INSTRUCTION & SAFETY MANUAL 5 A SIL 3 Relay Output Module for NE or ND Loads, with NE or ND Relay condition, DIN-Rail and Termination Board, Model D5290S-078 D5290S-078 - 5 A SIL 3 Relay Output Module G.M. International ISM0152-8...
General Description: The D5290S-078 is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed. 2 for high risk industries. It provides isolation between input channel and output contacts.
Normally Open (NO) contact (Out S_2) Input - Normally Closed (NC) contact (Out P_1) Normally Closed (NC) contact (Out P_2) Normally Open (NO) contact (Out S_4) Normally Open (NO) contact (Out S_3) G.M. International ISM0152-8 D5290S-078 - 5 A SIL 3 Relay Output Module...
Page 4
Terminals 13-14, 15-16, 21-22 and 23-24 are open. Terminals 17-18 and 19-20 are closed. To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram. D5290S-078 - 5 A SIL 3 Relay Output Module G.M. International ISM0152-8...
Page 5
Safety Function and Failure behavior: D5290S-078 is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0. In the 1st Functional Safety application, the normal state operation of relay module is energized, with NE (Normally Energized) loads.
Page 6
Safety Function and Failure behavior: D5290S-078 is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0. In the 2nd Functional Safety application, the normal state operation of relay module is energized, with NE (Normally Energized) loads.
Page 7
Safety Function and Failure behavior: D5290S-078 is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0. In the 3rd Functional Safety application, the normal state operation of relay module is energized, with NE (Normally Energized) loads.
Page 8
Safety Function and Failure behavior: D5290S-078 is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0. In the 4th Functional Safety application, the normal state operation of relay module is energized, with ND (Normally De-energized) loads.
Page 9
Safety Function and Failure behavior: D5290S-078 is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0. In the 5th Functional Safety application, the normal state operation of relay module is de-energized, with ND loads.
Page 10
Safety Function and Failure behavior: D5290S-078 is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0. In the 6th Functional Safety application, the normal state operation of relay module is de-energized, with ND loads.
Page 11
Remove the bypass from the safety-related PLC or restore normal operation inserting the unit. This test reveals almost 99% of all possible Dangerous Undetected failures in the relay module. D5290S-078 - 5 A SIL 3 Relay Output Module G.M. International ISM0152-8...
Warning D5290S-078 is an electrical apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature Classification T4, Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb - 40 to +60 °C.
Page 13
= relay2; dip5 = relay3) Please, see next page for testing procedure at T-proof. WARNING: after T-proof test, dip-switch 1-3-5 must be set to “OFF” position for normal operation. G.M. International ISM0152-8 D5290S-078 - 5 A SIL 3 Relay Output Module...
Need help?
Do you have a question about the D5290S-078 and is the answer not in the manual?
Questions and answers