Horizon Fitness T-2.5KW Manual page 18

Fuel cell ups solutions
Table of Contents

Advertisement

Page 17
When the system starts in manual mode, the system will never return to Standby. The front panel 
ON/OFF switch allows the user to manually turn the system on to generate power. And the only 
method to stop the unit is by pressing the switch again.  
When choose Primary Mode or Manual Mode, press enter to the next interface, then press enter 
again to start the system or press up key to reset the system mode.  
3) Low Volt Mode 
When the system starts in low volt mode, the unit will attempt to achieve an output voltage which 
is the value set in the Float Volt field. Once the system has achieved and held float voltage for a 
period of time (set in the Float Timer field), the unit will return to Standby. This mode functions as 
a battery charge mode, charging up an external battery to the float voltage, and then returning to 
Standby. When the  batteries discharge  to the low voltage threshold, the system will start  again. 
This charge/discharge method is useful for very small loads, where the battery is properly sized to 
support  the  small  load,  and  is  recharged  by  the  fuel  cell.  The  fuel  cell  system  will  operate 
"thermostatically",  turning  on  at  the  low  voltage  threshold,  and  turning  off  after  holding  the 
output at the float volt setting until the float timer expires. When primary power is restored to the 
site and the bus voltage is held at or above the float volt setting until the float timer expires, the 
unit will return to Standby and remain there, provided the bus voltage remains above the low volt 
threshold. 
 
Low volt mode is a useful option for off‐grid hybrid systems that are relatively low power. The fuel 
cell is used to charge the batteries, and the batteries then carry the load for extended periods. The 
total system solution is most efficient for small loads that are <5% of the fuel cell capacity, with an 
appropriately sized battery. 
 
When  started  in  low  volt  mode,  the  fuel  cell  will  deliver  power  until  the  output  bus  voltage 
reaches the user‐set float voltage (whether because the unit has sufficient power to support the 
load and charge the batteries, or because the external power was restored). Once the float voltage 
is achieved, a user‐adjustable float timer will start. When the float timer expires, the unit will stop 
delivering power and return to Standby. 
 
Low Volt Threshold in the user interface is used to set the voltage at which the system begins to 
operate when either Low Volt Mode is enabled. This voltage must be at least 0.5V below the value 
set in Float Volt.  
The low volt threshold range is from 43.2V to 53V (factory default is 48V). 
 
Float Volt in the user interface is used to set the voltage at which the system returns to Standby.  
And the range of float volt is from 50V to 57.6V (factory default is 52V). 
 
Float Timer in the User Interface is used to set the timer that determines the end of the float mode. 
Float  timer  can  be  set  from  5  to  120  minutes  in  5  minute  increments  (factory  default  is  30 
minutes).  
 
 Condition setting 
Copyright Horizon Fuel Cell Technologies – T‐2.5KW_UM_V1.5
Page 17

Advertisement

Table of Contents
loading

Table of Contents