Technical Specifications - Vector SRC-C1T1 Product Data Sheet

Indoor co2+temperature transmitter
Hide thumbs Also See for SRC-C1T1:

Advertisement

Ordering
Item Name
Item code
40-300198
SRC-C1T1
40-300198-0
SRC-C1T1-W0
40-300198-1
SRC-C1T1-W1
40-300198-2
SRC-C1T1-W2
Accessories
Item name
Item code
40-500006
OPA-S
40-500030
OPU-S

Technical Specifications

Important notice and safety advice
This device is for use as a transmitter. It is not a safety device. Where a device failure could endanger human life and
property, it is the responsibility of the client, installer and system designer to add additional safety devices to prevent
such a device failure. Ignoring specifications and local regulations may cause equipment damage and endangers life and
property. Tampering with the device and misapplication will void warranty.
Power supply
Operating voltage
Power consumption
Connection
Terminal connectors
Sensing method
CO2 measurement
Response time (90%)
Measurement range
Repeatability
Accuracy
Pressure dependence
Accuracy:
Temperature -
0...50°C (32...122°F):
measurement
50...60°C (122...158°F):
Note on accuracy: allow one hour after power up for compensation swing in
Signal outputs
Analog outputs
Output signal
Resolution
Maximum load
Environment
Operation
Climatic conditions
Temperature
Humidity
Transport & storage
Climatic conditions
Temperature
Humidity
Mechanical conditions
General
Degree of protection
Safety class
Material:
Dimensions (H x W x D)
Weight (including package)
Doc: 70-00-0794, V2, 20200311
Subjects to alteration
Description/Option
CO2 transmitter
0 Signal range: -40...60°C (-40...140°F) (Default)
1 Signal range: -35...35°C (-31...95°F)
2 Signal range: 0...50°C (32...122°F)
Description/Option
External display module square housing
Note: For the correct display of values V1.7 and later is required.
External display module rectangular housing
Note: For the correct display of values V1.7 and later is required.
Cover
Mounting plate
© Vector Controls GmbH, Switzerland
www.vectorcontrols.com
24 V AC 50/60 Hz ± 10%, 24 VDC ± 10%
SELV to HD 384, class II transformer, 48 VA max.
Max. 2 VA
For wire 0.34...2.5 mm
2
(AWG 24...12)
Non-dispersive infrared (NDIR) waveguide technology
with ABC automatic background calibration algorithm
2 Minutes
0 - 2000 ppm
vol.
± 20 ppm ± 1 % of measured value
± 40 ppm ± 3 % of measured value
+ 1.6 % reading per kPa deviation from normal
pressure, 100 kPa
0.5 K
1 K
DC 0-10 V or 0...20 mA
10 bit, 9.7 mV, 0.019.5 mA
Voltage signal: ≥1kΩ, current signal: ≤500Ω
To IEC 721-3-3
class 3 K5
0...50° C (32...122° F)
<95% RH non-condensing
To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class 1 K3
-30...70° C (-22...158° F)
<95% RH non-condensing
class 2M2
IP30 to EN 60 529
III (IEC 60536)
Fire proof ABS plastic
Galvanized steel
21 x 88 x 88 mm (0.8 x 3.5 x 3.5 in)
175 g (6.2 oz.)
SRC-C1T1
P
D
S
RODUCT
ATA
HEET
Page 2

Advertisement

loading