Water Pump - LG Therma V AHBW A0 Series Service Manual

General svc manual
Table of Contents

Advertisement

Checking Key Components of Unit

1.2 Water Pump

Water pump always
running while system
operation
DIP Switch No.5
is set to OFF ?
Water pump
control by
is not correct
* : It is normal condition that water pump runs or stops during system operation (including compressor start-up)
due to specific control logic.
• Water pump does not because of mechanical defects of water pump or wrong wiring at the water pump.
• To correct mechanical defects, contact official After Service Center and replace the water pump.
• To correct wrong wiring, check if wires ʻCN_W/PUMP (A)ʼ connector on the unit PCB and water
A
pump terminal box (black plastic box at the water pump) are connected firmly. Also, check wires are
electrically connected by measuring resistance of each wires (if electrically connected exactly, resis-
tance should be 0 ohm).
• Unit PCB can not make control signal or wrong wiring at the water pump.
• To correct unit PCBʼs making control signal, first check the signal level. Use electric voltage meter
and measure voltage at ʻCN_W/PUMP (A)ʼ connector on the unit PCB. If measured value is not
B
220 V ~ 240 V AC while ʻWater Pump Operating Icon (
PCB is in trouble. In this case, contact official After Service Center and replace the unit PCB.
• To correct wrong wiring, please refer Ⓐ.
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Start
*Water pump runs
NO
compressor start-up
YES
NO
Heating
Operation
YES
NO
YES
unit PCB
B
NO
and stops while
YES
END
(it is normal
condition)
)ʼ is displayed at control panel, the unit
- 38 -
NO
Water pump always
stop while system
operation
YES
Water pump does
not working
A