Description
Indicator LEDs
Normal
Charging (battery test not possible while charging)
Mains off, battery not connected or charger fault
Battery test (Duration: 1h,3h,8h)
Battery fault
Light source test (Duration: 3s)
Light source fault
Battery fault and light source fault
LED Status explanation
Off
On
The FloodLED is a self-contained maintained/non-maintained luminaire with selftest function.
Selftest functions
Every 15 days the luminaire will perform an emergency operation test. This will turn on the light source for
approximately 3 seconds. The green LED will flash during this test sequence.
Every 6 months the luminaire will perform a battery condition test. The test will last for the chosen
autonomy. The light source will be lit and the green LED will flash during this test sequence.
Note: When using Wireless communication, the frequencies and schedules for tests will instead be
determined by the connected PC software.
Important notice when installing luminaires within the same area!!!
To avoid that luminaires perform their battery test at the same day, connect the battery packs with more
than 1,5 minutes inbetween.
Honeywell Life Safety AS, Postboks 236, 1372 Asker
7
Step 6: Place the battery's connector to the corresponding connector
on the PCB.
Step 7:
In case you use a module connect it on the PCB.
Note! FloodLED supports only the Wireless module.
Step 8. Refit the luminaire to the bottom cover and fasten the two
removed screws.
Step 9: Mount the bracket to the wall or to the ceiling.