Wiring Requirements - Software House iSTAR Edge Installation And Operating Instructions Manual

Hide thumbs Also See for iSTAR Edge:
Table of Contents

Advertisement

Installation Requirements

Wiring Requirements

Signal
From
RS-485 Comm,
iSTAR
two wire
Edge
Power
iSTAR
Edge
RJ45-Ethernet
iSTAR
Edge
Supervised
iSTAR
Input
Edge or I8
Request-to-exit
iSTAR
(REX or RTE)
Edge or
RM-4/4E
module
Door contact
iSTAR
(DSM)
Edge or
RM-4/4E
module
Supervised
iSTAR
Input (UL)
Edge or I8
a
Note
Relay Control
RM-4
module
Reader Data
iSTAR
Edge or
RM-4/4E
module
a. To comply with UL requirements, use shielded, minimum 22 AWG stranded, twisted pair cable for monitor points,
DSMs, and REXs. Use Belden 9462 or equivalent.
b. Calculations are based on a single RM-4 reader with keypad and LCD (250 mA):
Using 22 AWG, distance = 600 ft. (.0165 Ω /ft.)
Using 18 AWG, distance = 1500 ft. (.0065 Ω /ft.)
10
Table 6 shows general wiring requirements for an iSTAR Edge and its
components.
TABLE 6. Equipment Wiring Specifications
Belden #
To
or equiv.
RM & I/O
9841
Modules
RM & I/O
8442/8461
Modules
Hub, Host
N/A
Input
8442/8461
Switch
8442/8461
Contact
8442/8461
Input
9462
ARM-1
9462
Proximity/
9942
Wiegand
signaling
read head
9260
Alpha wire
5386C
#
AWG
Prs
Shield
24
1
Yes
22/18
1
No
Cat 5 or
2
N/A
more
24
22/18
1
No
22/18
1
No
22/18
1
No
22
1
Yes
22
1
Yes
22
3
Yes
20
18
Max
Max. Wire
Length
Resistance
4000 ft.
103Ω
(1212 m)
b
Range of
See Note
600 ft. to
1500 ft.
depends
on AWG
8.4 Ω
328 ft.
(100 m)
32Ω
2000 ft.
(606 m)
32 Ω
2000 ft.
(606 m)
32Ω
2000 ft.
(606 m)
32Ω
2000 ft.
(606 m)
25 ft.
.04Ω
(7.6 m)
3.2 Ω (22)
200 ft.
(60.96 m)
3.2 Ω (20)
300 ft.
(91.4 m)
3.2 Ω (18)
500 ft.
(152.4 m)

Hide quick links:

Advertisement

Table of Contents
loading