BEKA BA3400 Series Instructions Manual

BEKA BA3400 Series Instructions Manual

Pageant plug-in digital input modules

Advertisement

Instructions for BA3400 series
Pageant plug-in
Digital Input modules
B A 3
4 0 1
BEKA associates Ltd. Old Charlton Rd, Hitchin, Hertfordshire,
SG5 2DA, UK
Tel: +44(0)1462 438301
web:
www.beka.co.uk
1. INTRODUCTION
The BA3400 series plug-in DI (Digital Input) modules are
part of the BEKA Pageant Display system. Two models
are available:
BA3401
8 contact inputs
BA3402
8 NAMUR 2-wire inputs
Both models have IECEx, ATEX and UKCA intrinsic safety
apparatus certification.
The DI modules plug into any of the seven module sockets
at the rear of the BA3101 Pageant Operator Display.
Power for the module is provided by the BA3101 Operator
Display which determines the modules response speed.
If required multiple DI modules may be plugged into an
Operator Display.
Fig 1 shows a BA3400 DI plug-in module with its features
identified.
Plug-in BA3400 series Pageant DI Modules are CE marked to show compliance with the European
Explosive Atmospheres Directive 2014/34/EU and the European EMC Directive 2014/30/EU.
The modules are also UKCA marked to show compliance with UK statutory requirements Equipment and
Protective Systems Intended for Use in Potentially Explosive Atmospheres Regulations UKSI 2016:1107
(as amended) and with the Electromagnetic Compatibility Regulations UKSI 2016:1091 (as amended).
Issue 3
22nd February 2023
e-mail:
sales@beka.co.uk
Each of the eight inputs is a separate intrinsically safe
circuit but they are not isolated from each other. Inputs
should therefore only be connected to isolated sensors and
wiring such as reed relays, switch contacts and proximity
detectors. The BA3402 can power and monitor the status
of 2-wire NAMUR compliant sensors, such as proximity
detectors. It may also be used to monitor switch status in
noisy environments.
In addition to their normal function, inputs 7 and 8 may
be used for the decoding a quadrature signal from a plant
position sensor or a BEKA BA490 rotary encoder.
B A 3
8 pairs of
input terminals
Fig 1 BA3400 series plug-in DI module
2. INTRINSIC SAFETY CERTIFICATION
Notified Body CML B.V. and UK Approved Body Eurofins
CML have issued the BA3400 series plug-in DI modules
with the following apparatus certificates:
IECEx
ATEX
UKCA
The ATEX certificate has been used to confirm compliance
with the European ATEXr Directive for Group II, Category
1GD equipment, similarly the UKCA certificate has been
used to confirm compliance with UK statutory requirements.
All BA3400 series DI modules carry both the CE and
UKCA marks, subject to local codes of practice, they may
be installed in any of the European Economic Area (EEA)
member countries and in the UK. ATEX certificates are
also acceptable for installations in some non EU countries.
These instructions describe IECEx, ATEX and UKCA
installations which conform with IEC / EN 60079-14
Electrical installations design, selection and erection.
When designing systems the local code of practice should
be consulted.
4 0 1
Certification
information
label
IECEx CML 21.0004X
CML 21ATEX2110X
CML 21UKEX2111X

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BA3400 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for BEKA BA3400 Series

  • Page 1 Plug-in BA3400 series Pageant DI Modules are CE marked to show compliance with the European Explosive Atmospheres Directive 2014/34/EU and the European EMC Directive 2014/30/EU. The modules are also UKCA marked to show compliance with UK statutory requirements Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres Regulations UKSI 2016:1107 (as amended) and with the Electromagnetic Compatibility Regulations UKSI 2016:1091 (as amended).
  • Page 2: Installation

    Pageant BA3101 display but there are power limitations. iii. The BA3400 series shall only be used as part of a BEKA Pageant System. The percentage of the total available power that these modules consumes is: 2.3 Certification label information...
  • Page 3 3.2 BA3400 series plug-in DI module Installation 1. The BA3400 series DI module may be fitted before or Therefore the maximum inductance that may be after the Operator Panel is installed. The Operator connected Lo is not specified, the cable length between...
  • Page 4 Unlike most quadrature inputs which produce one Almost any certified intrinsically safe 2-wire NAMUR incrementing or decrementing input pulse for each A + B compliant sensor located in the same hazardous area as cycle, the BA3401 produces four as shown in Fig 6 which the BA3402 may be directly connected to any of the eight results in increased resolution.
  • Page 5: Maintenance

    Closed BA3400 series DI modules which fail within the guarantee period should be returned to BEKA associates or your Counter local BEKA agent. It is helpful if a brief description of the input pulses fault symptoms is provided. Clockwise rotation 7.
  • Page 6 BA3400 Series Pageant Digital Input Modules Codesys Mapping and Parameters The Pageant Codesys Quick Start Guide which can be The following table lists the BA3400 series Pageant Digital downloaded from the BEKA website https://www.beka. Input Modules Codesys parameters that can be set and co.uk/manuals/pageant_codesys_quick_start_guide.pdf...
  • Page 7 BA3402 – DI MODULE NAMUR Channel or Parameter Variable Type Default Range Description Name Type Enumeration Enabled Quadrature Control Parameter Disabled Enable Quadrature on Inputs 7 and 8 Of BYTE Disabled Input 1 Fault Detection Control Input 2 Fault Detection Control Input 3 Fault Detection Control Input 4 Fault Detection Control 0: Fault Detection Disabled,...
  • Page 8 All associated manuals, certificates, and datasheets can be downloaded from Old Charlton Rd, Hitchin, Hertfordshire, SG5 2DA, UK https://www.beka.co.uk/qr-ba3100 Tel: +44(0)1462 438301 e-mail: sales@beka.co.uk web: www.beka.co.uk...

This manual is also suitable for:

Ba3401Ba3402

Table of Contents