senva TotalSense Series Installation Instructions Manual

senva TotalSense Series Installation Instructions Manual

Indoor air quality sensor bacnet/modbus/analog
Hide thumbs Also See for TotalSense Series:

Advertisement

INSTALLATION INSTRUCTIONS
TM
T talSense
Indoor Air Quality Sensor
BACnet/Modbus/Analog
IMPORTANT WARNINGS
Only qualified trade installers should install this product
This product is not intended for life-safety applications
Do not install in hazardous or classified locations
The installer is responsible for all applicable codes
De-energize power supply prior to installation or service
PRODUCT APPLICATION LIMITATION:
Senva products are not designed for life or safety applications. Senva products
are not intended for use in critical applications such as nuclear facilities, human
implantable device or life support. Senva is not liable, in whole or in part, for
any claims or damages arising from such uses.
FEATURES
The TotalSense series design allows customization for a sensor
that meets project requirements for monitoring temperature,
carbon dioxide (CO2), total volatile organic compounds
(TVOC), particulate matter (PM), relative humidity (RH),
passive-infrared occupancy sensor (PIR), and ambient light.
The product can be ordered as a stand-alone CO2, RH, Temp,
TVOC, PM, or PIR sensor as well as almost any combination of
sensors. Resistive-set-point sliders and pushbuttons are also
available to meet the requirements for any job. All models
come standard with programmable set-point relay (except on
PM models) and barometric pressure compensation for CO2.
Choose the analog version to receive up to three
selectable and programmable analog outputs or utilize the
communications version to access a myriad of data through
Modbus RTU or BACnet MS/TP. Communications version
comes standard with ambient light sensing.
To verify the features see the
'Product Identification' section of
the installation manual or use the
configuration tool at senvainc.com or
scan the QR code on the right.
senvainc.com 1-866-660-8864 (F)1-503-296-2529 9290 SW Nimbus Ave. Beaverton Oregon 97008
Series
TotalSense Configurator
PRODUCT IDENTIFICATION
Pkg
Out
CO2
RH
AQ2
-
Package
W = Surface
Output Type
A = 3-wire Analog
B = BACnet/Modbus
CO2
A = None
C = Standard CO2
D = Dual Channel CO2
Relative Humidity
A = None
2 = 2% RH accuracy
VOC
A = None
V = TVOC
Particulate Matter
A = None
P = PM 1.0, 2.5, 4.0, 10.0 (Available on AQ2W-B
BACnet/Modbus versions only)
Temperature Output
A = None
B = Transmitter and display/comms temp reading
C = 100Pt RTD
D = 1000Pt RTD
E = 10K Type 2
F = 10K Type 3
G = 10k w/11k
H = 3k
I = 2k2
J = 1k8
K = 20k
Display
X = None
D = Color OLED Display
S = Color OLED display with solid cover
R = Air Quality Ring
PIR Motion/Occupancy Sensor
Blank = None
P = PIR Sensing
Accessories
† ‡
C = 1k Ω Setpoint Slider
D = 10k Ω Setpoint Slider
T = 200-900 Ω Setpoint Slider
E = 910 Ω offset resistor (available with slider only)
S= Slider override Pushbutton (available with slider only)
O = Thermistor Override Pushbutton
U = User Pushbutton
Additional Setpoint sliders and offset resistors available
upon request
‡ Slider and pushbutton options not available with PM sensor
Disp
VOC
PM
T
Acc

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TotalSense Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for senva TotalSense Series

  • Page 1 E = 10K Type 2 implantable device or life support. Senva is not liable, in whole or in part, for F = 10K Type 3 any claims or damages arising from such uses.
  • Page 2: Installation

    INSTALLATION SETUP - WIRING 1. IMPORTANT! Locate the device in an area away from The following diagrams show terminal locations for each ventilation sources and heat generating equipment and version of the TotalSense. The number of options selected will appliances. The device should be mounted at light switch determine which of the terminals are included on each device.
  • Page 3: Setup - Communications

    SETUP - COMMUNICATIONS SETUP - DISPLAY Example screen: TotalSense devices ordered with color OLED display can *BUTTON *SLIDER be configured from the display or over communications (if applicable). The default screen layout will vary depending on which model is ordered. Each of the 5 sections can be customized.
  • Page 4 FEATURE - AIR QUALITY RING FEATURE - AIR QUALITY An Air Quality (AQ) Ring may be selected in place of a display. If Air Quality is selected to be displayed or if the Air quality Ring The AQ ring will glow green, yellow, or red according to the option is selected, the device will monitor each CO2, VOC, PM, detected levels of CO2, PM, VOC, RH, and Temp.
  • Page 5: Troubleshooting

    Ring element. Scaling: Check wiring. Ensure power supply meets Senva’s TVOC sensor uses an Ethanol reading to determine a No output requirements. raw TVOC value. Additionally, conversion from µg/m3 uses the molecular weight of Ethanol. To scale based on a different gas...
  • Page 6: Specifications

    SPECIFICATIONS Without Display 16-30VDC/24VAC , 3.5W nominal, 4W max. Power Supply With LED Ring or Display 24-30 VDC/24VAC , 4.3W nominal, 5W max Color OLED (optional) 1.5” Organic LED Display, 128x128 PX, color Interface Air Quality Ring Color changing (red/yellow/green) LED ring Quantity Up to 3 outputs Analog Outputs (Analog...

Table of Contents