Technical Specifications - Vector SDC-C1 Quick Start Manual

Duct co2 transmitter
Table of Contents

Advertisement

Technical Specifications

Power supply
Operating voltage
Power consumption
Safety extra-low voltage (SELV)
Connection
Terminal connectors
Sensing method
CO2 measurement
Sampling method
Response time (90%)
Measurement range
Repeatability
Accuracy
Pressure dependence
Signal outputs
Analog outputs
Output signal
Resolution
Maximum load
Environment
Operation
Climatic conditions
Temperature
Humidity
Transport & storage
Climatic conditions
Temperature
Humidity
Mechanical conditions
Standards
Degree of protection
Safety class
Housing materials
Cover, back part
General
Dimensions (H x W x D)
Weight (including package)
Product testing and certification
Declaration of
Conformity
Doc: 70-00-0399A, V2.9, 20220405
Subject to change without notice
Transmitter case
Probe
Information on the conformity of our products can be found on our website
www.vectorcontrols.com
© Vector Controls GmbH, Switzerland
www.vectorcontrols.com
24 VAC 50/60 Hz ± 10%, 24 VDC ± 10%
Max. 2 VA
HD 384, class II
For wire 0.34...2.5 mm
Non-dispersive infrared (NDIR) waveguide technology
with ABC automatic background calibration algorithm
Diffusion
2 Minutes
0 - 5000 ppm
vol.
± 20 ppm ± 1 % of measured value
± 40 ppm ± 3 % of measured value
+ 1.6 % reading per kPa deviation from normal
pressure, 100 kPa
0...10 VDC, 0...20 mA or 2...10 VDC, 4...20 mA
10 bit, 9.7 mV, 0.019.5 mA
Voltage signal: ≥1kΩ, current signal: ≤250Ω
To IEC 721-3-3
class 3 K5
0...50 °C (32...122 °F)
<85% RH non-condensing
To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class 1 K3
-30...70 °C (-22...158 °F)
<95% RH non-condensing
class 2M2
IP30 to EN 60 529
III (IEC 60536)
PC+ABS (UL94 class V-0)
68 x 91 x 47 mm (2.7 x 3.7 x 1.9 in)
Ø 14 x 160 mm, (Ø 0.55 x 6.2 in)
290 g (10.2 oz.)
on the corresponding product page under "Downloads".
SDC-C1
D
CO2 T
UCT
RANSMITTER
2
(AWG 24...12)
Page 2-8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sdc-c1-16-140-300152

Table of Contents