1. Description
®
The Digalox
DPM72 devices with Modbus interface can communicate as master or
slave with other DPM72 devices or devices from other manufacturers via the
Modbus RTU protocol. Values from the device are available as display values,
values from other devices can be integrated into the display as remote values. In
master mode, values can also be exchanged between two slaves with the help of a
buffer.
2. Specification
• 8 data bits, 1 stop bit
• Baud rate: adjustable up to 500,000 baud
• Parity: none, even, odd, space, mark
• ¼ unit load, up to 128 participants
• External terminating resistor required
3. Electrical connections
DPM72
A
A
GND
B
4. Configuration – general
To configure a device, disconnect it from the Modbus network, short-circuit terminal
J8 and connect the device to a PC using an RS485 USB adapter. "RS485 config"
appears on the display (if available), the device can now be configured using the
"Digalox
®
Manager" software. After completing the configuration, open J8 again. For
devices with a display, all values that are to be transferred must also be visible on
the display. Devices without a display provide the first four configured display
values. By setting jumpers J4-J6, different display values are provided accordingly.
®
Digalox
DPM72 RS485/Modbus interface
Instruction manual (Rev-2022-07)
R
= 120 - 270 Ω (external terminating resistor)
t
R
t
620 Ω
----- 5 / 8 -----

Advertisement

loading
Need help?

Need help?

Do you have a question about the Digalox DPM72 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for TDE Instruments Digalox DPM72

  • Page 1 ® Digalox DPM72 RS485/Modbus interface Instruction manual (Rev-2022-07) 1. Description ® The Digalox DPM72 devices with Modbus interface can communicate as master or slave with other DPM72 devices or devices from other manufacturers via the Modbus RTU protocol. Values from the device are available as display values, values from other devices can be integrated into the display as remote values.
  • Page 2 5. Configuration – master In master operating mode, up to 64 actions can be defined, which the master carries out periodically. They allow read or write access to the Modbus registers of the slaves. A delay between the messages can be set via the master delay parameter in order to ensure compatibility with slower slaves.
  • Page 3 8. Status LEDs There are three LEDs on the rear of the device that indicate the device and bus state: • Power (green) • Bus (orange) • Act (red) State Meaning Power (green) shines Device on Bus (orange) shines or flashes Bus active Act (rot) flashes quickly or shines Device sends...
  • Page 4 Invalid register access requested by MB illegal data Check master master; Modbus exception 2 addr. configuration answered 12. Contact details TDE Instruments GmbH, Gewerbestraße 8, D-71144 Steinenbronn Phone: +49 7157 20801 E-mail: info@tde-instruments.de Internet: www.tde-instruments.de, www.digalox.com ----- 8 / 8 -----...