T6 PV CONNECTOR
T4 PV CONNECTOR
INSTALLATION MANUAL
INSTALLATION
MANUAL
For professional use only

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the T6 and is the answer not in the manual?

Questions and answers

Summary of Contents for Tlian T6

  • Page 1 A Canadian Solar subsidiary T6 PV CONNECTOR T4 PV CONNECTOR INSTALLATION MANUAL INSTALLATION MANUAL For professional use only...
  • Page 2: Table Of Contents

    T6 CONNECTOR PARTS T6 PRODUCT SPECIFICATIONS T6 INSTALLATION PARAMETERS SAFETY PRECAUTIONS T6 FIELD TOOLKIT CONNECTOR & WIRE ASSEMBLY STEPS THE CORRECT CONNECTION DISCONNECTING THE CONNECTORS AMENDED EDITIONS AND DATES LIST OF FORBIDDEN CHEMICAL SUBSTANCES UL-Rev IM-TC-UL/1.1 Copyright © Feb.2023. Tlian Co., Ltd.
  • Page 3: T6 Connector Parts

    1. T6 CONNECTOR PARTS ① Item Part Name ② PV Cable ③ Male Pin Contact (-) ① Male Connector (-) Female Socket Contact (+) Female Connector (+) ④ ⑤ 2. T6 CONNECTOR SPECIFICATIONS Male Connector (-) Male Pin Contact (-)
  • Page 4: T6 Installation Parameters

    4. SAFETY PRECAUTIONS • CAUTION1 : The exposure to or direct contact with chemicals or oils of T6 Products must be assembled and installed by qualified product may cause corrosion, degradation of performance, or personnel, ensuring all safety regulations are followed. For...
  • Page 5: T6 Field Toolkit

    5. T6 FIELD TOOLKIT Wire crimping tool Mark Riveting Range 4.0/12 4.0 mm 12 AWG 6.0/10 6.0 mm 10 AWG 10.0/8 10.0 mm 8 AWG Wire striper (14/12/10AWG) Cutting pliers Metal wrench Wire striper (8AWG) Wire crimping tool T6 disconnect...
  • Page 6: Connector & Wire Assembly Steps

    7.5 mm , and for 10mm² cable, the length is 9mm,and that the ≥380 N. wire strands are not damaged during the process of stripping Crimp range the insulation. UL-Rev IM-TC-UL/1.1 Copyright © Feb.2023. Tlian Co., Ltd.
  • Page 7 STEP 6: CONNECTING THE CONNECTORS Check the appearance of the connectors before connecting them together. The sealing ring should be in the slot with no warping or distortion. The plastic clasps should not be damaged or broken. The connectors should be free of moisture and foreign objects.
  • Page 8: The Correct Connection

    The technical descriptions herein are only for connector, and the female connector will automatically get reference when using these products. disconnected . Clasp of the dis- connect tool Automatically disconnected Insert into the slot UL-Rev IM-TC-UL/1.1 Copyright © Feb.2023. Tlian Co., Ltd.
  • Page 9: List Of Forbidden Chemical Substances

    APF125 (Wacker Chemical), 3M adhesive, Avancis adhesive. Remarks: For any chemical not listed above that may come into contact with any T6 product,it is the user's responsibility to validate that such chemical will not affect the performance of T6 products.
  • Page 10 10 | TLIAN CO., LTD. www.csisolar.com UL-Rev IM-TC-UL/1.1 Copyright © Feb.2023. Tlian Co., Ltd.