General; Setting Equipment - Lennox A96DFMV Installation Instructions Manual

Warm air gas furnace downflow air discharge
Table of Contents

Advertisement

Air filters must be replaced upon construction completion.
The input rate and temperature rise must be set per the
furnace rating plate.
One hundred percent (100%) outdoor air must be provided
for combustion air requirements during construction.
The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly
cleaned following final construction cleanup.
All furnace operating conditions (including ignition, input
rate, temperature rise and venting) must be verified
according to these installation instructions.

General

WARNING
Product Contains Fiberglass Wool.
Disturbing the insulation in this product during
installation, maintenance, or repair will expose you to
fiberglass wool. Breathing this may cause lung cancer.
(Fiberglass wool is known to the State of California to
cause cancer.)
Fiberglass wool may also cause respiratory, skin, and
eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets available
from address shown below, or contact your supervisor.
Allied Air Enterprises, Inc.
215 Metropolitan Drive
West Columbia, SC 29170
CAUTION
These units should not be installed in areas normally
subject to freezing temperatures.
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
Page 6 of 52
In addition to the requirements outlined previously, the
following general recommendations should be considered
when installing one of these furnaces:
Place the furnace as close to the center of the air
distribution system as possible. The furnace should also
be located close to the chimney or vent termination point.
When the furnace is installed in an attic or other insulated
space, keep insulation away from the furnace.
When the furnace is installed in an unconditioned space,
consider provisions required to prevent freezing of
condensate drain system.
Installation – Setting Equipment
Do not install the furnace on its front or its back. See
Figure 5. Do not connect the return air ducts to the
back of the furnace. Doing so will adversely affect the
operation of the safety control devices, which could
result in personal injury or death.
Select a location that allows for the required clearances that
are listed on the unit nameplate. Also consider gas supply
connections, electrical supply, vent connection, condensate
trap and drain connections, and installation and service
clearances (24 inches [610 mm] at unit front). The unit must
be level from side to side, for proper operation. It is
recommended to tilt the unit slightly toward the drain to insure
proper drainage. See Figure 4.
Front
View
Unit must be level side to side in all applications for proper operation. A slight tilt
toward the drain is recommended for proper drainage.
Figure 5
Issue 1034
WARNING

SETTING EQUIPMENT

Figure 4
Side View
506552-01