Gigabyte H263-S62-LAN1 User Manual page 15

Liquid cooling solution
Table of Contents

Advertisement

System
Management
Server
Operating Properties
System fan
Power Supply
Server
Operating Properties
Operating
Properties
System fan
Power Supply
Aspeed® AST2600 management controller
Š
GIGABYTE Management Console (AMI MegaRAC SP-X) web interface
Š
Dashboard
Š
HTML5 KVM
Š
Sensor Monitor (Voltage, RPM, Temperature, CPU Status ...etc.)
Š
Sensor Reading History Data
Š
FRU Information
Š
SEL Log in Linear Storage / Circular Storage Policy
Š
Hardware Inventory
Š
Fan Profile
Š
System Firewall
Š
Power Consumption
Š
Power Control
Š
LDAP / AD / RADIUS Support
Š
Backup & Restore Configuration
Š
Remote BIOS/BMC/CPLD Update
Š
Event Log Filter
Š
User Management
Š
Media Redirection Settings
Š
PAM Order Settings
Š
SSL Settings
Š
SMTP Settings
Š
Operating temperature: 10°C to 35°C
Š
Operating humidity: 8-80% (non-condensing)
Š
Non-operating temperature: -40°C to 60°C
Š
Non-operating humidity: 20%-95% (non-condensing)
Š
NOTE!
The environment ambient temperature and relative humidity are relative
Š
to the inlet supply water temperature and the coolant flow rate.
In the event that the room's relative humidity exceeds 60% then the inlet
Š
water temperature must be set between 40° to 45°C to avoid condensation
and to keep the system running optimally.