Download Print this page
Areva MiCOM C232 Technical Manual
Areva MiCOM C232 Technical Manual

Areva MiCOM C232 Technical Manual

Compact bay unit for control and monitoring with protection functions
Hide thumbs Also See for MiCOM C232:

Advertisement

Quick Links

MiCOM C232
Compact Bay Unit for
Control and Monitoring
with Protection Functions
Version -302-401/402/403/404-603
Technical Manual
C232/EN M/A23
Volume 1.2

Advertisement

loading
Need help?

Need help?

Do you have a question about the MiCOM C232 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Areva MiCOM C232

  • Page 1 MiCOM C232 Compact Bay Unit for Control and Monitoring with Protection Functions Version -302-401/402/403/404-603 Technical Manual C232/EN M/A23 Volume 1.2...
  • Page 2: Operation

    3 Operation (continued) 3.18 Limit Value Monitoring (Function Group LIMIT) Disabling or enabling limit value monitoring Limit value monitoring can be disabled or enabled from the integrated local control panel. Monitoring phase currents and phase voltages The C232 offers the possibility of monitoring the following measured values to determine if they exceed a set upper limit value or fall below a set lower limit value: Maximum phase current Minimum phase current...
  • Page 3 3 Operation (continued) 3-93 Limit value monitoring of minimum and maximum phase current 3-123 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 4 3 Operation (continued) 22Z5135A 3-94 Limit value monitoring of maximum and minimum phase-to-phase voltage and maximum and minimum phase-to-ground voltage 3-124 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 5 3 Operation (continued) Monitoring the neutral- displacement voltage The neutral-displacement voltage calculated from the three phase-to-ground voltages is monitored by two stages to determine whether it exceeds set thresholds. If the thresholds are exceeded, a signal is issued after the set timer stage has elapsed. 3-95 Monitoring the neutral-displacement voltage 3-125...
  • Page 6 3 Operation (continued) Monitoring the linearized measured DC values The direct current that is linearized by analog measured data input is monitored by two stages to determine if it exceeds or falls below set thresholds. If it exceeds or falls below the thresholds, a signal is issued once a set time period has elapsed.
  • Page 7 3 Operation (continued) 3.19 Programmable Logic (Function Group LOGIC) Programmable (or user-configurable) logic enables the user to link binary signals within a framework of Boolean equations. Binary signals in the C232 can be linked by logical ‘OR’ or ‘AND’ operations or by additional ‘NOT’...
  • Page 8 3 Operation (continued) 3-97 Control of logic operations via setting parameters or stored input signals The L O G I C : T r i g g e r n signal is a ‘triggering function’ that causes a 100 ms pulse to be issued.
  • Page 9 3 Operation (continued) 3-98 Setting options for programmable logic (shown here for output 1) 3-129 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 10 3 Operation (continued) The output signal of one equation can be processed as the input signal for another higher-order equation, and this makes it possible to have a sequence of interlinked Boolean equations. The equations are processed in the sequence defined by the order of each equation so that the end result of a sequence of interlinked Boolean equations is given by the highest-order equation.
  • Page 11 3 Operation (continued) 3-100 Operating mode 2: Operate-delay/pulse duration 3-101 Operating mode 3: Operate/release delay, retriggerable 3-131 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 12 3 Operation (continued) 3-102 Operating mode 4: Operate-delay/pulse duration, retriggerable 3-103 Operating mode 5: Minimum time Through appropriate configuration, it is possible to assign the function of a binary input signal to each output of a logic operation. The output of the logic operation then has the same effect as if the binary signal input to which this function has been assigned were triggered.
  • Page 13 3 Operation (continued) 3-104 Signal assignment to outputs of Boolean equations 3-133 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 14 3 Operation (continued) 3.20 Control and Monitoring of Switchgear Units (Function Groups DEV01 to DEV10) The C232 is designed for the control of up to 6 switchgear units. The topology of a switchbay with its switchgear units is defined by the bay type. Defining the bay type With the selection of the bay type, the user defines the following properties: Manually operated switchgear units with position signals to be processed...
  • Page 15 3 Operation (continued) 3.20.1 Processing of Position Signals for Manually Operated Switchgear The position signals ‘Open’ and ‘Closed’ are assigned to binary signal inputs. The signals conditioned by debouncing and chatter suppression (see: ‘Main Functions of the C232’) are used for further processing. If no logic value of '1' is present at any of the two binary signal inputs, the running time monitoring is started.
  • Page 16 3 Operation (continued) 3-105 Processing of position signals for manually operated switchgear 3-136 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 17 3 Operation (continued) 3.20.2 Functional Sequence for Controllable Switchgear Units Local or remote control of external devices Switchgear units can be controlled remotely or locally. The Selection of the Control Point is described in the section entitled “Configuration of the Bay Panel and of the Measured Value Panels;...
  • Page 18 3 Operation (continued) 3-106 Generating the switching request 3-138 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 19 3 Operation (continued) Enabling of the switching commands Before a switching command is executed, the C232 checks the interlocking equations defined in the interlocking logic to determine whether the switching command is permissible. Bay interlock equations for operation with or without station interlock can be defined.
  • Page 20 3 Operation (continued) Bay interlock for operation with station interlock For the station interlock equations to be interrogated, there needs to be communication with substation control level. If the C232 detects a communication error or if there is no communication interface, there will be an automatic switch to bay interlock without station interlock.
  • Page 21 3 Operation (continued) For circuit breakers, the open command can be linked to the protection trip signal. The close command can be linked to the close command of the protection functions. The bay type defines which of the switchgear units are circuit breakers. The trip or close commands of the protection functions are executed directly without a check on the interlocking equations.
  • Page 22 3 Operation (continued) Issue of the switching commands The operating mode set for the commands determines whether they are issued for the set times or whether are issued in accordance with time control. 3-110 Issue of the switching commands 3-142 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 23 3 Operation (continued) Time control of the switching commands As the switching command ends, the running time monitoring of the switching device is started. The C232 anticipates a status signal - ‘Open’ or ‘Closed’ to be issued by the switching device within the monitoring time. The status signal of the switchgear position comes in via appropriately configured binary inputs of the C232 where debouncing and chatter suppression can be set.
  • Page 24 3 Operation (continued) 3-111 Monitoring the switching commands 3-144 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 25 3 Operation (continued) Time control for direct motor control The control sequence applied above applies to all switchgear units operated via an ‘Open’ - or ‘Close’ - contact. For bays with direct motor control of switch disconnectors, disconnectors or grounding switches, the following modified control sequence described below applies to the motor-operated switchgear units.
  • Page 26 3 Operation (continued) Time control for direct motor control with external command termination For bay types that are defined for direct motor control, it is possible to intervene in the control sequence of motor-operated switchgear units by way of external terminating contacts.
  • Page 27 3 Operation (continued) 3-112 Triggering and monitoring the motor relay 3-147 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 28 3 Operation (continued) 3.21 Interlocking Logic (Function Group ILOCK) The switching commands to the controllable switchgear units of the bay are not enabled until the interlock conditions have been checked. The interlocks are defined in the form of Boolean equations in the interlocking logic function. The choice of the bay type automatically defines the bay interlock conditions (or equations) for the ‘Open’...
  • Page 29 3 Operation (continued) 3-113 Interlocking logic illustrated for equation 1 3-149 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 30 3 Operation (Fortsetzung) 3.22 Single-Pole Commands (Function Group CMD_1) Commands can be sent to the P139 through the communication interface. If the P139 receives the command, then the appropriately configured output relay is triggered and a signal is issued - provided that remote control has been enabled. The user may select the operating mode for any single-pole command.
  • Page 31 3 Operation (continued) 3.23 Single-Pole Signals (Function Group SIG_1) Binary, single-pole signals from the station can be transmitted by the C232 to the control station through appropriately configured binary signal inputs. The input signal is conditioned by debouncing and chatter suppression (see: 'Main Functions of the C232).
  • Page 32 3 Operation (continued) 3-115 Functional sequence for single-pole signals, illustrated for signal S001 3-152 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 33 3 Operation (continued) 3.24 Binary Counts (Function Group COUNT) The C232 has one binary counter which counts the positive edges at an appropriately configured binary signal input. The signal to be counted can be debounced. Enabling or disabling the counting function The counting function can be disabled or enabled from the integrated local control panel.
  • Page 34 3 Operation (continued) Counting function The debounced signal is counted by a 16 bit counter. Each counter can be set to a specific count from the local control panel and through the serial interfaces (preload function). The count (counter reading) can be displayed on the LCD display and output via the PC and communication interfaces.
  • Page 35 3 Operation (continued) 3-117 Binary count 3-155 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 36 3 Operation (continued) 3.25 Tap Changer (Function Group TAPCH) The transformer tap control function makes it possible to acquire data of one tap position and to output tap change commands for one tap changer. The functions and settings for the tap changer are described below. Acquisition of tap positions Data on tap positions are acquired in BCD code with 6 bits maximum and one sign bit for positions in the range of -64 to +63 maximum.
  • Page 37 3 Operation (continued) 3-118 Tap Changer: TAPCH 1 3-157 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 38 3 Operation (continued) 3-158 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 39 4 Design Design The C232 is mounted in an aluminum case. Connection is via threaded terminal ends. The case is suitable for either wall-surface mounting or flush panel-mounting. The mounting brackets adjust for flush mounting. Figures 4-1 and 4-2 show the case dimensions and mounting dimensions. A cover frame is supplied for flush mounting (see Installation and Connection).
  • Page 40 4 Design (continued) Dimensional drawing of the wall-mounting case (-X7,-X8 and -X9 or –X10: communication interfaces, optional) C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 41 4 Design (continued) Dimensional drawing of the flush-mounting case (-X7,-X8 and -X9 or –X10: communication interfaces, optional) C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 42 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 43: Installation And Connection

    5 Installation and Connection Installation and Connection Unpacking and Packing All C232 units are packaged separately in their own cartons and shipped inside outer packaging. Use special care when opening cartons and unpacking units, and do not use force. In addition, make sure to remove from the inside carton the Supporting Documents and the type identification label supplied with each individual unit.
  • Page 44 5 Installation and Connection (continued) Location Requirements The C232 has been designed to conform to EN 60255-6. Therefore it is important when choosing the installation location to make sure that it provides the conditions specified in the chapter entitled 'Technical Data'. Several important conditions are listed below. Environmental Conditions Ambient temperature: -5 °C to +55 °C [+23 °F to +131 °F]...
  • Page 45 5 Installation and Connection (continued) Installation The dimensions and mounting dimensions for surface-mounted cases are given in Chapter 4. When the C232 is surface-mounted on a panel, the leads to the C232 are normally run along the front side of the mounting plane. If the wiring is to be in back, an opening can be provided below the surface-mounted case, as shown in Figure 5-2.
  • Page 46 5 Installation and Connection (continued) Panel cutout for the flush-mounted case (dimensions in mm) C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 47 5 Installation and Connection (continued) Installation of the 40 T case with cover frame) C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 48 5 Installation and Connection (continued) Protective and Operational Grounding The unit must be reliably grounded to meet protective equipment grounding requirements. The case is grounded using the appropriate bolt and nut as the ground connection. The cross-sectional area of this ground conductor must also conform to applicable national standards.
  • Page 49 5 Installation and Connection (continued) Connection The C232 must be connected in accordance with the terminal connection diagram indicated on the type identification label. The terminal connection diagram is included among the Supporting Documents supplied with the unit. The terminal connection diagrams that apply to the C232 are also found in the Appendix to this manual.
  • Page 50 5 Installation and Connection (continued) Connecting the time- overcurrent protection measuring circuits C232 could be equipped with up to four current or voltage transformers. The applicable assignment of the terminal connections is described in the Appendix (E). The C232 model 4 (with time-overcurrent protection) is fitted with four current-measuring inputs as a standard.
  • Page 51 5 Installation and Connection (continued) Connecting the binary inputs and output relays The binary inputs and output relays are freely configurable. When configuring these components it is important to note that the contact rating of the binary I/O modules (X) varies (see the Chapter on “Technical Data”).
  • Page 52 5 Installation and Connection (continued) Connection example for direct motor control, bay type No. 89 (A23.105.M04), feeder bay with circuit breaker, double busbar 5-10 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 53 5 Installation and Connection (continued) 5.6.2 Connecting the Serial Interfaces PC interface The PC interface is provided in order to operate the unit from a personal computer (PC). The PC interface is not designed for permanent connection. Consequently, the female connector does not have the extra insulation from circuits connected to the system that is required per VDE 0106 Part 101.
  • Page 54 200-to-220-Ω resistor. In most AREVA devices, and also in the C232, a 220-Ω resistor is integrated into the RS 485 interface and can be connected by means of a wire jumper.
  • Page 55 5 Installation and Connection (continued) 2-wire connection 5-13 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 56 5 Installation and Connection (continued) 4-wire connection 5-14 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 57: Local Control Panel

    6 Local Control Panel Local Control Panel Local control panel The switchgear units of the bay can be controlled from the local control panel. In addition, all data required for operation of the unit C232 are entered here, and the data important for system management are read out here as well.
  • Page 58 6 Local Control Panel (continued) TRIP ALARM OUT OF SERVICE HEALTHY EDIT MODE View of the local control panel C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 59 6 Local Control Panel (continued) Display levels All data relevant for operation and all device settings are displayed on two levels. Data such as the switching status or the measured operating values are displayed at the Panel level and provide an up-to-date overview of the state of the bay. The menu tree level below the Panel level allows the user to select all data points (settings, signals, measured variables, etc.) and to change them, if appropriate.
  • Page 60 6 Local Control Panel (continued) Display Panels The following display Panels are available with the C232: Bay Panel Measured Value Panels, which are called up according to system conditions Signal Panel The Bay Panel displays the up-to-date switching state of the selected bay in single-pole representation.
  • Page 61: Enter Key

    6 Local Control Panel (continued) Keys ‘Up’ and ‘Down’ Keys Panel Level: The effect of using the ‘up’ and ‘down’ keys differs between the individual Panels. Bay Panel: The ‘up’ and ‘down’ keys switch between the measured values selected for this Panel. Measured Value Panel: The ‘up’...
  • Page 62: Clear Key

    6 Local Control Panel (continued) CLEAR Key Press the CLEAR key to reset the LED indicators and clear all measured event data. The records in the recording memories are not affected by this action. Panel Level: Bay Panel: If the reset key is pressed while selecting a switchgear unit on the Bay Panel then the selection of the switchgear unit is canceled.
  • Page 63 6 Local Control Panel (continued) The following presentation of the individual control steps shows which displays can be changed in each case by pressing the keys. A small black square to the right of the enter key indicates that the “EDIT MODE” LED indicator is lit up. An underscored external device name in the Bay Panel indicates a selected switchgear unit.
  • Page 64 6 Local Control Panel (continued) Illumination of the Display If none of the control keys is pressed, the display illumination will switch off once the set ‘return time illumination’ (set in the menu tree at ‘Par/Conf/LOC’) has elapsed. Press any one of the control keys to turn the display illumination on again. The control action that is normally triggered by that key will not be executed.
  • Page 65 6 Local Control Panel (continued) X YYY 10:33:22 Locked Remote 1088 A Curr. IP,max prim. Example for a Bay Panel Representation of the external devices with External device State character set 1 character set 2 Circuit breaker ‘Open’ ‘Closed’ ‘Off-end’,’Faulty’ Switch disconnector ‘Open’...
  • Page 66 6 Local Control Panel (continued) Control Step / Description Control Display Action Measured value display in the X YYY 10:33:22 Measured values are shown one at a time. Bay Panel A configuration step determines whether the measured value will also be displayed in bar form.
  • Page 67 6 Local Control Panel (continued) Controlling switchgear units Switchgear units can be controlled from the local control panel, provided that the unit has been set for ‘local control’. If the local/remote key is set to switch between remote and local control (R↔L), then the switch from ‘remote’ to ‘local’ operation requires a password.
  • Page 68 6 Local Control Panel (continued) Control Step / Description Control Display Action Now press the enter key. X YYY 10:33:25 If the correct password has been entered, the Bay Panel will re-appear. The third line from the bottom will display ‘Local’. If an invalid password has been entered, the display shown above in Step 1 will appear.
  • Page 69 6 Local Control Panel (continued) Control Step / Description Control Display Action After selecting a switchgear unit, press the keys “Open” “Close” to control the switchgear unit. Before this switching action is executed, compliance with bay interlock conditions – if applicable – is checked.
  • Page 70 6 Local Control Panel (continued) Control Step / Description Control Display Action If a control action does not take place within a set time period after selection of a switchgear unit or if the return time for illumination has elapsed, then the selection is canceled. X YYY 10:33:38 Press the local/remote key (L/R) to switch to...
  • Page 71 6 Local Control Panel (continued) 6.4.2 Measured Value Panels and Signal Panel Measured Value Panels The measured values that will be displayed on the Measured Value Panels can first be selected in the menu tree under Par/Conf/LOC. The user can select different sets of measured values for the Operation Panel, the Overload Panel, the Ground Fault Panel, and the Fault Panel.
  • Page 72 6 Local Control Panel (continued) Signal Panel The Signal Panel shows the signals relevant for operation. Each signal is fully time- tagged (date and time of day). A maximum of three signals are displayed. Control Step / Description Control Display Action Events 16:57:33...
  • Page 73 6 Local Control Panel (continued) Control at the Menu Tree Level 6.5.1 Navigation in the Menu Tree Folders and function groups All data points are grouped in function groups according to the function they are associated with and are also organized in different folders based on practical control requirements.
  • Page 74 6 Local Control Panel (continued) 6.5.2 Switching Between Address Mode and Plain Text Mode The display on the local control panel can be switched between address mode and plain text mode. In the address mode the display shows setting parameters, signals, and measured values in numerically coded form, that is, as addresses.
  • Page 75 6 Local Control Panel (continued) 6.5.3 Change-Enabling Function Although it is possible to select any data point in the menu tree and read the associated value by pressing the keys, it is not possible to switch directly to the input mode. This safeguard prevents unintended changes in the settings.
  • Page 76 6 Local Control Panel (continued) Control Step / Description Control Display Action Oper/CtrlTest/LOC In the menu tree ‘Oper/CtrlTest/LOC’ select Param. change enabl. the ‘Param. change enabl.’ parameter. Oper/CtrlTest/LOC Press the ENTER key. Eight asterisks (*) Param. change enabl. appear in the fourth line of the display. ******** Oper/CtrlTest/LOC Press the following keys in sequence:...
  • Page 77 6 Local Control Panel (continued) Automatic return The automatic return function prevents the change-enabling function from remaining activated after a change of settings has been completed. Once the set return time (menu tree ‘Par/Conf/LOC’) has elapsed, the change-enabling function is automatically deactivated, and the display switches to a Measured Value Panel corresponding to the current system condition.
  • Page 78 6 Local Control Panel (continued) 6.5.4 Changing Parameters If all the conditions for a value change are satisfied (see above), the desired setting can be entered. Control Step / Description Control Display Action Oper/CtrlTest/LOC Example of a display. Param. change enabl. In this example the change-enabling function is activated and the protective function is disabled, if necessary.
  • Page 79 6 Local Control Panel (continued) 6.5.5 Setting a List Parameter Using list parameters, the user is able to select several elements from a list in order to perform tasks such as defining a trip command or defining the measured values that will be displayed on Measured Value Panels.
  • Page 80 6 Local Control Panel (continued) Control Step / Description Control Display Action Par/Func/Glob/MAIN Press the ENTER key. The LED indicator Fct.assign.trip cmd. will go out. The assignment has been made. #02 DIST The unit will now operate with the new settings. Trip zone 4 If no operator has been selected, the ‘OR’...
  • Page 81 6 Local Control Panel (continued) 6.5.6 Memory Readout After a memory is entered, the memory can be read out at the entry point. It is not necessary to activate the change-enabling function or even to disable the protective function. Inadvertent clearing of a memory at the entry point is not possible. The following memories are available: In the menu tree ‘Oper/Rec/OP_RC’: Operating data memory In the menu tree ‘Oper/Rec/MT_RC’: Monitoring signal memory...
  • Page 82 6 Local Control Panel (continued) Readout of the operating data memory The operating data memory contains stored signals of actions that occur during operation, such as the enabling or disabling of a device function. A maximum of 100 entries is possible, after which the oldest entry is overwritten. Control Step / Description Control Display...
  • Page 83 6 Local Control Panel (continued) Readout of the monitoring signal memory If the unit detects an internal fault in the course of internal self-monitoring routines or if it detects power system conditions that prevent flawless functioning of the unit, then an entry is made in the monitoring signal memory.
  • Page 84 6 Local Control Panel (continued) Readout of the event memories There are eight event memories for each type of event. The latest event is stored in event memory 1, the previous one in event memory 2, and so forth. Readout of event memories is illustrated using the fault memory as an example. Control Step / Description Control Display...
  • Page 85 6 Local Control Panel (continued) 6.5.7 Resetting All information memories – including the event memories and the monitoring signal memory – and also the LED indicators can be reset manually. In addition, the LED indicators are automatically cleared and initialized at the onset of a new fault – provided that the appropriate operating mode has been selected –...
  • Page 86 6 Local Control Panel (continued) 6.5.8 Password-Protected Control Actions Certain actions from the local control panel (such as a manual trip command for testing purposes) can only be carried out by entering a password. This setup is designed to prevent accidental output and applies even when the global change-enabling function has been activated.
  • Page 87 6 Local Control Panel (continued) Control Step / Description Control Display Action Oper/CtrlTest/MAIN Press the ENTER key again. The LED Man. trip cmd. USER indicator will go out. The unit will execute the Don't execute command. Oper/CtrlTest/MAIN As long as the LED indicator labeled EDIT Man.
  • Page 88 6 Local Control Panel (continued) The password can be changed by the user at any time. The procedure for this change is described below. The starting point is the factory-set password. Control Step / Description Control Display Action Par/Conf/LOC In the menu tree ‘Par/Conf/LOC’ select the Password parameter ‘Password’.
  • Page 89 6 Local Control Panel (continued) Control Step / Description Control Display Action Par/Conf/LOC Re-enter the password. Password Par/Conf/LOC Password Par/Conf/LOC Press the ENTER key again. If the Password password has been re-entered correctly, the ******** LED indicator labeled EDIT MODE goes out and the display appears as shown on the right.
  • Page 90 6 Local Control Panel (continued) If the configured password has been forgotten, it can be called up on the LCD display as described below. The procedure involves turning the device off and then on again. Control Step / Description Control Display Action Turn off the device.
  • Page 91 6 Local Control Panel (continued) Changing and display of the L/R password The L/R password must be entered to enable local control. Control Step / Description Control Display Action Par/Conf/LOC In the menu tree ‘Par/Conf/LOC’ select Password L/R parameter ‘Password L/R’. ******** Par/Conf/LOC Press enter key.
  • Page 92 6 Local Control Panel (continued) Control Step / Description Control Display Action Par/Conf/LOC Re-enter the L/R password. Password L/R Par/Conf/LOC Password L/R Par/Conf/LOC Press enter key once more. If the Password L/R password has been repeated correctly, the ******** “EDIT MODE” LED goes out and the display changes as illustrated.
  • Page 93 7 Settings Settings Parameters The C232 must be adjusted to the system and to the protected equipment by means of appropriate settings. This section gives instructions for determining the settings, which are located in the folder entitled ‘Parameters’ in the menu tree. The sequence in which the settings are listed and described in this chapter corresponds to their sequence in the menu tree.
  • Page 94 7 Settings (continued) 7.1.1 Device Identification The device identification settings are used to record the ordering information and the design version of the C232. They have no effect on the device functions. These settings should only be changed if the design version of the C232 is modified. DVICE: Device type Device 000 000...
  • Page 95 7 Settings (continued) DVICE: Order ext. No. 26 000 028 DVICE: Order ext. No. 27 000 029 The order extension number for the device. DVICE: Module var. slot 1 086 050 DVICE: Module var. slot 2 086 051 DVICE: Module var. slot 3 086 052 Item number of the module inserted in the respective slot.
  • Page 96 7 Settings (continued) 7.1.2 Configuration Parameters LOC: Language Local control panel 003 020 Language in which texts will be displayed on the local control panel. LOC: Decimal delimiter 003 021 Character to be used as decimal delimiter on the local control panel. LOC: Password 003 035 The password to be used for changing settings from the local control panel...
  • Page 97 7 Settings (continued) LOC: Fct. Operation Panel Fig. 3-3 053 007 Definition of the values to be displayed on the Measured Value Panel referred to as the Operation Panel. LOC: Fct. Fault Panel Fig. 3-4 053 003 Definition of the values to be displayed on the Fault Panel. LOC: Fct.asg.
  • Page 98 7 Settings (continued) PC: Name of manufacturer PC link Fig. 3-6 003 183 Setting for the name of the manufacturer. Note: This setting can be changed to ensure compatibility. PC: Bay address Fig. 3-6 003 068 PC: Device address 003 069 Bay and device addresses are used to address the device in communication via the PC interface.
  • Page 99 COMM1: -103 prot. variant Fig. 3-8 003 178 The user may select either the AREVA D or the AREVA variant of the 103 protocol. Note: This setting is hidden unless the IEC 870-5-xxx protocol is enabled. COMM1: MODBUS prot. variant Fig.
  • Page 100 7 Settings (continued) The C232 monitors telegram transmission to make sure that no pause within a telegram exceeds 33 bits. This monitoring function can be disabled if it is not required. Note: This setting is only necessary for modem transmission. COMM1: Mon.
  • Page 101 7 Settings (continued) Enable for the transmission of spontaneous signals via the communication interface. COMM1: Select. spontan.sig. Fig. 3-8, 3-9, 003 179 3-10 Selection of signals transmitted via the communication interface, e.g. from private range of IEC 60870-5-103. COMM1: Transm.enab.cycl.dat Fig.
  • Page 102 7 Settings (continued) Setting for the communication address length. Note: This setting is hidden unless the IEC 870-5-101 protocol is enabled. COMM1: Octet 2 comm. addr. Fig. 3-9 003 200 Setting for the length of the higher-order communication address. Note: This setting is hidden unless the IEC 870-5-101 protocol is enabled.
  • Page 103 7 Settings (continued) COMM1: ASDU1 / ASDU20 conv. Fig. 3-9 003 190 Setting specifying whether telegram structure 1 or 20 shall be converted as a single signal or double signal. Note: This setting is hidden unless the IEC 870-5-101 protocol is enabled. (ASDU: Application Service Data Unit).
  • Page 104 7 Settings (continued) MODBUS registers in the range 30301 to 30400 are assigned to the selected measured values. Assignment is made in the order of selection. This means that the first measured value is given the register no. 30301, the second the register no.
  • Page 105 7 Settings (continued) COMM1: Autom.event confirm. Fig. 3-11 003 249 Setting specifying whether an event must be confirmed by the master in order for an event to be deleted from the 'event queue'. Note: This setting is hidden unless the MODBUS protocol is enabled. COMM1: Phys.
  • Page 106 7 Settings (continued) COMM1: Ind./cl. bin.outputs Fig. 3-12 003 233 Selection of data points and data classes for object 10 – binary outputs. Assignment of indices is made in the order of selection, beginning with 0. Note: This setting is hidden unless the DNP 3.0 protocol is enabled. COMM1: Ind./cl.
  • Page 107 7 Settings (continued) COMM2: Dead time monitoring Fig. 3-14 103 176 The C232 monitors telegram transmission to make sure that no excessive pause occurs within a telegram. This monitoring function can be disabled if it is not required. Note: This setting is only necessary for modem transmission. COMM2: Mon.
  • Page 108 7 Settings (continued) COMM2: Delta meas.v.ILS tel Fig. 3-14 103 150 The telegram is transmitted if a measured value differs by the set delta quantity from the last measured value transmitted. COMM2: Delta t Fig. 3-14 103 053 All measured data are transmitted again through the communication interface after this time period has elapsed –...
  • Page 109 7 Settings (continued) Binary inputs The C232 has optical coupler inputs for processing binary signals from the system. The number and connection schemes for the available binary inputs are shown in the terminal connection diagrams. The Address List gives information about the configuration options for all binary inputs.
  • Page 110 7 Settings (continued) The operating mode for each binary signal input can be defined. The user can specify whether the presence (active ‘high’ mode) or absence (active ‘low’ mode) of a voltage shall be interpreted as the logic ‘1’ signal. Note: The operating mode of the binary inputs is automatically set to active ‘high’...
  • Page 111 7 Settings (continued) MEASI: Function group MEASI Measured data input 056 030 Canceling function group MEASI or including it in the configuration. If the function group is cancelled from the configuration, then all associated settings and signals are hidden, with the exception of this setting. MEASI: General enable USER Fig.
  • Page 112 7 Settings (continued) MEASI: IDC,lin 1 Fig. 3-20 037 151 MEASI: IDC,lin 2 Fig. 3-20 037 153 MEASI: IDC,lin 3 Fig. 3-20 037 155 MEASI: IDC,lin 4 Fig. 3-20 037 157 MEASI: IDC,lin 5 Fig. 3-20 037 159 MEASI: IDC,lin 6 Fig.
  • Page 113 7 Settings (continued) Binary outputs The C232 has output relays for the output of binary signals. The number and connection schemes for the available output relays are shown in the terminal connection diagrams. The Address List gives information about the configuration options for all binary outputs. The C232 identifies the fitted modules during startup.
  • Page 114 7 Settings (continued) OUTP: Fct. assignm. K 201 Fig. 3-22 157 002 OUTP: Fct. assignm. K 202 157 006 OUTP: Fct. assignm. K 203 157 010 OUTP: Fct. assignm. K 204 157 014 OUTP: Fct. assignm. K 205 157 018 OUTP: Fct.
  • Page 115 7 Settings (continued) LED indicators The C232 has a total of 13 LED indicators for parallel display of binary signals. The Address List in the Appendix gives information about the configuration options for all LED indicators. The following table provides an overview. LED indicator Description on Configuration...
  • Page 116 7 Settings (continued) LED: Operating mode H 2 Fig. 3-24 085 002 LED: Operating mode H 3 085 005 LED: Operating mode H 4 085 008 LED: Operating mode H 5 085 011 LED: Operating mode H 6 085 014 LED: Operating mode H 7 085 017 LED: Operating mode H 8...
  • Page 117 7 Settings (continued) DTOC: Function group DTOC Definite-time overcurrent 056 008 protection Canceling function group DTOC or including it in the configuration. If the function group is cancelled from the configuration, then all associated settings and signals are hidden, with the exception of this setting. IDMT: Function group IDMT Inverse-time overcurrent 056 009...
  • Page 118 7 Settings (continued) DEV01: Function group DEV01 External devices 01 to 10 210 047 DEV02: Function group DEV02 210 097 DEV03: Function group DEV03 210 147 DEV04: Function group DEV04 210 197 DEV05: Function group DEV05 210 247 DEV06: Function group DEV06 211 047 DEV07: Function group DEV07 211 097...
  • Page 119 7 Settings (continued) DEV01: Funct. type, command 210 032 DEV02: Funct. type, command 210 082 DEV03: Funct. type, command 210 132 DEV04: Funct. type, command 210 182 DEV05: Funct. type, command 210 232 DEV06: Funct. type, command 211 032 DEV07: Funct. type, command 211 082 DEV08: Funct.
  • Page 120 7 Settings (continued) SIG_1: Function group SIG_1 Single-pole signals 249 250 Canceling function group SIG_1 or including it in the configuration. If the function group is cancelled from the configuration, then all associated settings and signals are hidden, with the exception of this setting. SIG_1: Signal S001 config.
  • Page 121 7 Settings (continued) 7.1.3 Function Parameters 7.1.3.1 Global PC: Command blocking PC link Fig. 3-6 003 182 When command blocking is activated, commands are rejected at the PC interface. PC: Sig./meas.val.block. Fig. 3-6 003 086 When signal and measured value blocking is activated, no signals or measured data are transmitted through the PC interface.
  • Page 122 7 Settings (continued) MAIN: Inom device 010 003 Setting for the secondary nominal current of the system transformer for measurement of phase currents. This also corresponds to the nominal device current. MAIN: Vnom V.T. sec. 010 009 Setting for the secondary nominal voltage of the system transformer for measurement of phase-to-ground and phase-to-phase voltages.
  • Page 123 7 Settings (continued) MAIN: Min.dur. trip cmd. 1 Fig. 3-50 021 003 Setting for the minimum duration of trip command 1. MAIN: Min.dur. trip cmd. 2 Fig. 3-50 021 004 Setting for the minimum duration of trip command 2. MAIN: Latching trip cmd. 1 Fig.
  • Page 124 7 Settings (continued) MAIN: Cmd. dur. short cmd. Fig. 3-110, 221 231 3-114 Setting for the command duration of a short command. MAIN: Inp.asg.interl.deact Fig. 3-54 221 007 Definition of the binary signal used to deactivate interlocking of the control commands of the switchgear units.
  • Page 125 7 Settings (continued) PSS: Control via USER Parameter subset selection Fig. 3-62 003 100 If parameter subset selection is to be handled from the integrated local control panel rather than via the binary signal inputs, choose the ‘Yes’ setting. PSS: Param.subs.sel. USER Fig.
  • Page 126 7 Settings (continued) 7.1.3.2 General Functions MAIN: Hold time dyn.param. Main function Fig. 3-39 018 009 Setting for the hold time of the "dynamic parameters". After switching to the "dynamic" thresholds, the latter will remain active in place of the "normal" thresholds during this period.
  • Page 127 7 Settings (continued) LIMIT: tI> Fig. 3-93 014 031 Setting for the operate delay of the first overcurrent stage of limit value monitoring. LIMIT: tI>> Fig. 3-93 014 032 Setting for the operate delay of the second overcurrent stage of limit value monitoring.
  • Page 128 7 Settings (continued) LIMIT: VPP>> Fig. 3-94 014 028 Setting for the operate value of overvoltage stage VPP>> of limit value monitoring. LIMIT: tVPP> Fig. 3-94 014 039 Setting for the operate delay of overvoltage stage VPP> of limit value monitoring.
  • Page 129 7 Settings (continued) LIMIT: IDC,lin<< Fig. 3-96 014 115 Setting for operate value IDC,lin<< for monitoring the linearized direct current. LIMIT: tIDC,lin< Fig. 3-96 014 116 Setting for the operate delay of undercurrent stage IDC,lin<. LIMIT: tIDC,lin<< Fig. 3-96 014 117 Setting for the operate delay of undercurrent stage IDC,lin<<.
  • Page 130 7 Settings (continued) LOGIC: Fct.assignm. outp.30 031 016 LOGIC: Fct.assignm. outp.31 031 020 LOGIC: Fct.assignm. outp.32 031 024 These settings assign functions to the outputs. LOGIC: Op. mode t output 1 Fig. 3-98 030 001 LOGIC: Op. mode t output 2 030 005 LOGIC: Op.
  • Page 131 7 Settings (continued) LOGIC: Time t1 output 16 030 062 LOGIC: Time t1 output 17 030 066 LOGIC: Time t1 output 18 030 070 LOGIC: Time t1 output 19 030 074 LOGIC: Time t1 output 20 030 078 LOGIC: Time t1 output 21 030 082 LOGIC: Time t1 output 22 030 086...
  • Page 132 7 Settings (continued) LOGIC: Time t2 output 30 031 019 LOGIC: Time t2 output 31 031 023 LOGIC: Time t2 output 32 031 027 Settings for timer stage t2 of the respective outputs. Note: This setting has no effect in the ‘minimum time’ operating mode. LOGIC: Sig.assig.
  • Page 133 7 Settings (continued) LOGIC: Sig.assig.outp.12(t) 044 023 LOGIC: Sig.assig.outp.13(t) 044 025 LOGIC: Sig.assig.outp.14(t) 044 027 LOGIC: Sig.assig.outp.15(t) 044 029 LOGIC: Sig.assig.outp.16(t) 044 031 LOGIC: Sig.assig.outp.17(t) 044 033 LOGIC: Sig.assig.outp.18(t) 044 035 LOGIC: Sig.assig.outp.19(t) 044 037 LOGIC: Sig.assig.outp.20(t) 044 039 LOGIC: Sig.assig.outp.21(t) 044 041 LOGIC: Sig.assig.outp.22(t) 044 043...
  • Page 134 7 Settings (continued) CMD_1: Design. command C001 Single-pole commands 200 000 CMD_1: Design. command C002 200 005 CMD_1: Design. command C003 200 010 CMD_1: Design. command C004 200 015 CMD_1: Design. command C005 200 020 CMD_1: Design. command C006 200 025 CMD_1: Design.
  • Page 135 7 Settings (continued) SIG_1: Designat. sig. S001 Single-pole signals 226 000 SIG_1: Designat. sig. S002 226 008 SIG_1: Designat. sig. S003 226 016 SIG_1: Designat. sig. S004 226 024 SIG_1: Designat. sig. S005 226 032 SIG_1: Designat. sig. S006 226 040 SIG_1: Designat.
  • Page 136 7 Settings (continued) SIG_1: Gr.asg. debounc.S011 226 083 SIG_1: Gr.asg. debounc.S012 226 091 SIG_1: Gr.asg. debounc.S013 226 099 SIG_1: Gr.asg. debounc.S014 226 107 SIG_1: Gr.asg. debounc.S015 226 115 SIG_1: Gr.asg. debounc.S016 226 123 SIG_1: Gr.asg. debounc.S017 226 131 SIG_1: Gr.asg. debounc.S018 226 139 SIG_1: Gr.asg.
  • Page 137 7 Settings (continued) TAPCH: Designation TapCh 1 Tap changers Fig. 3-118 249 100 Assignment of a name to the tap changer. TAPCH: Inp.assign. TapCh 1 Fig. 3-118 249 101 Assignment of the tap changer position signal to the binary signal inputs in BCD code.
  • Page 138 7 Settings (continued) 7.1.3.3 Parameter Subsets DTOC: Enable Definite-time overcurrent Fig. 3-72 072 098 073 098 074 098 075 098 protection This setting defines the parameter subset in which definite-time overcurrent protection is enabled. DTOC: I> Fig. 3-73 017 000 073 007 074 007 075 007 Setting for the operate value of the first overcurrent stage (phase current stage).
  • Page 139 7 Settings (continued) DTOC: tI>> Fig. 3-73 017 006 073 020 074 020 075 020 Setting for the operate delay of the second overcurrent stage. DTOC: tI>>> Fig. 3-73 017 007 073 021 074 021 075 021 Setting for the operate delay of the third overcurrent stage. DTOC: IN>...
  • Page 140 7 Settings (continued) DTOC: tIN>> Fig. 3-76 017 010 073 028 074 028 075 028 Setting for the operate delay of the second overcurrent stage (residual current stage). DTOC: tIN>>> Fig. 3-76 017 019 073 029 074 029 075 029 Setting for the operate delay of the third overcurrent stage (residual current stage).
  • Page 141 7 Settings (continued) IDMT: Factor kt,neg PSx Fig. 3-88 072 054 073 054 074 054 075 054 Setting for factor kt,neg of the starting characteristic (negative-sequence current system). IDMT: Min.trip time negPSx Fig. 3-88 072 078 073 078 074 078 075 078 Setting for the minimum trip time (negative-sequence current system).
  • Page 142 7 Settings (continued) 7.1.3.4 Control MAIN: BI active USER Main functions Fig. 3-54 221 003 Enabling the bay interlocking function from the local control panel. MAIN: SI active USER Fig. 3-54 221 002 Enabling the station interlocking function from the local control panel. MAIN: Inp.asg.
  • Page 143 7 Settings (continued) DEV01: Designat. ext. dev. External devices 01 t o10 Fig. 3-2 210 000 DEV02: Designat. ext. dev. 210 050 DEV03: Designat. ext. dev. 210 100 DEV04: Designat. ext. dev. 210 150 DEV05: Designat. ext. dev. 210 200 DEV06: Designat.
  • Page 144 7 Settings (continued) DEV01: Interm. pos. suppr. Fig. 3-105, 210 012 3-111 DEV02: Interm. pos. suppr. 210 062 DEV03: Interm. pos. suppr. 210 112 DEV04: Interm. pos. suppr. 210 162 DEV05: Interm. pos. suppr. 210 212 DEV06: Interm. pos. suppr. 211 012 DEV07: Interm.
  • Page 145 7 Settings (continued) DEV01: With gen. trip cmd.1 Fig. 3-109 210 021 DEV02: With gen. trip cmd.1 210 071 DEV03: With gen. trip cmd.1 210 121 DEV04: With gen. trip cmd.1 210 171 DEV05: With gen. trip cmd.1 210 221 DEV06: With gen.
  • Page 146 7 Settings (continued) DEV01: Inp.asg.el.ctrl.open Fig. 3-106 210 019 DEV02: Inp.asg.el.ctrl.open 210 069 DEV03: Inp.asg.el.ctrl.open 210 119 DEV04: Inp.asg.el.ctrl.open 210 169 DEV05: Inp.asg.el.ctrl.open 210 219 DEV06: Inp.asg.el.ctrl.open 211 019 DEV07: Inp.asg.el.ctrl.open 211 069 DEV08: Inp.asg.el.ctrl.open 211 119 DEV09: Inp.asg.el.ctrl.open 211 169 DEV10: Inp.asg.el.ctrl.open 211 219 This setting defines the binary signal that will be used as the control signal...
  • Page 147 7 Settings (continued) DEV01: Inp. asg. end Close Fig. 3-112 210 016 DEV02: Inp. asg. end Close 210 066 DEV03: Inp. asg. end Close 210 116 DEV04: Inp. asg. end Close 210 166 DEV05: Inp. asg. end Close 210 216 DEV06: Inp.
  • Page 148 7 Settings (continued) DEV01: Fct.assig.BiwSI open Fig. 3-107 210 039 DEV02: Fct.assig.BiwSI open 210 089 DEV03: Fct.assig.BiwSI open 210 139 DEV04: Fct.assig.BiwSI open 210 189 DEV05: Fct.assig.BiwSI open 210 239 DEV06: Fct.assig.BiwSI open 211 039 DEV07: Fct.assig.BiwSI open 211 089 DEV08: Fct.assig.BiwSI open 211 139 DEV09: Fct.assig.BiwSI open...
  • Page 149 7 Settings (continued) DEV01: Fct.asg.BI w/o SI op Fig. 3-107 210 041 DEV02: Fct.asg.BI w/o SI op 210 091 DEV03: Fct.asg.BI w/o SI op 210 141 DEV04: Fct.asg.BI w/o SI op 210 191 DEV05: Fct.asg.BI w/o SI op 210 241 DEV06: Fct.asg.BI w/o SI op 211 041 DEV07: Fct.asg.BI w/o SI op...
  • Page 150 7 Settings (continued) ILOCK: Fct.assignm. outp. 1 Interlocking logic Fig. 3-113 250 000 ILOCK: Fct.assignm. outp. 2 250 001 ILOCK: Fct.assignm. outp. 3 250 002 ILOCK: Fct.assignm. outp. 4 250 003 ILOCK: Fct.assignm. outp. 5 250 004 ILOCK: Fct.assignm. outp. 6 250 005 ILOCK: Fct.assignm.
  • Page 151 8 Information and Control Functions Information and Control Functions C232 generates a large number of signals, processes binary input signals, and acquires measured data during fault-free operation of the protected object as well as fault-related data. A number of counters are maintained for statistical purposes. This information can be read out from the integrated local control panel.
  • Page 152 8 Information and Control Functions (continued) MAIN: Curr. IP,max prim. Fig. 3-30 005 050 Display of the maximum phase current as a primary quantity. MAIN: IP,max prim.,delay Fig. 3-30 005 036 Display of the delayed maximum phase current as a primary quantity. MAIN: IP,max prim.,stored Fig.
  • Page 153 8 Information and Control Functions (continued) MAIN: Active power P prim. Fig. 3-34 004 050 Display of the updated active power value as a primary quantity. MAIN: Reac. power Q prim. Fig. 3-34 004 052 Display of the updated reactive power value as a primary quantity. MAIN: Act.energy outp.prim Fig.
  • Page 154 8 Information and Control Functions (continued) MAIN: Voltage VPP,max p.u. Fig. 3-33 008 045 Display of the maximum phase-to-phase voltage referred to V MAIN: Voltage VPP,min p.u. Fig. 3-33 009 045 Display of the minimum phase-to-phase voltage referred to V MAIN: Voltage A-B p.u.
  • Page 155 8 Information and Control Functions (continued) 8.1.1.2 Physical State Signals INP: State U 201 Binary inputs 178 001 INP: State U 202 178 005 INP: State U 203 178 009 INP: State U 204 178 013 INP: State U 205 178 017 INP: State U 206 178 021...
  • Page 156 8 Information and Control Functions (continued) OUTP: State K 201 Binary outputs 157 001 OUTP: State K 202 157 005 OUTP: State K 203 157 009 OUTP: State K 204 157 013 OUTP: State K 205 157 017 OUTP: State K 206 157 021 OUTP: State K 207 157 025...
  • Page 157 8 Information and Control Functions (continued) 8.1.1.3 Logic State Signals LOC: Illumination on EXT Local control panel 037 101 LOC: Loc.acc.block.active Fig. 3-5 221 005 LOC: Rem.acc.block.active Fig. 3-5 221 004 COMM1: Command block. EXT “Logical” communication Fig. 3-7, 3-8, 003 173 3-9, 3-10, interface 1...
  • Page 158 8 Information and Control Functions (continued) MAIN: Enable control Fig. 3-54 221 058 MAIN: Test mode Fig. 3-61 037 071 MAIN: Blocked/faulty Fig. 3-43 004 065 MAIN: Trip cmd. blocked Fig. 3-50 021 013 MAIN: Latch. trip c. reset Fig. 3-50 040 139 MAIN: Manual trip signal Fig.
  • Page 159 8 Information and Control Functions (continued) PSS: Control via user EXT Parameter subset selection Fig. 3-62 036 101 PSS: Activate PS 1 EXT Fig. 3-62 065 002 PSS: Activate PS 2 EXT Fig. 3-62 065 003 PSS: Activate PS 3 EXT Fig.
  • Page 160 8 Information and Control Functions (continued) SFMON: Invalid arithm. op. 093 011 SFMON: Undefined interrupt 093 012 SFMON: Exception oper.syst. 093 013 SFMON: Data acquis. failure 090 021 SFMON: Checksum error param 090 003 SFMON: Clock sync. error 093 041 SFMON: Overflow MT_RC Fig.
  • Page 161 8 Information and Control Functions (continued) DTOC: tIN>> elapsed Fig. 3-76 040 121 DTOC: tIN>>> elapsed Fig. 3-76 039 079 DTOC: Trip signal tIN> Fig. 3-77 041 021 DTOC: Trip signal tIN>> Fig. 3-77 040 028 DTOC: Trip signal tIN>>> Fig.
  • Page 162 8 Information and Control Functions (continued) LIMIT: tIDC,lin> elapsed Fig. 3-96 040 182 LIMIT: tIDC,lin>> elapsed Fig. 3-96 040 183 LIMIT: Starting IDC,lin< Fig. 3-96 040 184 LIMIT: Starting IDC,lin<< Fig. 3-96 040 185 LIMIT: tIDC,lin< elapsed Fig. 3-96 040 186 LIMIT: tIDC,lin<<...
  • Page 163 8 Information and Control Functions (continued) LOGIC: 7 set externally 034 081 LOGIC: 8 set externally 034 082 LOGIC: Enabled Fig. 3-98 034 046 LOGIC: Output 1 Fig. 3-98 042 032 LOGIC: Output 2 042 034 LOGIC: Output 3 042 036 LOGIC: Output 4 042 038 LOGIC: Output 5...
  • Page 164 8 Information and Control Functions (continued) LOGIC: Output 19 (t) 042 069 LOGIC: Output 20 (t) 042 071 LOGIC: Output 21 (t) 042 073 LOGIC: Output 22 (t) 042 075 LOGIC: Output 23 (t) 042 077 LOGIC: Output 24 (t) 042 079 LOGIC: Output 25 (t) 042 081...
  • Page 165 8 Information and Control Functions (continued) DEV08: Switch. device open 211 136 DEV09: Switch. device open 211 186 DEV10: Switch. device open 211 236 DEV01: Switch.device closed Fig. 3-111 210 037 DEV02: Switch.device closed 210 087 DEV03: Switch.device closed 210 137 DEV04: Switch.device closed 210 187 DEV05: Switch.device closed...
  • Page 166 8 Information and Control Functions (continued) ILOCK: Output 8 250 039 ILOCK: Output 9 250 040 ILOCK: Output 10 250 041 ILOCK: Output 11 250 042 ILOCK: Output 12 250 043 ILOCK: Output 13 250 044 ILOCK: Output 14 250 045 ILOCK: Output 15 250 046 ILOCK: Output 16...
  • Page 167 8 Information and Control Functions (continued) SIG_1: Signal S014 EXT 226 108 SIG_1: Signal S015 EXT 226 116 SIG_1: Signal S016 EXT 226 124 SIG_1: Signal S017 EXT 226 132 SIG_1: Signal S018 EXT 226 140 SIG_1: Signal S019 EXT 226 148 SIG_1: Signal S020 EXT 226 156...
  • Page 168 8 Information and Control Functions (continued) 8.1.2 Control and Testing DVICE: Service info 031 080 Device 031 080 LOC: Param. change enabl. Local control panel 003 010 Setting the enable for changing values from the local control panel. COMM1: Sel.spontan.sig.test “Logical“...
  • Page 169 8 Information and Control Functions (continued) Reset of the following memories: All counters LED indicators Operating data memory All event memories Event counters Fault data Measured overload data Recorded fault values This control action is password-protected (see section entitled ‘Password- Protected Control Operations’...
  • Page 170 8 Information and Control Functions (continued) OP_RC: Reset recording Operating data recording Fig. 3-64 100 001 The operating data memory and the counter for operation signals are reset. MT_RC: Reset recording Monitoring signal recording Fig. 3-65 003 008 Reset of the monitoring signal memory. FT_RC: Trigger USER Fault recording Fig.
  • Page 171 8 Information and Control Functions (continued) Events 8.2.1 Event Counters MAIN: No. general start. Main functions Fig. 3-48 004 000 Number of general starting signals. MAIN: No. gen.trip cmds. 1 Fig. 3-52 004 006 Number of general trip commands 1. MAIN: No.
  • Page 172 8 Information and Control Functions (continued) 8.2.2 Measured Fault Data FT_DA: Fault duration Fault data acquisition Fig. 3-66 008 010 Display of the fault duration. FT_DA: Running time Fig. 3-66 004 021 Display of the running time. FT_DA: Fault current P p.u. Fig.
  • Page 173 9 Commissioning Commissioning Safety Instructions The device must be reliably grounded before auxiliary voltage is turned on. The surface-mounted case is grounded using the appropriate bolt and nut as the ground connection. The flush-mounted case must be grounded in the area of the rear sidepieces at the location provided.
  • Page 174 9 Commissioning (continued) Commissioning Tests Preparation After the C232 has been installed and connected as described in Chapter 5, the commissioning procedure can begin. Before turning on the power supply voltage, the following items must be checked again: Is the device connected to the protective ground at the specified location? Does the nominal voltage of the battery agree with the nominal auxiliary voltage of the device? Are the current and voltage transformer connections, grounding, and phase...
  • Page 175 9 Commissioning (continued) If either the PC interface or the communication interface will be used for setting the C232 and reading out event records, then the following settings must first be made from the integrated local control panel. ‘Par/DvID/’ folder: D V I C E : D e v i c e p a s s w o r d 1 D V I C E : D e v i c e p a s s w o r d 2 ‘Par/Conf/’...
  • Page 176 9 Commissioning (continued) After the settings have been made, the following checks should be carried out again before blocking is canceled: Has the appropriate bay type been configured? Does the function assignment of the binary signal inputs agree with the terminal connection diagram? Has the correct operating mode been selected for the binary signal inputs? Does the function assignment of the output relays agree with the terminal connection...
  • Page 177 9 Commissioning (continued) Checking the binary signal inputs By selecting the corresponding state signal (‘Oper/Cycl/Phys’ folder), it is possible to determine whether the input signal that is present is recognized correctly by the C232. The values displayed have the following meanings: Low: Not energized.
  • Page 178 9 Commissioning (continued) Checking the protection function Four parameter subsets are stored in the C232, one of which is activated. Before checking the protective function, the user should determine which parameter subset is activated. The activated parameter subset is displayed at P S S : A c t u a l p a r a m . s u b s e t ('Oper/Cycl/Log/"...
  • Page 179 9 Commissioning (continued) The trip times for the inverse-time overcurrent protection function as a function of the set tripping characteristics are shown in the following table: Tripping Formula for the Constants Formula for the Characteristic Tripping Release Characteristic Characteristic k = 0.01 to 10.00 0 Definite Time Per IEC 255-3 ⋅...
  • Page 180 9 Commissioning (continued) Testing the control functions The selected bay type is displayed on the Bay Panel. The activation of the Bay Panel display is described in Chapter 6. If the position signals of the switchgear units are connected correctly to the C232, then the updated switching status of the switchgear units will be displayed on the bay panel.
  • Page 181 9 Commissioning (continued) To determine which interlocks are activated, check as follows: For bay interlock (BI) check: M A I N : B a y i n t e r l o c k . a c t . , 'Oper/Cycl/Log/' folder For substation interlock (SI) check: M A I N : S u b s t .
  • Page 182 9 Commissioning (continued) Completion of commissioning Before the C232 is released for operation, the user should make sure that the following steps have been taken: All memories have been reset. (Reset at M A I N : G e n e r a l r e s e t (password-protected) and M T _ R C : R e s e t r e c o r d i n g , both in 'Oper/CtrlTest/ folder.) Blocking of output relays has been canceled.
  • Page 183: Troubleshooting

    10 Troubleshooting 10 Troubleshooting This chapter describes problems that might be encountered, their causes, and possible methods for eliminating them. It is intended as a general orientation only, and in cases of doubt it is better to return the C232 to the manufacturer. Please follow the packaging instructions in the section entitled ‘Unpacking and Packing’...
  • Page 184 10 Troubleshooting (continued) SFMON: Cold restart 093 024 A cold restart has been carried out on account of a checksum error in the memory (NOVRAM). 1st device reaction / 2nd device reaction: Warm restart / Device blocking 'Warning' output relay: Yes / Yes 'Blocked/faulty' output relay: Yes / Yes...
  • Page 185 10 Troubleshooting (continued) SFMON: +24V supply faulty 093 082 The +24 V internal supply voltage has dropped below a minimum value. 1st device reaction / 2nd device reaction: Warm restart / Device blocking 'Warning' output relay: Yes / Yes 'Blocked/faulty' output relay: Yes / Yes SFMON: -15V supply faulty 093 080...
  • Page 186 10 Troubleshooting (continued) SFMON: Undef. operat. code 093 010 Undefined operation code, i.e. software error. 1st device reaction / 2nd device reaction: Warm restart / Device blocking 'Warning' output relay: Yes / Yes 'Blocked/faulty' output relay: Yes / Yes SFMON: Invalid arithm. op. 093 011 Invalid arithmetic operation, i.e.
  • Page 187 10 Troubleshooting (continued) SFMON: Overflow MT_RC 090 012 Last entry in the monitoring signal memory in the event of overflow. 1st device reaction / 2nd device reaction: – / – 'Warning' output relay: Yes / Yes 'Blocked/faulty' output relay: – / – SFMON: Semaph.
  • Page 188 10 Troubleshooting (continued) 10-6 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 189: Maintenance

    When the operating temperatures inside the devices are lower, the required maintenance intervals are increased accordingly. Replacement of the maintenance-related components named above is not possible without soldering. Maintenance work must be carried out by AREVA service personnel only. Routine functional testing The C232 is used as a safety device and must therefore be routinely checked for proper operation.
  • Page 190 11 Maintenance (continued) In addition, a dynamic test can be used to check transmission performance and the phase relation of the current transformers and the anti-aliasing filter. A dynamic test is not absolutely necessary, since it only checks the stability of a few less passive components.
  • Page 191 12 Storage 12 Storage Devices must be stored in a dry and clean environment. A temperature range of -25°C to +70°C (-13°F to +158°F) must be maintained during storage (see the Chapter on Technical Data). The relative humidity must be controlled so that neither condensation nor ice formation will result.
  • Page 192 12-2 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 193: Accessories And Spare Parts

    13 Accessories and Spare Parts 13 Accessories and Spare Parts The C232 is supplied with standard labeling for the LED indicators. User-specific labeling for non-standard configurations of the LED’s can be printed on the blank label strips packed with the device. The label strip can then be glued to the front panel area reserved for this purpose.
  • Page 194 13-2 C232-302-401/402/403/404-603 / C232/EN M/A23...
  • Page 195: Order Information

    14 Order Information C232 Designs Order No. Compact Bay Unit for Control and Monitoring C232 C232- 0 -302 -603 -XXX Compact case Wall-mounting and fush-mounting, local HMI with graphic LCD Model 1 1 0 0 0 0 -401 1 two-pole switching command with checkback signals 2 two-pole breaker position indications or 4 free inputs and 4 free inputs...
  • Page 197 Region Your Contact: South East Asia Tel. : +65 67 49 07 77 Fax : +65 68 41 95 55 Pacific Tel. : +65 67 49 07 77 Fax: +65 68 46 17 95 China | | Tel. : +86 10 64 10 62 88 Fax : +86 10 6410 62 64 India Tel.
  • Page 198 T R AN S MIS S IO N & D IS T R IBU T IO N Energy Automation & Information energy.automation-information@ areva-td.com www.areva.com...

This manual is also suitable for:

302-401-603302-402-603302-403-603302-404-603