Start-Up and Performance Checklist

Customer: _____________________________________
Indoor Unit Model: _______________________________
Outdoor Unit Model: ______________________________
Notes: __________________________________________________________________________________________
Start-Up Checks
Refrigerant Type: _____________________
Rated Load Amps: ____________________ Actual Amps: ______ Rated Volts: _______ Actual Volts: ________
Condenser Fan Full Load Amps: _________ Actual Amps: ______
Cooling Mode
Suction Pressure: ____________________ Liquid Pressure: _________
Supply Air Temperature: _______________ Ambient Temperature: ___________ Return Air Temperature: _________
System Refrigerant Charge (Refer to manufacturer's information on unit or installation instructions for required subcooling
and approach temperatures.)
Subcooling:
Approach:
Indoor Coil Temerpature Drop (18 to 22°F):
Page 24 of 24
Saturated Condensing Temperature (A)
minus Outdoor Air Temperature (B)
Liquid Line Temperature (A)
minus Outdoor Air Temperature (B)
Return Air Temperature (A)
minus Supply Air Temperature (B)
Issue 2231
Address: _______________________________________
Serial: _________________________________________
Serial: _________________________________________
A - B = Subcooling
A - B = Approach
A - B = Coil Temp Drop
508296-G01 / 31-5000753