The unit must be placed so that it cannot be flushed with water during operation. As an option, the unit can be provided with protection that allows the installation to withstand IP class X5. REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
Temovex unit. The cover is telescopic and will fit ceiling heights between 2,30 - 2,70 m. We recommend a gap of 5 mm between ceiling and duct cover to avoid any transfer of vibrations. REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
The bottom card can now be reached and set up with required functions. The printed circuit board screen print. REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
ECO mode. NOTE! When using ECO Remote, DO6 must be Electric heater, control signals (Terminal J4) configured for Normal flow, DO7 for Sum alarms and DI2 to ECO. REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
In this example, DI2 is selected. Connection of ULS, KAVK, CP-heating etc. (230V) Brown Blue KAVK Yellow/Green CP-heating Connection according to above, on any output DO4-DO7 and selected output configure to selected function. REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
Please note! The configuration of inputs and outputs should be in this order for the display to work: DO6 - Normal, DO7 - Alarm, DI1 - ECO, DI2 - Forc REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
Page 10
J6/1 J6/2 J10/3 J10/4 Connection Internet (Cloudigo) Connect an internet cable to DUC as on picture. Pull out the cable through a suitable lead-through on the top of the unit. REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
Page 15
Filter timer ☐No Activate Filter timer Number of days since start (Current value) __________ 2.23. Cloudigo ☐Yes Activate Cloudigo 2.24. Save settings Save current settings ☐Yes 2.25. User menu Temperature ☐Off REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
Demand setpoint should be the desired temperature in the room. 2.2.1.1.1. PI-settings temperature Setting of control parameters. 2.2.1.2. CO2-control Menu for setting the CO2 setpoint 2.2.1.2.1. PI-settings CO2 Setting of control parameters. REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
The supply air regulator is indirect acting, i.e., the output signal increases with decreasing temperature. With the correct P and I parameter, the temperature at the supply air sensor will be kept constant at the set setpoint. 2.4.2. Room control REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
ECO2 works just as well in ECO mode (when nobody home), as it does when you are at home and the unit is running at normal flow. · ECO2-boosting together with cooling can be turned off, if you want boosting together with heating only. REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
No alarm is given in the absence of cooling. Screen view at boosting and ECO. At fan speed between min and normal: ECO. At fan speed normal: Normal. At fan speed between normal and boost: ECO2. REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
If there is a fault in the freeze protection sensor, this generates a freeze protection alarm and a sensor error alarm and both fans stop, outdoor air damper and bypass will close. The heat valve will open to its maximum and the circulation pump for heat will continue to run. REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
If you want to change this, set at what outdoor temperature, bypass will be allowed to open if necessary. There is also an adjustable hysteresis, to prevent the bypass from open and close all times, if the temperature is around 0 degrees (default setting). REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
In the standard case the fans will run at the same speed (normal speed) all night long (22:00-06:00). In the morning boosting is allowed but still with a low set point (18 degrees) until the extended running time (4 h) has ended, which will be at 10:00h. REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
If start and stop is the same, it could make the relay toggle all the time if the outdoor temperature happens to be the set value. If stop temperature is set lower than start temperature, the start temp will have priority as both start and stop temp. REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
That means a new menu (Stove timer) is available to the right. Configuring stove timer. Two different times are set at the stove timer, the ignition time and the after time. REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
Modbus via TCP is normally on but should be deactivated if you use a "public network" in cases where you connect the controller to the internet. This is to prevent outsiders from being able to read from the controller. Complete Modbus list can be obtained from REC on request. REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500...
If a remote panel is ordered at the same time as the AHU, the configuration is done for remote panel at the factory. When ordering a remote panel as supplement later, the Modbus must be deactivated. Contact REC for help with this.
Press the right arrow and change to new alarm class. Tip: If you change an alarm from A or B to C, the alarm will be automatically acknowledged when the cause has disappeared. REC Indovent AB, Box 37, 431 21 Mölndal tel.031-675500 www.rec-indovent.se...
Page 32
Rec Indovent reserves the right to alter specifications and design without prior notice. REC Indovent AB Box 37, SE-431 21 Mölndal, Sweden Visiting address: Kärragatan 2 Tel: +46 31 67 55 00 Fax: +46 31 87 58 45 www.rec-indovent.se Certified according to ISO 9001/14001...