Dimensional Drawing - Carrier TOSHIBA MMD-UP0071BHP-UL Service Manual

Multi type
Table of Contents

Advertisement

3. DIMENSIONAL DRAWING

5.4"
Ø4.9"(125) knockout hole
(136)
For Auxiliary fresh air taking
(Sold separately)
Dimension in inches (mm)
Model MMD-UP****BHP-UL
0071~0091
0121
0151~0181
0211~0541
Ceiling
3.9"(100)
or more
Model MMD-UP****BHP-UL
0071~0091
0121~0181
0211~0541
C
L
Hanging bolt pitch B
Main unit dimension A
External dimensions of flange C
D
A
B B
27.6" (700)
30.1" (765)
39.4" (1000)
41.9" (1065)
39.4" (1000)
41.9" (1065)
57.7" (1465)
55.1" (1400)
Air discharge
1.0"(25)
1.0"(25)
A
B
or more
Service door (Ceiling opening)
Floor surface
3.9"(100) or more
Air discharge
Check port
17.7"(450)
B
Service space
(B for maintenance of air filter)
A
29.5" (750)
27.6" (700)
41.3" (1050) 19.7"(500)
57.1" (1450) 27.6" (700)
0.9"(22)
2.0"(50)
Hanging bolt pitch 25.6"(650)
Access panel
Drain pan / Drain
pump check cover
Air
discharge
0.8"(20)
1.5"(37)
D
C
25.2" (640)
29.5" (750)
37.0" (940)
41.3" (1050)
37.0" (940)
41.3" (1050)
52.8" (1340)
57.1" (1450)
Ceiling
Ceiling
22.4"(570)
B
Ceiling
- 19 -
Unit : in (mm)
29.5"(750)
2.0"(50)
13.6"(345)
7.4"
(187.5)
14.0"(355)
1.0"(25)
16.3"(415)
Electrical
control box
22.4"(570)
Air fow direction
Refrigerant pipe connecting port
E (Liquid side)
Refrigerant pipe connecting port
4.3"
F (Gas side)
(108)
Drain pipe connecting port
Outer diameter 1.3''(32)
0.7"(18)
9.2"(233)
9.1"(232)
E
∅1/4" (6.4)
∅1 /2" (12.7)
∅1/4" (6.4)
∅1 /2" (12.7)
∅3/8" (9.5)
∅5/8" (15.9)
∅3/8" (9.5)
∅5/8" (15.9)
Air intake
2.0''(50) or more
1.0''(25)
22.4''(570)
Service door (Ceiling opening)
Air intake
1.0"(25)
Service door (Ceiling opening)
Air intake
11.8"(300)
or more
1.0"(25)
22.4"(570)
Service door (Ceiling opening)
F

Hide quick links: