C2000-A1-PAX0400-EX1 User Manual 1. Getting Started 1.1. Preparation Before Use You will need the following hardware and software to use the C2000-A1-PAX0400-EX1. • C2000-A1-PAX0400-EX1 module • A power source that provides 9 to 27 VDC, and several wires • A PC running a Windows 7 or later versions, and an Ethernet cable •...
1.3. Software Installation & Device Debugging 1.3.1. Software Installation Download the software on URL: https://www.sinoconsys.com/en/download/?file=sdk. Unzip the folder and run KonNaD.Setup.exe as administrator. The setup wizard will pop up to direct you to complete the installation. 1.3.2. Device Debug Search Devices Select Search for serial devices and click Edit button to set the search parameters: ·...
C2000-A1-PAX0400-EX1 User Manual Note: if no device can be found. • Check whether to install and run as administrator ; • Check whether the RS485 to USB converter is correctly connected to the device and whether the converter is faulty;...
Page 7
C2000-A1-PAX0400-EX1 User Manual Refer to Software Tools for more detailed information. Refer to Registers for information on "Secondary Development". SinoCon Co., Ltd. www.sinoconsys.com 7 / 25...
C2000-A1-PAX0400-EX1 User Manual 2. Hardware Description 2.1. Specifications Classification Parameter Specification Analog Input AI Channels Connector Lead wire input Acquisition Range 0-20/4-20mA Acquisition Accuracy 3‰ Resolution 12 bit Acquisition Characteristics Single input Acquisition Frequency 500Hz Input Impedance 240Ω Upstream Serial Port...
C2000-A1-PAX0400-EX1 User Manual 2.3. Indicators Classification Indicator Description Meaning Downstream RS485 data Steady on:RS485 line fault, please check if the positive Serial Port receive and negative poles of 485 line are reversed indicator Flashing:RS485 receiving data Off:RS485 no receiving data RS485 data Flashing:RS485 transmitting data...
C2000-A1-PAX0400-EX1 User Manual 2.4. Port Description Recommended Classification Port Description wiring Analog Input Analog input RVV 2*0.5 Analog input common RVV 2*0.5 Upstream Serial 485+、 RS485+, RS485- (upstream) RVSP 2*0.5 Port 485- Power Input V+、V- Power supply input positive, power supply input RVV 2*1.0...
C2000-A1-PAX0400-EX1 User Manual 3. Product Features 3.1. AI Data Acquisition 3.1.1. AI channels: The device can acquire 0-20mA or 4-20mA current with a resolution of 12 bits. Note: There are two ways to read the current value acquired by the device: ·...
C2000-A1-PAX0400-EX1 User Manual 4. Software Tools 4.1. Main Screen The main screen displays the results of a broadcast search for C2000-A1-SDD1010-AB3. Main Screen 1. Set: Set the device parameters 2. Remote Set: For Ethernet type devices, when the device is in the LAN but crosses multiple routers and cannot be searched, the device parameters can be modified through Remote Set.
C2000-A1-PAX0400-EX1 User Manual 6. Search for Ethernet devices: Used to search Ethernet type devices 7. Search for serial devices: Used to search serial port devices 8. Listening settings: Used to connect the device in client mode to the software tool.
C2000-A1-PAX0400-EX1 User Manual · Model: Unchangeable; · Version: Unchangeable; · Name: You can modify the device's name; · Address: The RS485 address for the device ranges from 1 to 255. 4.2.2. View Device Status Click Refresh at the bottom left screen to view the device point value information, as shown below: SinoCon Co., Ltd.
Page 17
C2000-A1-PAX0400-EX1 User Manual · AI1 ~ AI4 Engineering quantity: AI Engineering quantity point value on the software divided by 1000 is the actual current value. For example, the "11996.34" for AI1 Engineering quantity means the measured current is 11.996mA. SinoCon Co., Ltd.
C2000-A1-PAX0400-EX1 User Manual 4.2.3. Control Device Status The software can change the state of the device by changing the value. For example, you can set "AI sampling range" to "0~20mA" or "4~20mA" by clicking the "edit icon" behind the Value.
C2000-A1-PAX0400-EX1 User Manual 5. Protocol The device uses the standard Modbus RTU protocol. If you have any questions about the protocol, you can refer to the relevant Modbus documentation or consult with our customer service. 5.1. Registers Start Number Parameter Name...
C2000-A1-PAX0400-EX1 User Manual 40017 Parity 0: None (default) 1: 0x03,0x06,0x10 Odd 2: Even Writing other value is invalid. 40018 Restart The first time 0x06,0x10 write 0xa55a, the second time write 0x5aa5 within 2s, the system restarts. 40019 Write 0x5A01 0x06,0x10...
C2000-A1-PAX0400-EX1 User Manual 0x0004 19200 0x0005 38400 0x0006 57600 0x0007 115200 5.2. Examples 5.2.1. Read AI Engineering Quantity Status (0x03) Assume that the RS485 address of the device is 1, take the case of acquisition 4 channels AI as an example. The...
Page 23
C2000-A1-PAX0400-EX1 User Manual Function 1 Byte, 03 = Read Code Length 2 Bytes, number of following bytes Field 00000000000000004000469C4000469C Data 4 Bytes, AI1-AI2: 00000000 AI3-AI4:4000469C high 2 bytes: 469C low 2 bytes: 4000 469C4000(H) = 20000(D) = 20mA(20000/1000) 191A 2 Bytes, CRC16...
C2000-A1-PAX0400-EX1 User Manual 7. Warranty Policy In the normal use of the products you purchased, free warranty service will be provided from the date of purchase whenever the quality problems caused by raw materials or production process are concerned. However, due to the user's failure to install, disassemble or improperly use the product according to the requirements of this product manual, the company provides maintenance services, but charges appropriate maintenance fees.