Satel SPP-110 Instructions Manual
Satel SPP-110 Instructions Manual

Satel SPP-110 Instructions Manual

Conventional fire alarm sounder

Advertisement

Quick Links

Conventional fire alarm sounder
SPP-110
EN
Firmware version 1.00
spp-110_en 01/23
SATEL sp. z o.o. • ul. Budowlanych 66 • 80-298 Gdańsk • POLAND
tel. +48 58 320 94 00
www.satel.pl

Advertisement

loading
Need help?

Need help?

Do you have a question about the SPP-110 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Satel SPP-110

  • Page 1 Conventional fire alarm sounder SPP-110 Firmware version 1.00 spp-110_en 01/23 SATEL sp. z o.o. • ul. Budowlanych 66 • 80-298 Gdańsk • POLAND tel. +48 58 320 94 00 www.satel.pl...
  • Page 2 IMPORTANT The device should be installed by qualified personnel. Prior to installation, please read carefully this manual in order to avoid mistakes that can lead to malfunction or even damage to the equipment. Disconnect power before making any electrical connections. Changes, modifications or repairs not authorized by the manufacturer shall void your rights under the warranty.
  • Page 3: Installation

    The SPP-110 sounder is used for acoustic alarm signaling. The sounder is designed to work with the SATEL fire alarm control panels (conventional: CSP-104, CSP-108, CSP-204, CSP-208; addressable: ACSP-402). 1. Features  Acoustic signaling by means of piezoelectric transducer.  32 selectable tones.
  • Page 4 SPP-110 SATEL 4. Place the enclosure base against the wall and mark the location of mounting holes. 5. Drill the holes for wall plugs (screw anchors) in the wall. 6. Run the cables inside the enclosure base. 7. Use wall plugs and screws to secure the enclosure base to the wall. Select wall plugs specifically intended for the mounting surface (different for concrete or brick wall, different for plaster wall, etc.).
  • Page 5 SATEL SPP-110 10. Replace the cover and turn it clockwise (Fig. 6). 11. Lock the cover with a screw (Fig. 7). 2.1 Configuring the sounder settings Use the DIP switches on the electronics board (Fig. 8) to configure the sounder settings.
  • Page 6 SPP-110 SATEL DIP switch Acoustic signaling 12345 Frequency Hz Description 00100 2400-2850 7 Hz 10100 2400-2850 1 Hz 01100 500-1200 3 s sound, 0.5 s silence, repeated 11100 1200-500 1 Hz 2 Hz (250 ms – 250 ms) 00010 2400-2850 10010 0.5 Hz (1 s)
  • Page 7 SATEL SPP-110 Angle-dependent [°] minimum sound level [dBA] Tone / supply voltage 15° 45° 75° 105° 135° 165° 7 / 28 VDC 80.9 88.6 92.8 92.6 87.3 82.9 8 / 18 VDC 78.6 86.5 90.5 90.3 84.6 80.7 8 / 28 VDC 80.2...
  • Page 8: Maintenance

    The fire alarm system elements require regular maintenance. The periodic checks of the SPP-110 sounder should be carried out at least every 6 months. In spaces where working conditions are difficult (e.g. dust, aggressive environment that may cause corrosion, etc.), the periodic checks should be carried out more often.
  • Page 9 SATEL SPP-110 Operating environment type ..................... A Dimensions ....................108 x 108 x 87 mm Weight ..........................225 g...
  • Page 10 SPP-110 SATEL The SPP-110 fire alarm sounder conforms to the essential requirements of the EU Regulations and Directives: CPR 305/2011 Regulation of the European Parliament and of the Council of 9 March 2011 laying down harmonized conditions for the marketing of construction products and repealing the Council Directive 89/106/EEC on construction products;...