Possible reason:
Wrong wire connection
IPM malfunction
Compressor malfunction
Faulty PCB
Troubleshooting and repair:
a) Check the wiring between PCB and compressor.
b) Check the outdoor unit fan and ventilation.
c) Check the IPM in PCB.
d) Check the resistance of compressor.
e) If all are normal, change a new PCB.

2.4.20 P7 IDU anti-frosting protection

Description: indoor unit evaporator temperature T2 is lower than 0℃.
Possible reason:
Filter or evaporator is dirty
Indoor fan motor can't work normally or the flap is closed
Troubleshooting and repair:
a) Clear the filter and evaporator
b) Check the fan motor

2.4.21 P8 High IPM temperature protection

Description: the detected temperature of IPM is higher than 100℃.
Possible reason:
Power supply issue
System leakage or block
Faulty outdoor unit PCB
Connection problem
Troubleshooting and repair:
d) Check the power supply.
e) Check the fastening screws on the PCB and IPM radiator. If they are not fixed tightly, tighten the
screws and apply silicon grease. Otherwise, go to next step.