAFETY STANDARDS
DIELECTRIC WITHSTAND
VOLTAGE
INSULATION RESISTANCE
CONDUCTED EMISSION
RADIATED EMISSION
CURRENT HARMONICS
EMS IMMUNITY
±10% ; 127 - 370VDC
100 - 240VAC
50-60Hz
93.5% @ 230VAC
4.8A @ 115VAC; 2.4A @ 230VAC
<60Amps; Measured at 264VAC,
0
25 C Ambient, Cold Start
>0.95 @ Full Load Over entire input range
<
2 Sec @ Full Load Over entire input range
24 - 28VDC
20A at 24V; 17.14A at 28V
<1% of Vout
*
±1%
25ms at 24V & 16ms at 28V @ 115/230VAC, Full Load
30VDC 1A; 60VDC 0.5A; 125VAC 0.5A,
resistive load; min. current 1mA
Possible for up to two power supplies
(with external diode)
8A- 250VAC Internal
110% to 140% of rated output current
Protection type : Hiccup mode; recovers
automatically after fault condition is removed.
Hiccup mode when output is shorted; Recovers
automatically after fault condition is removed.
31VDC ± 0.5VDC
Protection type : Latched; Input AC power
has to be recycled to recover the power supply.
Power supply shuts down when the temperature of
0
PCB below PFC choke reaches typically120C;Turns
0
ON only after the temperature falls to below 90C
typically and AC power is recycled there after.
0
0
-25 C to +70 C
0
0
*De-rate output power at 12W/ C above +50 C Ambient.
0
0
-40 C to +85 C.
5 to 95% RH, Non Condensing
2000m
Designed to meet UL 62368-1
Processing for UL-508
I/P to Earth
: 2500VAC
I/P to O/P
: 4000VAC
O/P to Earth
: 1500VAC
O/P to DC-OK : 500VAC
100 M min. (between all outputs and all inputs
/
PE
terminals) at 500 VDC
EN55022 ; Class B
EN55022 ; Class A
Class D
Compliance to IEC61000-4-4,5,11
DIMENSIONAL DIAGRAM
DIMENSION
60*154*158.55mm (W*H*D)
WEIGHT
1050 gms
WIRING DIAGRAM
+
+ + + - - - -
- -
- -
- -
- -
+
+
24VDC 20A
24VDC 20A
OUTPUT
OUTPUT
480W
480W
DC ON
DC ON
DC OK
DC OK
Vo ADJ.
Vo ADJ.
RPS480-24-CE
RPS480-24-CE
INPUT
INPUT
100 - 240VAC
100 - 240VAC
; 50/60Hz
; 50/60Hz
L L L L N N N N
L L L L N N N N

WIRING INSTRUCTIONS

1. To prevent risk of electric shock, power supply equipment must be
kept OFF while wiring.
2. Terminals and electrically charged parts must not be touched when
the power is ON.
3. Wiring shall be done strictly according to terminal layout provided
in the operating manual.
Doc. name: OP INST RPS480-24-CE OP910-V02(Page 1 of 2)
4.85
PE (Protective
Earth) Input

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RPS480-24-CE and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Selec RPS480-24-CE

  • Page 1 3. Wiring shall be done strictly according to terminal layout provided CONDUCTED EMISSION EN55022 ; Class B in the operating manual. EN55022 ; Class A RADIATED EMISSION SAFETY INSTRUCTION Class D CURRENT HARMONICS Compliance to IEC61000-4-4,5,11 EMS IMMUNITY Doc. name: OP INST RPS480-24-CE OP910-V02(Page 1 of 2)
  • Page 2 Minor electric shock, fire or product failure may occasionally occur. Do not allow any pieces of metal or conductors or any clippings or cuttings resulting from installation work to Fig. 3 enter the product. Doc. name: OP INST RPS480-24-CE OP910-V02(Page 2 of 2)

Table of Contents