Operating manual DKS - classic DKS - expert Information for mounting General information Electrical installation and safety must correspond to local regulations. The control- ler is to left under continuing tension in order to guarantee functional readiness at any time. Pre-positioned power switches are, therefore limited to emergency or main switches which are usually left in the ’on position.
Operating manual DKS - classic DKS - expert Preparation of the assembly and start-up The two fixing screws can be seen in the front housing. 1. Wire and attach all electrical connectors. 2. The controller must be inserted into the intended installation cut-out and fixed by means of the 2 fixing screws.
Operating manual DKS - classic DKS - expert 1.4.2 1-stage heat generator without burner norm-connector • Unscrew and remove the cable with mating connector • Use the screw connectors of the panel controller Connection by the direct power supply of the heat generator screw connectors of the panel controller Power supply heat generator Dok.
Operating manual DKS - classic DKS - expert 1.4.3 Allocation of the connectors sensors part Connec- Abbr. Symbol Denomination tor No. eBUS eBUS eBUS Sensor heat generator Sensor domestic hot water Outside temperature sensor Flow temperature sensor heating circuit 1, green Setpoint value input analog 0-10V Solar panel sensor DHW tank bottom with solar application...
Operating manual DKS - classic DKS - expert Specialist notes to the operation Display check When first switching on or after a RESET the display appears temporary the soft- ware-version and all segments. 1. Software number 521822 Note: First zeros in the second line are not indicated. 2.
Operating manual DKS - classic DKS - expert Structure of the parameter levels The parameter levels and parameters are divided into three entrance stages: • uncoded: Level 1 to 3 (user and specialist) • code 1: Level 4 to 19 (specialist) •...
Operating manual DKS - classic DKS - expert Parameter levels Level 1 and 2 see the user operating manual doc. no. 112818. Service level In the service level a heating technician can make basic adjustments and queried functions which give information about the correct mode of operation of the plant. 3.2.1 Operating data "dat"...
Page 14
Operating manual DKS - classic DKS - expert Operation step Operation Display Select function "out" Select output function Example: A1 = burner stage I = "off" Select output function Example: A1 = burner stage I = "on" The standard display Select further relays or leave function Close cover appears...
Operating manual DKS - classic DKS - expert 3.2.3 Displaying the controller output ports Depending on the operating mode, some of these symbols will be shown. DHR - classic DHR - com- Designation fort Symbol heating circuit/generator (1=green; 2=red) green Generator I or burner stage I Burner stage II Heating circuit mixing valve open...
Operating manual DKS - classic DKS - expert 3.2.4 Change of parameters on level 3 Example: Room protection temperature (parameter 3-0) Note: Control steps apply also to following parameters! Operation step Operation Display Select the heating circuit (if switched ON, parameter 7-0) DKS expert DKS expert Select service level...
Operating manual DKS - classic DKS - expert Change of settings in the coded service levels 4 to 11 3.3.1 Example: Sensor configuration store (parameter 4-0) Note: Control expiration applies to all following adjusters! Operation step Operation Display Select the heating circuit (if switchet ON, parameter 7-0) DKS expert DKS expert...
Page 18
Operating manual DKS - classic DKS - expert Operation step Operation Display Select another function The selected function or or close the cover the standard display appears The setting is stored Dok. Nr. 112819 31/2011...
Operating manual DKS - classic DKS - expert General description of functions and parameters Level 3 - Heating circuits/Domestic hot water 4.1.1 Heating curve/base point (parameter 3-1) The heating curve indicates the relationship between the flow water and the out- side temperature, ΔTV/ΔTA.
Page 20
Operating manual DKS - classic DKS - expert Adjusting the heating curve slope and base point The heating curve is governed by the following adjustments: Function Symbol Basic setting performed by Slope Specialist (probably adjusting by user) Base point flow temperature Specialist Set point room temperature User...
Page 21
Operating manual DKS - classic DKS - expert Fine-adjusting the heating curve The slope of the heating curve becomes adjusted in the "2nd Level" and can be adapted if necessary also by the user. Room temperature Daytime outside temperature too cold to warm reduce by 0.2 and increase by 0.2 and...
Operating manual DKS - classic DKS - expert 4.1.2 Room-temperature compensation (Reinforcement room influence, p-part) (parameter 3-7) If the measured room-temperature deviates from the set value (e.g. on account of extraneous sources of heat, such as sunlight) the controller corrects the flow tem- perature in accordance with the value set for parameter 3-7.
Operating manual DKS - classic DKS - expert 4th level - Configuration of the plant These parameter settings have in influence on the entire plant. Parameter Code Function Memorise sensor configuration Calculation of average outside temperature eBUS address of heating circuit/DHW controller 5th level - Domestic hot water production 4.3.1 Basic function of domestic hot water production...
Operating manual DKS - classic DKS - expert 7th level - Heating circle function Basic adjustments are made for the heating circles (red/green). Further parame- ters can be adjusted in levels 1, 2 and 3. 4.4.1 Basic functions heating circle function In the heating mode and reduced heating mode the room temperature set...
Operating manual DKS - classic DKS - expert 4.4.2 Heating limits There are 3 heating limits which depend on the heating program. 1. normal heating mode (house) 2. reduced heating mode (parameter 3-2)"only with clock program " 3. heating limit heating circle flow (parameter 3-8) 1.
Page 26
Operating manual DKS - classic DKS - expert 3. Heating limit: "heating circle flow" The heating limit "heating circle flow" prevents the heating circle pump from run- ning, because the flow set point cannot heat the building. The switching off value results from the following values: •...
Operating manual DKS - classic DKS - expert 8th level - Solar function 4.5.1 Basic functions solar If the collector temperature is higher than the buffer temperature + increase "on" (parameter 8-1) the solar pump is switched on. If it is smaller than the buffer tem- perature + increase "out"...
Operating manual DKS - classic DKS - expert Overview of settings 3rd level Basic setting Adaptions Date: Date: Function Heating circuit Heating circuit X =active 1(green) 2 (red) 1(green) 2 (red) Room protection temperature 3 ÷15 °C It is valid for all heating modes if changed to holyday, standby, summer. With room temperature sensor (remote con- trol FS 5601) room temperature becomes reference temperature.
Page 29
Operating manual DKS - classic DKS - expert Basic setting Adaptions Date: Date: Function Heating circuit Heating circuit X =active 1(green) 2 (red) 1(green) 2 (red) Heating limit depending on calculated flow temperature -10 ÷60 setpoint value If calculated flow temperature setpoint is no more able to contribute to the heating (room temperature set point + set value), heating system is turned off.
Operating manual DKS - classic DKS - expert 4th level - Configuration of the plant Basic setting Adaptions Date: Date: Functions X = active Memorise sensor configuration on/off If all necessary sensors are wired, set this value to "on" thus to memorise sensor configuration. Then change setting level or close the front cover.
Operating manual DKS - classic DKS - expert 5th level - DHW production Basic setting Adaptions Date: Date: Function X = active DHW production parallel or prior on/off to heating 0.2÷20.0 According to the setting, DHW production is executed parallel, prior or parallel depending on the charge. on = absolutely parallel off = absolutely prior 20 ...
Operating manual DKS - classic DKS - expert 8th level - Solar functions Basic setting Adaptions Date: Date: Function X = active Switching difference ON 0÷40 If the temperature difference between collector TKO and storage tank bottom TPU or DHW tank bottom TBU is larger than the set point, the solar pump is switched on.
Operating manual DKS - classic DKS - expert 11th level - Parameters of heat generator Basic setting Adaptions Date: Date: Function 1(green) 2 (red) 1(green) 2 (red) X = active Cancel operating data on÷off Operating data can be reset to "0". off = standard 11-4 on = reset of operating dates to "0".
Operating manual DKS - classic DKS - expert 6.2.2 Unlock during error message See user operating manual doc. no. 112818. 6.2.3 Reload factory settings All uncoded and coded parameters of al levels can be reloaded on their factory settings per boiler/heating circle. Operation step Operation Display...
Operating manual DKS - classic DKS - expert Error message See user operating manual doc. no. 112818. Heating circulation pump functions The circulation pumps run when: • the outside temperature is below the heating limit • frost protection is activated (outside temperature is lower than 2°C) •...
Operating manual DKS - classic DKS - expert FS 5601 remote control 6.7.1 Connecting the FS 5601 remote control Connection allocation m u l t i Allocation of the connectors Room devices Data bus earth Data bus signal 6.7.2 Start-up of the FS 5601 remote control Before the eBUS connection is attached, the controller must be switched without tension.
Operating manual DKS - classic DKS - expert 6.7.3 Operating with FS 5601 remote control The connection of a FS 5601 remote control is not indicated particularly in the dis- play on the controller, it is however recognizable from the measured room tempe- rature appearing on the display at the 2nd Level (cover open).
Operating manual DKS - classic DKS - expert Technical data General data Supply voltage 230 VAC + 10 %, 50 Hz Power consumption max. 10 VA Operational ambient temperature 0 °C ... 50 °C Ambient temperature camp/transport -20 °C ... 60 °C Humidity in the enterprise max.
Operating manual DKS - classic DKS - expert Checking temperature sensors All temperature sensors for DKS classic /- expert have the same characteristic (NTC, 5000 Ω with 25 °C). The resistance values are shown in the following table. Resistance Ω...
Operating manual DKS - classic DKS - expert Explanation of terms and abbreviations Actual value measured value (temperature) DHW circulation pump Domestic hot water eBUS 2-wiring data bus for the heating technology Firing controller (modulating, eBUS) Remote control FS 5601 Gen.1 Heat generator sensor 1 Ground...
Operating manual DKS - classic DKS - expert INDEX Operating with FS 5601/FB 5811 remote Aligning of set and actual control .......... 38 temperatures ........ 21 Allocation of the connectors sensors part ........9 Parameter levels ......... 13 Assistance for start-up and elimination of Pump protection ........