The HeatMaster ® 71 - 101 - 201 models are always supplied with a low NOx air/gas pre-mix burner ACV BG 2000-M. Indeed, if it is used in combination with Smart, HR and Jumbo cylinders, the HeatMaster ®...
Page 5
DESCRIPTION HeatMaster ® 71 / 101 Cold water inlet and filling loop connection Auto-air vent Primary NTC 1 and 2 sensors Primary expansion tank (2x) Filling loop connection to primary circuit Low-water pressure switch Thermometer bulb and pressure gauge connection...
In normal operation, the burner starts automatically as soon as the boiler drops below the temperature setpoint. The user must not attempt to gain access to the components inside the control panel. ® HeatMaster control panel 1. Temperature-pressure gauge 2. Display - MCBA controller 3.
USER GUIDE SETTING THE PARAMETERS • Domestic hot water temperature instruction: • Enabling and disabling central heating mode: (Central heating) (Hot water temperature) - Press “mode” key once: the screen displays “PARA”. - Press the “mode” key once: the screen indicates “PARA”. - Press the “step”...
X8: Flat cable connection for alarm module AM3-2 and / or AM3-11 heating circuit control module The AM3-2 and AM3-11 alarm modules are only an option for the HeatMaster ® 71 / 101models. Connection for transformer EN • 10 664Y2500.B...
Page 11
ATTENTION: This parameter can only be changed by approved ACV contractors. Alarm module kit (optional) Codes AM3-2 : 10800094 AM3-11 : 10800095 HeatMaster ® 71 / 101 Panel 1. Alarm module flat cable connection (option) 2. AM3-2 module (option) 3. AM3-11module (option) EN • 11 664Y2500.B...
ACCESSIBILITY The appliance must be placed in such a way that it is always easily accessible. Furthermore, the unit must have the following minimum clearance around it. HeatMaster ® 71 - 101 HeatMaster ® Min. 100mm Min. 100 mm Min. 100mm Min.
In order to avoid this risk, it is strongly entering the boiler. recommended that your chimney is insulated. Ventilations HM 71 HM 101 HM 201 To avoid condensation water flowing from the terminal, Minimum supply of fresh air...
Page 17
INSTALLATION HeatMaster ® 71 - 101 A. High ventilation B. Low ventilation C. Draught regulator D. Inspection cover E. Height of the lined chimney F. Diameter of the chimney HeatMaster ® A. High ventilation B. Low ventilation C. Draught regulator D.
11. Primary circuit filling valve 12. Temperature and pressure safety valve (UK only) If there is a risk of low pressure in the hot water circuit (installation of HeatMaster ® on the roof of a building), it is essential to install a vacuum breaker device onto the cold water supply.
71/101/201 boilers are equipped with - Purge the gas pipe and carefully check that there are no a BG 2000-M 71/101/201burner with a gas Ø 3/4” - 1” leaks on the boiler’s internal and external pipes. and 1”1/4 connection [F] to connect a gas supply valve.
• The BG 2000-M burner installed on HeatMaster ® models is The burner’s main components are: controlled by a MCBA Honeywell controller which manages...
Page 21
If necessary adjust the CO by turning the screw in the Conversion to propane: clockwise direction to reduce and the anti-clockwise to increase. (see photo) Prohibited in Belgium. BG 2000-M/71 - 101 BG 2000-M/201 Increase Increase Reduce Reduce EN • 21...
BRINGING INTO SERVICE FILLING OF DHW AND HEATING CIRCUITS IMPORTANT It is essential that the DHW cylinder is filled and pressurised before filling the heating circuit. Open the stop valve (1) and the outlet (8). Put the general switch to the ON position. When the water flows from the outlet, the DHW cylinder is Adjust temperature set points via the MCBA display.
MAINTENANCE ANNUAL MAINTENANCE Drainage of the heating circuit ACV recommends that the boiler is inspected and serviced, 1. Turn the general switch on the control panel to OFF position, isolate the external electrical supply and close the gas including the burner, at least once a year by a competent and supply valve.
MCBA PARAMETERS FOR THE SPECIALIST STANDBY MODE Once the cause of the blocking has been resolved, the burner starts up automatically after a maximum of 150 seconds. Standby Mode Status Boiler function When the boiler is switched on, it starts up in Stand-by mode, as Internal adjustment —...
To activate the modified parameters, press “MODE” key again (this will switch you to Info mode). However, if you do not press any key, the system returns to Standby mode after 20 minutes and activates the changes. Display MODE Factory setting Display Description of the parameters HM 71 HM 101 HM 201 Setting the hot water temperature STEP 00 = Off Hot water...
MCBA PARAMETERS FOR THE SPECIALIST INFORMATION ON THE INSTALLATION ENTERING THE CODE Info mode Code mode To switch from Standby mode to Info mode, You can access the following parameters press twice on “MODE” by entering the service code: • Parameters 5 through 42 Display •...
Page 27
SETTING THE PARAMETERS: Factory setting only accessible with the code Display Description of the parameters HM 71 HM 101 HM 201 Minimum boiler temperature using outdoor sensor To avoid problems with the hot water function it is not advised to adjust this parameter below 60°C...
Page 28
MCBA PARAMETERS FOR THE SPECIALIST Factory setting Display Description of the parameters HM 71 HM 101 HM 201 Natural gas Min. fan speed [rpm] Propane STEP Natural gas Max fan speed during ignition [rpm x 100] Propane STEP Central heating pump over run 0 = 10 sec.
Page 29
STEP - circulator controlled by the room thermostat - DHW priority is not active. DHW production type: This parameter cannot be modified in any way on a HeatMaster ® STEP Manual fan speed (- 01 = modulation enabled) STEP Not used...
Page 30
MCBA PARAMETERS FOR THE SPECIALIST COMMUNICATION MODE [with code] ERROR MODE [with code] This mode displays communication between the boiler The ERROR mode indicates the most recent error, as well and the control module, the optional interface kit as the status of the boiler and the temperature values at or the optional programmable room thermostat.
Page 31
MCBA PARAMETERS FOR THE SPECIALIST LIST OF ERROR CODES + SOLUTIONS To unlock the system: [in ERROR mode] • Press “RESET” on the screen. • If the fault is repeated continually, contact your If a fault occurs during operation, the system locks out installer.
Page 32
MCBA PARAMETERS FOR THE SPECIALIST Codes Description of the fault Resolution of the fault - Check the connection of the NTC 3 sensor - Check the wiring of the NTC 3 sensor Short circuit NTC 3 If the problem persists replace the NTC 3 sensor - Check the connection of the NTC 1 sensor - Check the wiring of the NTC 1 sensor NTC 1 connection open...
Page 42
537D6211 537D6224 Ø 150 mm Ø 150 mm 537D6212 Ø 150 mm 537D6225 Ø 150 mm 537D6219 537D6210 Ø 150 mm - 45°Mm Ø 150 mm 537D6214 Ø 150 mm - L 250 mm 537D6215 Ø 150 mm - L 500 mm 537D6216 Ø...