Transformers with IECEx certification
Ambient temp.
+55°C
+50°C
+45°C
+40°C
+39°C
Please note the Max. output current is total current for the whole system, not just for single individual
socket. For example, if max. output current is 16A and the TrafoEx transformer is equipped with 2x
sockets, total current of the 2x sockets can't exceed 16A. If one socket is used with 10A load, the other
available socket can be used with no more than 6A load.
When connecting relating equipment to the SLAM
characteristics of the equipment in case and ensure that above mentioned special conditions are taken
account.
Portable and transportable
®
The SLAM
TrafoEx is certified for portable or transportable use. Please see below for conditions
defining the portable and transportable conditions.
Portable
The unit is connected to mains power source, but none of the relating equipment has not been connected
to the output sockets of the transformer. Unit may be moved around when energized.
Transportable
The unit is connected to mains power source and relating equipment has been connected to the output
sockets with compatible plug. Unit may not be moved when energized. To move the equipment,
disconnect the mains power source or related equipment from the output sockets.
Enclosure
The empty enclosure with a coating must not be used in areas affected by charge-producing
processes, mechanical friction and separation processes, electron emission (e.g. in the vicinity
of electrostatic coating equipment), and pneumatically conveyed dust.
13/16
Max. Output current with CEAG sockets
Output 12V or 24V
6A
10A
13A
15A
16A
Output 48V
6A
8A
8A
8A
8A
®
TrafoEx please observe the operational