OPERATIONAL CHECKS

Note: This equipment must be checked regularly in compliance with local regulation and
codes of practice.
After installation, you should allow 24 hours for the battery pack to charge fully
before testing.
Isolate the power supply and check that the lamp remains illuminated for at least
three hours. Restore the power supply.
Each day: Check that the green charging LED is lit.
Each month (short test): Isolate the power supply and check that the lamp remains
illuminated. Record the results on the test record sheet included with these
instructions.
Every six months: Isolate the power supply and check that the lamp remains
illuminated after 1 hour. Record the results on the included test record.
Once each year: Isolate the power supply and check that the lamp is still illuminated
after 3 hours. Record the results on the included test record.
Please keep these test records in a safe place. A fire officer or other authorised
person may want to see your record of inspection and testing.

CLEANING AND MAINTENANCE

Clean the product with a soft, dry cloth only. Do not use any solvents or abrasive
chemical cleaners.
The LED lamps in this product are non-replaceable.
Changing the battery
If after a routine operation check, the lamp does not remain lit for the 3 hour period,
a new battery pack may be required. Change the battery pack as follows:
1.
Isolate from the mains supply.
2.
Remove the end cover and legend diffuser.
3.
Unplug the 2 pin battery pack connector.
4.
Remove the old battery pack.
5.
Write the current date on the new battery pack.
6.
Fit the new battery pack and secure in position.
7.
Reconnect the battery pack terminal connector.
8.
Refit the legend diffuser making sure that it is securely slotted in place.
9.
Refit the end cap and tighten the screws.
10. Restore mains power and allow to charge for 24 hours.
11. Perform the full operation check and update the test record.
Note: To help promote good battery performance, it is recommended that the battery is
cycled periodically from completely discharged back to fully charged.
7