Intrinsically safe intelligent photo electronic smoke sensor

Advertisement

Available languages

Available languages

TC842B1007 System Diagram
SAFE AREA
IST200
Control
Translator
Panel
Module
S a f e a r e a a p p a r a t u s , w h i c h i s
unspecified except that it must not be
supplied from or contain under normal
or abnormal conditions a source of
potential with respect to earth in excess
of 253 Vrms or 253 VDC
Maximum Permissible Capacitance,
Inductance and Impedance Figures Across
Terminals 1 and 2 on a B501AP Base
Capacitance
Inductance
Group
µF
mH
IIC
0.083
4.2
IIB
0.65
12.6
IIA
2.15
33.6
Table 1
EU DECLARATION OF CONFORMITY
Date of issue:
Manufacturer:
Products:
Model No
22051EISE
B501AP
We hereby declare that the product identified above meets the requirements of the following EU
Directives and therefore qualify for free movement within markets comprising the European Union
(EU) and the European Economic Area (EEA).
This declaration is issued under the sole responsibility of the manufacturer.
EMC Directive 2014/30/EU
Conforms to:
ROHS Directive 2011/65/EU
Conforms to:
ATEX Directive 2014/34/EU
Conforms to:
Notified Body:
Notified Body No:
Rating:
For and on behalf of
Pittway Tecnologica S.r.l.
Marco Corti
Plant Manager
HAZARDOUS AREA
(See Note 2)
Shunt Zener
Diode Safety
Barrier or
Isolation
Barrier (see
Note 1.)
4 (+)
2 (+)
B501AP
2 & 4 linked in base
TC842B1007
Smoke Detector
II1G Ex ia IIC T5, T4
Baseefa08ATEX0278X
L/R Ratio
B501AP Pins
µH/Ohm
55
1
210
2
444
4
Table 2
7 April 2016
Pittway Tecnologica Srl
Via Caboto 19/3
34147 TRIESTE
Italy
Description
Variants
Optical Smoke Detector
IDX-751, TC842B1007
Detector Base
-
EN 50130-4: 2011
EN 55022: 2010
EN 50581: 2012
EN 60079-0: 2012 + A11: 2013
EN 60079-11: 2012
SGS BASEEFA Limited
Rockhead Business Part, Staden Lane
Buxton, Derbyshire, SK19 9RZ.
1180
Ex II 1 G EEx ia II C T5, T4
Pittway Tecnologica S.r.l.
a socio unico
Via Caboto 19/3
34147 TRIESTE (Italy)
Tel: +39-040-9490111
Fax: +39-040-382137
Notes:
1. Any single channel shunt zener diode safety barrier or single channel of a dual
channel shunt zener diode safety barrier certified by Baseefa or any EEC approved
certification body to [EEx ia] IIC having the following or lower output parameters:
Uz = 28V; Imax: out = 93.3 mA; Wmax: out = 0.66 W
To Next
In any safety barrier used, the output current must be limited by a resistor "R", such
Detector(s)
that Imax:out = Uz/R. Or any of the following isolation barriers may be used:
P & F Smart Fire Detector Isolator Type KFDO-CS-Ex1.54-Y72221
One channel from: P & F Smart Fire Detector Isolator Type KFDO-CS-Ex2.54-
Y72222 (BAS00ATEX7087X)
2. The capacitance and either inductance or inductance/resistance (L/R) ratio of the
1 (-)
cable connected to the hazardous area terminals of barrier must not exceed the
values shown in Table 1.
3. The installation must comply with the appropriate national installation requirements,
e.g. in the U.K. to BSEN60079-14: 1997.
4. The electrical circuit in the hazardous area must be capable of withstanding an
A.C. test voltage of 500 VRMS to earth or frame of the equipment, for a period of
one minute without breakdown. This note does not apply when using an isolation
barrier.
Connection
Please refer to control panel installation instructions for specific
-V IN, -V OUT
+V IN
+V OUT
N. IVA IT 00744320326
Reg. Impr. TS n. 10331 Trib. TS
R.E.A. N. 97799
Cap.Soc. € 1.368.619,00 int. vers.
P.IVA e Cod. Fisc. 00744320326
DOC-S200IS Rev 00
Page 1 of 1
CAUTION
barrier/control panel compatibility information.
R12-172-00, REV G

Advertisement

loading

This manual is also suitable for:

Tc842b1007