  • Page 1 5 A SIL 3 Relay Output Module for NE Load, with full diagnostic and Modbus, DIN-Rail, Power Bus and Termination Board, Model D5293S D5293 - 5A SIL 3 Relay Output Module for NE Load with full diagnostic and Modbus G.M. International ISM0122-16...
  • Page 2: Technical Data

    Characteristics General Description: The D5293S is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed.2, for high risk industries. It provides isolation between input and output contacts. A wide compatibility towards different DCS/PLC is guaranteed: driving line pulse testing, executed by DCS/PLC, is permitted by a dedicated internal circuit, to prevent relay and LED flickering.
  • Page 3: Ordering Information

    Ordering information Power Bus and DIN-Rail accessories: Model: D5293S Connector JDFT050 Cover and fix MCHP196 Terminal block male MOR017 Terminal block female MOR022 Operating parameters are programmable from PC by the GM Pocket Portable Adapter PPC5092 via USB serial line and SWC5090 Configurator software.
  • Page 4: Function Diagram

    Function Diagram SAFE AREA, ZONE 2 GROUP IIC T4, NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2, GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4 MODEL D5293S Load and Supply 24 Vdc Line 10 -...
  • Page 5: Operation

    Operation The single channel 5 A Relay Output D5293S is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed. 2 for high risk industries. It provides isolation between input and output contacts. D5293S has 1+1 SPST contact for normally energized load. SIL 3 Safety Function for NE load (de-energized in fail safe state) is available at Terminal Blocks 13-14.
  • Page 6: Configuration Parameters

    The Pocket Portable Adapter type PPC5092 is suitable to connect the module D5293S to a PC via USB serial line, in order to configure and to monitor the operation parameters by means of SWC5090 software. The PPC5092 unit is connected to D5293S by mini USB and to PC by USB port. This adapter is not ATEX, UL or FM approved and is only to be used in Safe Area/Non Hazardous Locations.
  • Page 7: Parameters Details

    Supported ModBus Parameters: Parameters Details: D5293S communicates via Modbus RTU-485 protocol. Below are all available registers. Address 17: Supported ModBus Baudrates Param. Index Baudrate Description Notes Type (10) Address 4800 G.M. Factory Code 9600 19200 Instrument Code Identification 38400 Option Code...