Ziton ZP755B-2 Installation Sheet
Ziton ZP755B-2 Installation Sheet

Ziton ZP755B-2 Installation Sheet

Addressable detector base sounder

Advertisement

Quick Links

ZP755B-2 Addressable Detector Base Sounder
Installation Sheet
Description
The ZP755B-2 is an addressable sounder designed for use in
Ziton addressable fire detection and alarm systems.
The sounder includes a volume control, an address-setting
switch, programmable tone settings, and a pair of jumpers to
select the operating power – from the addressable loop or an
external supply. The sounder plugs into a base that is
purchased separately. See Table 1 for a list of model numbers.
Table 1: Models
Model
Description
ZP755B-2P
Addressable detector base sounder, Polar white
SPB–2P
Plug-in base, Polar white
Installation
To install the device, follow these general steps.
1.
Wire the base.
2.
Set the operating power.
3.
Set the address.
4.
Set the mode of operation.
5.
Set the tone.
6.
Set the volume.
7.
Mount the sounder onto the base.
The details of each step are given below.
© 2021 Carrier. All rights reserved.
Wiring the base
Connect the loop wiring for the plug-in base as shown in
Figure 1 below. There is no wiring between the sounder and
plug-in base.
Figure 1: Loop wiring for the plug-in base
6
5
1.
Ext. 24 VDC+ IN/OUT
2.
Ext. 24 VDC ground IN/OUT
5.
Loop+ IN/OUT
Setting the operating power
The sounder includes a pair of power selection jumpers, J1
and J2. To select the source of the sounder operating power,
position the jumpers as show in Figure 2.
Figure 2: Power-selection jumper configuration
1
J1
J2
1.
Loop powered
Note:
When using an external power supply, use only one that
is CE and EN 54-4 compliant to power all the sounders on the
same loop.
Setting the address
The sounder includes a seven-segment DIP switch (SW1) for
assigning device addresses. Each switch segment represents
the value shown in Figure 3. The address is the sum of all the
switch segments in the ON position. The switch is used to set
1 / 4
6.
Loop − IN/OUT
7.
Shield
2
J1
J2
2.
External 24 VDC
P/N 10-4211-501-ZP5B-12 • ISS 05OCT21
1
2

Advertisement

loading

Summary of Contents for Ziton ZP755B-2

  • Page 1 Figure 1: Loop wiring for the plug-in base Description The ZP755B-2 is an addressable sounder designed for use in Ziton addressable fire detection and alarm systems. The sounder includes a volume control, an address-setting switch, programmable tone settings, and a pair of jumpers to select the operating power –...
  • Page 2 Setting the tone Tone Two different tones can be programmed to operate from the panel. In ZP755B-2 mode these tones are selected using SW2-1, SW2-2, and SW2-3. Refer to Table 3. Note: In the ZP panel I/O mapping menu, outputs are programmed as "steady"...
  • Page 3 Table 3: Tone settings SW2-6 device mode SW2 switch setting Device mode Mapping input type switch setting -1 -2 -3 Fast flash Steady Tone type Tone A primary/alert Tone B secondary/evac. ZP755 Intermittent Continuous ZP755 Continuous Intermittent ZP755 Continuous Two-tone ZP755 Two-tone Continuous...
  • Page 4 Dimensions (Ø × D) 127 × 69 mm disposed of as unsorted municipal waste Compatibility Ziton addressable systems in the European Union. For proper recycling, return this product to your local Addressing method 7-segment DIP switch...