Advertisement
Do not hesitate to contact us at info@ondico.see if you have opinions or comments on the unit and this manual.
Above the unit is shown without the cover of the cabinet. The figure is simplified in order to easy show the position of the components.
Ondico AB is not responsible for damages that may occur due to incorrect use or if the product does not work as desired.
The Alarmbox is sending status information at start up and then every twenty minutes. This information is stored until next status update or longest 60 minutes. This means that if the Alarmbox is disconnected or stops working it will take maximum 60 minutes until it disappears from SMS messages.
ID | Switch 6 | Switch 7 | Switch 8 |
ID2 | OFF | OFF | ON |
ID3 | OFF | ON | OFF |
ID4 | OFF | ON | ON |
ID5 | ON | OFF | OFF |
ID6 | ON | OFF | ON |
ID7 | ON | ON | OFF |
ID8 | ON | ON | ON |
When an alarm is activated an SMS will be sent to all mobile telephone numbers on the alarm list. The red LED is double blinking 1-3 times. Up to ten different persons can be alerted.
Below is shown an example of an alarm SMS.
Example | Explanation |
*Ontech9030 | Asterix (*) means the alarm function is activated. |
Alarm: | |
2a, 3b | Indicates all alarms that have been activated since the last acknowledge. A a after the ID number means it is a normal alarm. A b after the ID number means it is a low battery alarm. See below. |
Inputs: | |
2a | Indicates the ID of the units where the alarm sensor is still active. In this example it means the input in unit ID 2 is active and must be deactivated before you acknowledge the alarm. |
Units: | |
1; 2/24; 3/22 | Indicates the IDs for the units connected to the master unit. Also the temperature at each Alarmbox is indicated. |
Temp: | |
24; 24,2 | Indicates the temperature at the master unit. |
Tstat: | |
OFF | Indicates the status of the Thermostat function. |
If the battery is low the unit will send an SMS with a b after the ID number. Replace the battery.
When an alarm has been sent it has to be acknowledge before the unit can send another alarm.
First make sure that the alarm sensor is not active, that is for example shut an open door that is alarmed.
Then acknowledge by sending an SMS with the content ABCD#9#.
Below is shown an example of an status SMS and how it is interpreted.
Example | Explanation |
*Ontech9030 | Asterix (*) means the alarm function is activated. |
Units: | |
1; 2/24; 3/22 | Indicates the IDs for the units connected to the master unit. Also the temperature at each Alarmbox is indicated. |
Temp: | |
24; 24,2 | Indicates the temperature at the master unit. |
Tstat: | |
OFF | Indicates the status of the Thermostat function. |
Symptom | Reason |
The LED is blinking all the time | Dipswitches 6, 7 and 8 are all in position OFF. Set valid ID. |
Alarm messages is sent continuously | Check that the cable jumper is connected on the NC and GND connectors on the terminal (If NC alarm sensor is connected there shall be no jumper) |
The magnetic switch is not working | Check the distanse between the cabinet and the magnet. Check that the jumber is removed. |
Ontech Alarmbox 9012 is fully compatible with master units with software revision R7 or higher.
For master units with software revision R6 or lower the temperature will not be shown.
Alarmbox units ID will not be shown in status SMS more than one minute after an update has been sent from the Alarmbox to the master unit.
See master units manual for instruction of how to check the software revision.
If there is no radio connection between the master unit and the Alarmbox, first move the units to a distance of approx. 2 meters in order to ensure that the radio works.
Also check that the DIP switch 6 on the master unit is in OFF position.
If radio contact not can be established one Ontech Relay 9010 can be used as a repeater if placed between the master unit and the Alarmbox. See the manual for the master unit for further instructions.
Short range radio | Frequncy 2,4 GHZ Power max 1 mW |
Alarm inputs | Activated by closing or opening function. The magnetic switch is activated with the attached magnet. |
Power | Litium battery 1/2 AA, 3 V. Will operate the unit more than two years with normal usage. |
Temperature range | -20º C to +40ºC |
Ondico AB, Datavägen 14A, 436 32 Askim, Sweden, hereby declares that the product Ontech Alarmbox 9012 is in conformity with the provisions of the Radio & Teleterminal directive R&TTE 1999/5/EG..
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Thank you! Your question has been received!
Need Assistance?
Do you have a question about the Alarmbox 9012 that isn't answered in the manual? Leave your question here.