XIV. Appendix A: Terminal Strip Diagram
POWER IN:
V+
12VDC or 18-24VDC Input
V+
12VDC or 18-24VDC Input
GND
Power Supply and System Ground
GND
Power Supply and System Ground
SENSOR IN:
V+
Sensor Power
IN
Sensor Input
4-20mA:
OUT
4-20mA Output
GND
Power Supply and System Ground, 4-20mA return Path
RELAY 1-4:
Global Water
800-876-1172 • globalw.com
12VDC Input:
18-24VDC Input: SW7 ON, SW8 OFF
12VDC Sensor Power:
18-24VDC Sensor Power:
Sensor Power Continuous: SW3 ON
Sensor Power Switched: SW3 OFF (Power Saving Mode)
4-20mA Sensors: SW4 ON, SW5 ON
0-5VDC Sensors: SW4 OFF, SW5 ON
0-1VDC Sensors: SW4 OFF, SW5 OFF
SW7 OFF, SW8 ON
SW1 ON, SW2 OFF
SW1 OFF, SW2 ON
(18VDC Power Input Only)