Pulse Width
Measurement (*3)
B' 1110 ( 0xE )
Pulse Width & Period
B' 1111 ( 0xF )
Measurement (*4)
- Frequency Range of the Encoder x1 mode is the same as the counting mode.
- Frequency, B'1101 (0xD) can't be used with other channel's Count Mode = 0x0, 0x1, 0x4 ~ 0x9
- Pulse Width, B'1110 (0xE) measures Aph Input's High (On) Pulse Width(32bit) in 0.1usec unit.
- Pulse Width & Period, B'1111 (0xF) measures Aph's Pulse High (On) Width (16bit) & Period (16bit) in
0.1usec unit.
2.1.6 Configuration Parameter Data – 4byte
Byte
Bit 7
0
1
2
3
Simple Pulse Width Measurement, 0.1usec Unit
- Pulse Width(32bit), if 1234, then Pulse High(On) width is
123.4usec (*3)
- Aph Input acts as Pulse Input
- Bph Input is not used
Simple Pulse Width & Period Measurement, 0.1usec Unit,
- Available in case of Pulse Input >= 200Hz(<= 2.5msec,
Pulse On Width)
- Pulse Width(16bit, Low Word) + Pulse Period(16bit, High
Word) (*4)
- Aph Input acts as Pulse Input
- Bph Input is not used
Bit 6
Bit 5
Bit 4
Bit 3
Reserved
Reserved
Reserved
Reserved
HX-RIO3 Series
Bit 2
Bit 1
Bit 0