Page 1
WO 2004/051591, DE 103 01 678 A1, DE 10309334, WO 04/109236, WO 05/096482, WO 02/095707, US 6,747,573, US 7,019,241 Subject to modifications EnOcean GmbH Phone +49.89.67 34 689-0 Kolpingring 18a +49.89.67 34 689-50 STM 300 / STM 300C User Manual V1.26 82041 Oberhaching info@enocean.com...
Page 2
This information describes the type of component and shall not be considered as assured characteris- tics. No responsibility is assumed for possible omissions or inaccuracies. Circuitry and specifications are subject to change without notice. For the latest product specifications, refer to the EnOcean web- site: http://www.enocean.com.
STM 300 / STM 300C GENERAL DESCRIPTION Basic functionality The extremely power saving RF transmitter module STM 300 of EnOcean enables the realization of wireless and maintenance free sensors and actuators such as room operat- ing panels, motion sensors or valve actua- tors for heating control.
WAKE1 pin (LRN input) With this special teach-in telegram it is possible to identify the manufacturer of a device and the function and type of a device. There is a list available from the EnOcean Alliance describing the functionalities of the respective products.
V1.26 STM 300 / STM 300C Antenna options 3.5.1 Overview Several antenna types have been investigated by EnOcean. They all have advantages and disadvantages as shown in the following table. Advantages Disadvantages Whip Antenna (15 cm @ 315 MHz, 8.5 cm @ 868 MHz)
False ceilings with panels of metal or carbon fiber Lead glass or glass with metal coating, steel furniture The distance between EnOcean receivers and other transmitting devices such as comput- ers, audio and video equipment that also emit high-frequency signals should be at least 0.5 A summarized application note to determine the transmission range within buildings is available as download from www.enocean.com.
The conformity has been proven and the ac- cording documentation has been deposited at EnOcean. The modules can be operated with- out notification and free of charge in the area of the European Union and in Switzerland.
United States without additional Part 15 FCC approval (ap- proval(s) for unintentional radiators may be required for the OEM’s finished product), under EnOcean’s FCC ID number. This greatly simplifies and shortens the design cycle and devel- opment costs for OEM integrators.
Page 38
STM 300 / STM 300C OEM Requirements In order to use EnOcean’s FCC ID number, the OEM must ensure that the following condi- tions are met. End users of products, which contain the module, must not have the ability to alter the firmware that governs the operation of the module.
STM 300 / STM 300C IC (Industry Canada) certification In order to use EnOcean’s IC number, the OEM must ensure that the following conditions are met: Labeling requirements for Industry Canada are similar to those required by the FCC. The Original Equipment Manufacturer (OEM) must ensure that IC labeling requirements are met.