• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *: Sound pressure level:
– Measured values in manufacturer's anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-5. Ceiling type
kW class
W
A
HIGH
MED
LOW
QUIET
3
m
/h
HIGH
MED
LOW
QUIET
W
HIGH
MED
LOW
QUIET
dB (A)
HIGH
MED
LOW
QUIET
dB (A)
mm
mm
mm
kg
mm (in)
mm
°C
%RH
°C
ABYG18KRTA
1Ø 230 V ~50 Hz
198—264 V
5.0
37
0.21
840
790
710
650
840
790
710
650
Sirocco × 2
50
38
36
33
31
38
36
33
31
53
53
294 × 715 × 39.9
1.30
3 × 14
Copper
Aluminum
Steel sheet
White
Approximate color of Munsell N9.25/
235 × 1,080 × 705
330 × 1,165 × 825
24
33
Ø6.35 (Ø1/4)
Ø12.70 (Ø1/2)
Flare
PVC
Ø25 (I.D.), Ø32 (O.D.)
18 to 32
80 or less
16 to 30
Wired remote controller, Wireless remote controller, Mobile app*3 (FGLair