Table of Contents 1.0 General Information 6.8 Configuration Screens Fan Configuration 2.0 Configuration Chart Preheat and Post Heat Configuration Cooling and DX Configuration 3.0 Specifications Filter and Damper Configuration General Configuration 3.1 System Overview myDC Control App 3.2 General Specifications 3.3 Electrical - DOAS/ERV 7.0 Alarm List 3.4 Fan and Core Performance...
Operation and Maintenance Manual Nova Series 1.0 General Information Warnings and Caution This manual includes important instructions for safe installation, operations and maintenance of the Energy Recovery Ventilator (ERV). Before installing the ERV, Warnings and cautions appear at the appropriate please read carefully and follow all of the instructions sections throughout this manual.
Operation and Maintenance Manual Nova Series 2.0 Configuration Chart The following is a complete description of the packaged ERV/HRV model numbers and nomenclature. Main Code: NOVA_XXX_XXX_X_X_X_X_XX_X_XX_XX_XX_XX_XXX_XX_XX_X_X_X NOVA_A16_ERV_B_I_R_H_S1_ND_01_02_3A_04_2401_13_08_2_1_A Sales Drawings: NOVA_A16_ERV_B_I_R_H_S1_ND_01_02_3A_04_A 1A (Optional) Upper Outlet Air Connection Straight - 01 3A (Optional)
Operation and Maintenance Manual Nova Series 3.0 Specifications 3.1 System Overview Standard units come complete with energy recovery option, EC fans, 2" filters, fully integrated controls and casing as outlined in the spec below. 3.2 General Specifications Standard Features Warranty...
Operation and Maintenance Manual Nova Series 3.3 Electrical ― DOAS/ERV Model Nom. V. Motor SA Fan FLA SA Fan FLA Tnsfmr FLA MROP D Rcmd Fuse A16/A18 2.50 2.50 0.29 5.91 8.41 B20/B22 0.78 3.90 3.90 0.29 9.06 12.96 B20/B22 2.00...
Operation and Maintenance Manual Nova Series 4.0 Configuring Controls 4.1 Setting the Fan Operating Points Setting Control Functions Under the “Fan Configuration" tab, you can set the way in which fans and air volumes are to be controlled and regulated.
Page 20
Operation and Maintenance Manual Nova Series Constant Air Volume Constant VOC • Supply and return fans are controlled in relation • The system must be configured with a VOC to flow/air volumes in the Supply and return sensor. ducts respectively.
Operation and Maintenance Manual Nova Series 4.2 Fan Control: Constant Air Volume Supply Return 1.10 Supply Air Fan Low Speed 1.20 Supply Air Fan Low Speed • Set the required setpoint for supply flow at "Low" • Set the required setpoint for return flow at "Low"...
Operation and Maintenance Manual Nova Series 4.3 Fan Control: Constant Pressure Return Slave Supply Return 1.31 Supply Air Fan Low Speed 1.30 Return Air Fan Speed Offset • Set the required setpoint for Supply flow at "Low" • Return air volume follows supply air volume with speed an offset corresponding to the value set.
Operation and Maintenance Manual Nova Series 4.4 Fan Control: Constant CO2 The function is used to maintain a constant/maximum CO2 level in a room or return duct. If the CO2 level is higher than the setpoint, return volume will be increased in a modulated fashion to “Return Air Fan High Speed”...
Operation and Maintenance Manual Nova Series 4.5 Fan Control: Constant VOC The function is used to maintain a constant/maximum VOC level in a return duct. If the VOC level is higher than the setpoint, return volume will be increased in a modulated fashion “Return Air Fan High Speed”...
Operation and Maintenance Manual Nova Series 4.6 Constant Room 4.7 Cooling The function is only available if active cooling in the form of a cooling element is installed and configured. The function is used to ensure that active cooling can be used if certain set preconditions are met.
Operation and Maintenance Manual Nova Series 4.8 Dehumidification The function is used to lower the relative humidity in the room by dehumidification. When dehumidification of the room is demanded, the energy content of the air (enthalpy) is measured continuously in the fresh air and exhaust air respectively.
Operation and Maintenance Manual Nova Series 4.9 Summer/Winter Compensation 4.10 Locking the Fan Speed Under General Temperature Settings, it is possible Adjustment to set temperature compensation parameters for On the Home screen, by clicking on any fan, a popup summer and winter operation.
Operation and Maintenance Manual Nova Series 4.11 Communication Protocols External Communication Setting communication parameters for TCP/IP, LAN, Web browser and BMS Set Internet Connection Static/Dynamic • DHCP = IP address assigned from DHCP server on local network or from the Internet •...
Page 29
Operation and Maintenance Manual Nova Series BACnet Settings for external BACnet communication BACnet IP is enabled by default On the General Tab, it is possible to edit: • Controller Name Use a standard RJ45 cable External BACnet TCP/IP • Device ID connects to plug connector "TCP/IP".
Operation and Maintenance Manual Nova Series 4.12 Restore/Back-up Settings System > Backup & Restore tab > Import Backup From PC Select Backup File > Locate the saved file and select it > Next...
Page 31
Operation and Maintenance Manual Nova Series Select "User Management", "Network Configuration", "EC-gfxProgram and BACnet objects", "BACnet Configuration and Firmware Modules" boxes > Next Select "ECY303_RTU" box > Next...
Page 32
Operation and Maintenance Manual Nova Series Select "Remove backup file after restore" box > Finish The controller is now restoring the files and rebooting. This process takes about 3 minutes.
Operation and Maintenance Manual Nova Series 5.0 Operation Setting operating modes and weekly programs. 5.1 Operation mode "High speed" = the system runs constantly according to the parameter settings for high speed Select Fan Speed • Operating times for the weekly program cannot "Stop"...
Operation and Maintenance Manual Nova Series 5.2 Setting Operating Times Adding a Schedule Event Drag and drop the Schedule widget into a document window. Schedules are used to define different weekly events (weekly schedule) and special events also referred to 2.
Page 35
Operation and Maintenance Manual Nova Series Adding an Exception 6. Once the exception is created, right-click on the schedule on the right side of the window and Exceptions are special events or special days in the select Create Event. currently selected schedule instance. Typically, you use them to define days with scheduling exceptions (for example, holidays).
Operation and Maintenance Manual Nova Series 5.3 Temperature Setpoint 5.4 Time and Date • Go to System and select the Locatime/Time tab . The setpoint described in this section is always the temperature setpoint for the control type selected. •...
Operation and Maintenance Manual Nova Series 5.5 Alarm Console The Alarm Console allows you to view and acknowledge active alarms. The alarm information is presented in different columns. The total amount of alarms and unacknowledged alarms are available at a glance at the top right corner of the Alarm Console window.
Operation and Maintenance Manual Nova Series 5.6 Trends Interval Select a default interval of time that is used to The Trends screen contains the Trend Builder, which determine what and how data is presented in your the operator can use to view all trend log objects that trend chart.
Operation and Maintenance Manual Nova Series 6.0 Maintenance 6.1 Fans Warning Warning During all work on fan in the hazardous area: Clean the fan's flow area: • Maintenance operation is only to be performed • Wet cleaning under voltage may lead to an by trained service personnel.
Operation and Maintenance Manual Nova Series 6.2 DX Coil 6.3 Hydronic Coil Operation and Maintenance Operation and Maintenance For First Time Use First Use Recommendation Air Distribution The air vent (at the uppermost point on the assembly) should be opened during set-up to Uniform air flow is crucial to coil performance and exhaust any air from the coil.
Operation and Maintenance Manual Nova Series 5. When the coil surface itself needs cleaning, Core Cleaning Instructions ensure an appropriate solution and equipment are selected to avoid damage to the coil and/ Obtain access to a source of regular tap water.
Operation and Maintenance Manual Nova Series 6.5 Filters After dirty filter alarm has been initiated, check filter for obstructions. If there are no obstructions than the filter high limit pressure has been reach and the filter is considered to have reached the end of life and needs to be replaced.
Operation and Maintenance Manual Nova Series 6.6 Fuse Replacement Size 240/60/1 208/60/3 460/60/3 Quantity A16-ERV 3/10 or 3/4 A-18 ERV 3/10 or 3/4 B20-ERV 3/10 or 3/4 4/10 3/16 or 3/4 1 for 3/16 or 3/4; 2 for remainder B22-ERV...
Operation and Maintenance Manual Nova Series 6.7 Control Unit Status Display Hand Mode Operation Setting equipment in Hand Mode can be used during The display shows an overview of the system's actual service and maintenance to test that the outputs status and operating conditions.
Operation and Maintenance Manual Nova Series 6.8 Configuration Screens The Configuration screens display and allow modification of all the program settings. They are organized into groups: Fan Configuration, Preheat and Heat Configuration, Cooling and DX Coil Configuration and General Configuration.
Page 46
Operation and Maintenance Manual Nova Series 1.12 Supply Air Fan High Speed • Set the required setpoint for Supply flow at "High" speed during Constant Air Volume control. 1.20 Return Air Fan Low Speed • Set the required setpoint for Return flow at "Low" speed during Constant Air Volume control.
Page 47
Operation and Maintenance Manual Nova Series 1.60 Supply Air Fan Enable • Determines if the Supply Fan is present or not. 1.61 Supply Air Fan Start Delay • Set delayed start time for the fan. The set time is used for damper opening.
Operation and Maintenance Manual Nova Series 6.8.2 Preheat & Post Heat Configuration This screen allows configuration of the heating coils (pre and post). 2.1 Preheater Type • Selects whether there is no preheater installed or if it is electric or hydronic.
Page 49
Operation and Maintenance Manual Nova Series 2.21 Startup Heating Percentage • During the system start-up, sets the hydronic preheater output after starting the supply air fan. 2.22 Standby Temperature • When the system is stopped and 2.20 is enabled, if the water temperature falls below this setpoint, heating will be modulated to maintain the temperature above this setpoint.
Page 50
Operation and Maintenance Manual Nova Series 2.53 Frost Protection Temperature • When the system is running and 2.50 is enabled, frost protection activates on a linear relationship defined by parameters 2.53 & 2.54. This setpoint represents the return water temperature at which the heating will be activated at 100%.
Operation and Maintenance Manual Nova Series 6.8.3 Cooling & DX Configuration This screen allows configuration of the cooling & DX Coils (Heat Pump) and HGRH 3.1 Cooling Type • Selects whether there is no cooling coil installed or if it is a DX coil, Hydronic or HGRH.
Page 52
Operation and Maintenance Manual Nova Series 3.20 Temperature Deadband • Sets the deadband to switch from heating to cooling and vice versa when operating DX and HGRH coils. 3.21 Dehumidification Sensor Selection • Selects the sensor to use as reference for dehumidification when operating DX and HGRH coils.
Operation and Maintenance Manual Nova Series 6.8.4 Filter & Damper Configuration This screen allows configuration of the filters and dampers. 4.1 Outdoor Air Damper • Selects whether the outdoor damper is present or not. 4.2 Outdoor Air Damper Delay Time •...
Page 54
Operation and Maintenance Manual Nova Series 4.14 Reset • Set the method to reset the outdoor air filter operation time. • Time Interval Off: Time based alarm (set by 4.13) is disregarded. • Time Interval ON: Resets the alarm timer.
Page 55
Operation and Maintenance Manual Nova Series 4.40 Frost Protection Type • Selects what methodology of frost protection is used. • “No Selection”: There is no frost protection. • “Only EA Temperature”: Use exhaust temperature to trigger frost protection, when it drops below 4.43.
Operation and Maintenance Manual Nova Series 6.8.5 General Configuration This screen allows configuration of general settings including fire alarms and temperature settings. 5.1 Temperature Setpoint • Sets the required temperature setpoint. 5.2 Temperature Control Mode • Selects the temperature control mode, depending on the location of the temperature sensor used for control: Constant Supply Air Temp, Constant Return Air Temp or Constant Room Air Temp.
Page 57
Operation and Maintenance Manual Nova Series 5.9 Summer Temperature Difference • Max. summer compensation of setpoint. 5.10 External Fire Alarm DI Enable • Enables/Disables the option to monitor an external fire alarm input (NC contact on UI1). When active the fans will run at the speeds specified on 5.11 &...
Page 58
Operation and Maintenance Manual Nova Series 5.44 Unitouch Enable • Determines if a Unitouch (Thermostat/room sensor) is present or not. 5.45 EC-Smart Enable • Determines if an EC-Smart (room sensor) is present or not. 5.46 Dial LCD Enable • Determines if a Distech dial HMI is present or not.
Operation and Maintenance Manual Nova Series 6.8.6 myDC Control App Main Menu The main menu of the controller appears with the The myDC Control App from Distech allows control following options: Schedules, Favorites, Settings and and monitoring of the unit from a mobile phone or Device Info.
Page 60
Operation and Maintenance Manual Nova Series Schedules Setpoints Schedules are used to define different weekly events TemperatureSetpoint (weekly schedule) and special events also referred to • Set the required temperature setpoint. as exceptions. The app allows review or modification of the schedules set on the web HMI. Refer to section SAlowSpeedCfm 5.2.
Page 61
Operation and Maintenance Manual Nova Series Modifying Setpoints EAtemperature To modify a setpoint, select one and from the popup • Current Exhaust Air temperature in the selected menu, select "Set Value". units (parameter 5.40). OAfilterPressure • Current Outdoor Air Filter pressure in Pascals.
Page 62
Operation and Maintenance Manual Nova Series Control DehumidificationEnable OperationModeSelection • DehumidificationOff: Dehumidification function is turned off. Note: see section 4.8 • Stop: The system is stopped • DehumidificationOn: Dehumidification function is • Low speed: The system runs constantly turned on. Note: see section 4.8 according to the parameter settings for low speed.
Page 63
Operation and Maintenance Manual Nova Series • PreheaterHandAuto: Preheater mode Alarms • PreHeaterHandOutput: Preheater output (in This screen shows the list of the most critical alarms percentage) when in Hand mode and their state. • ReHeaterHandAuto: Post heater mode •...
Page 64
Operation and Maintenance Manual Nova Series • SAfan2Fault: Supply Air Fan 2 fault (for systems This screen shows the list of the most critical with 4 fans) warnings and their state. • RAfan1Fault: Return Air Fan fault • ExternalStartMsg: External Start signal status •...
Page 65
Operation and Maintenance Manual Nova Series Settings This screen allows setup of the date, time and time zone. Touch each section, and use the popup to set the desired date, time and zone. Device Info Contains information about the controller. The most relevant information is: •...
Operation and Maintenance Manual Nova Series 7.0 Alarm List Alarm list, SW version: 23011.0 Alarm/Warning Text Description Inside fire alarm Internal fire alarm Alarm 1 External fire alarm External fire alarm Alarm 2 HR core defrost alarm...
Page 67
Operation and Maintenance Manual Nova Series Hardware Output 106 Alarm Universal Output 6 fault Alarm 21 Hardware Output 107 Alarm Universal Output 7 fault Alarm 22 X Hardware Output 108 Alarm Universal Output 8 fault Alarm 23 SA fan 1 Alarm...
Page 68
Operation and Maintenance Manual Nova Series After cooling mode Electric post heater remnant heat Warning 11 flushing before unit stop Dehumidification mode DX coil/ HGRH dehumidification Warning 12 active Outdoor air filter pressure warning OA filter pressure higher than Warning 13 ...
Need help?
Do you have a question about the NOVA Series and is the answer not in the manual?
Questions and answers