TABLE OF CONTENTS 1. OPERATOR’S MANUAL 1.1. IMPORTANT INFORMATION/SAFETY INSTRUCTIONS ....................4 1.2. INTENDED USE ................................5 1.3. TRANSPORT AND STORAGE ............................5 1.4. SAFETY MEASURES REGARDING OPERATING OF THE UNIT ..................5 1.5. TECHNICAL SPECIFICATION ............................6 1.6. TECHNICAL DRAWINGS ..............................7 1.7.
1. OPERATOR’S MANUAL 1. 1. IMPORTANT INFORMATION Read the Operator’s Manual carefully before installation or any other activity related to work with the unit! AWENTA takes not responsibility for any damage resulting from incorrect operation, non-intended use or unauthorised repairs or modifications of the product.
1.2. INTENDED USE The unit is equipped with a cross-flow plate heat exchanger, electric heater (sold separately) and is designed to save thermal energy by its recuperation, being one of the elements used in energy-saving technology systems. The unit is considered a supplementary device and must not be used as a stand-alone, independent heating source.
1.5. TECHNICAL SPECIFICATION Specifications: AUROS 415 AUROS 605 Supply voltage 230 VAC/50Hz Maximum power consumption 280 W 340 W (without the pre-heater) Pre-heater power output (optional) 2000 W Electrical protection class IP protection class IP33 Capacity (at 100 Pa) 430 m 605 m Max motor speed 4000 rpm...
1.7. STANDARD SYSTEM COMPONENTS Connection pipes Control panel Air filters Preheater (optional)* By-pass damper Counter-flow heat exchanger Fans Feet (optional) Wall bracket *position of the heater for the LH version 1.8. LAYOUT OF CONNECTIONS – LEFT /RIGHT VERSIONS Left version Right version (standard) ATTENTION! Condensate drains do not apply to the version with an enthalpy exchanger.
Connection ports designation: INTAKE – outdoor air intake duct EXHAUST – used air exhaust duct EXTRACT – duct removing used air from rooms SUPPLY – duct supplying air to rooms 1.9. OPERATION PRINCIPLE Fresh air is drawn in with the air intake located outside the building. Then, using ventilation ducts, the air is transported to the air handling unit.
Page 11
SECURING ANGLE BAR - After hanging the air handling unit on a wall bracket, the angle bar protecting it against accidental sliding off the wall bracket must be attached. ● STANDING INSTALLATION - For standing installation, feet appropriate to the model of appliance are required. Do not use other feet than those provided by the manufacturer (feet sold separately).
Page 12
Minimum lengths of ventilation ducts To ensure the best efficiency of the air handling unit and to reduce aerodynamic losses due to turbulence, it is recommended to install a straight section of air duct at the entry and exit of the unit. The minimum recommended lengths of such straight sections: - 25 cm of an air conduit at the inlet side;...
● Recommended duct thickness depending on ambient temperature: Ventilation duct ambient temperature Air duct type: from -20°C to 0°C from 1°C to 14°C from +15°C to 20°C Insulation thickness for a given temperature range Supply 20 mm + (200 mm)* 50 mm 20 mm Exhaust:...
Page 14
Fan maintenance (once a year) Even with regular maintenance of the filters and recuperator, dust deposits may accumulate in the fans, which reduces the efficiency of the air handling unit and the amount of air supplied to the rooms. Use a soft cloth or brush to clean the fans. In order to avoid possible damage to the rotor, do not use water, chemically aggressive solvents, sharp objects etc.
Maintenance of the air ducting (every 5 years) Even if all the aforementioned maintenance activities of the air handling unit are performed properly, dust deposits may build up inside the air ducts, which reduces the air handling unit's efficiency. Air ducts are maintained by periodic cleaning or changing them.
2. NANO COLOR CONTROL PANEL 2.1. OPERATION PRINCIPLE The NANO COLOR determines the set room temperature and ventilation performance based on the selected operating program. Possible programs: ● By clock zones. You can set up two Comfort operation zones and one Out of Home zone (no is one in the apartment). Outside of these zones the Economy zone applies.
Page 17
NOTE: In order to ensure smooth data transmission it is necessary to install a ferrite filter on the power and communication wires between the AERO module and the NANO COLOR thermostat. When leading the conductors through the filter loop them around the ring as shown in the photo at the side.
2.3. DESCRIPTION OF THE MAIN SCREEN Digital communication indicating via C14 protocol, flashing orange dot indicates that communication is in progress. Menu button. Operating mode button. Depending on the configuration, one of the following symbols will appear: Operation without a thermostat and ventilation. Operation with a thermostat.
Page 19
The symbols appear for the enabled thermostat operation with heating and/or cooling. In the INTAKE TEMPERATURE CONTROL MODE, the ROOM option should be set in the ventilation service menu. Signal to other devices that the room is not heated enough and the heating needs to be turned on.
2.4. OPERATION MODE When the mode selection button (button 3 of the main screen) is pressed the mode screen appears, depending on the configuration. Moves to the thermostat and ventilation settings. See the SETTINGS section for a detailed description. Returns to the main screen. Moves to the thermostat information screen.
Holiday mode. Manual selection of the ventilation operation mode. Enables the OUT OF HOME (NANO1) program. Enables the HOLIDAY program. Switches the BY-PASS to automatic mode, constantly closing or opening it. Switches the ventilation to air mode. The option is invisible when the OUT OF HOME (NANO1) or HOLIDAY mode is on.
2.6. TEMPERATURE SETTINGS Clicking the button 6 from the SETTINGS section brings up the following screen. Use the buttons to set the desired temperature. Setting comfort temperature. Setting the economic temperature. Set the temperature in the OUT OF HOME mode. 2.7.
Exhaust temperature. Exhaust fan rpm. Ventilation run. Supply fan rpm. Temperature downstream the AHU Kit (only for the operating diagram 2). Calculated intake temperature. AHU Kit or cooler (only for the operating diagram 2). Secondary heater (when the SECONDARY HEATER CONTROL function is enabled). AO4 rpm.
Page 24
In the case of a manual change, the following screen will appear on the main screen when the button 4 is pressed: Activation of the WINTER mode (HEATING). Activation of the SUMMER mode (NO HEATING AND COOLING). Activation of the COOLING mode. Exit to the main screen.
Current system operation mode. Setting the temperature below which the WINTER mode is switched on. Highlighted item means that the parameter can be edited. Sets the temperature above which WINTER mode is switched off. Sets the temperature below which the COOLING mode will turn off. Sets the temperature above which COOLING mode is activated.
Page 26
VACS-1 is equipped with an automatic calibration algorithm. As to have proper reading, the room in which the sensor is located should be ventilated at least once a month, in order to correct the reference point. After connecting to the power supply the sensor shows the value of 500ppm CO2.
2.12. VEX4 MODULE The VEX4 add-on module extends the functionality of the NANO COLOR room panel with additional inputs and outputs. The module can be freely configured to suit your needs. Edit subtitles (visible when the Allow to edit subtitles option is enabled) Exit to the main screen.
Adjusting ventilation speed Open/close the BY-PASS Decrease/increase the current desired temperature 2.14. FOULED FILTER INDICATION Filter fouling can be signalled in 2 ways: 1. Text flashing on the main screen: 2. DIRTY FILTER! text flashing on the VENTILATION INFO CHANGE AIR FILTER screen.
View of the weekly schedule. Press to move on to the remaining days of the week and holiday schedule settings. By clicking the bar of the selected day schedule you enter the edit window. Pressing will take you to the main menu. Edit schedule window for Monday You can set 2 comfort zones and an out of home zone.
Page 30
IN-OUT settings. Configuration EX4 module of additional inputs and Ventilation settings. outputs. Distributor settings. Sensor settings. NANO panel settings. Exit to the main screen. Below, a diagram of the service menu structure is shown: *Detailed description in section 12.17.4 ________________________________________________________________ AUROS 415 / 605 Instruction Manual...
2.17.1. IN-OUT EX4 module support Enables operation with an additional VEX4 module. EX4 – D1 input config Configures D1/D2 input settings • None – input not supported, will not be displayed on the outputs screen. • Info only – the input status will only be displayed on the outputs screen. •...
Page 32
Winter/summer change method You can choose from any of the following options: • Manual – the user changes the heating season setting individually. • According to on the outside temperature: ◦ when the thermostat is in WINTER mode, if the outside temperature rises above the set value it will automatically change to the SUMMER mode.
2.17.4. VENTILATION The VENTILATION menu structure is shown below: VENTILATION-AERO 4 Service parameters User parameters Access with code 99 Access with service code Operating diagram Standard OUT OF HOME program Intake temp. ctrl. mode No exclusions Tpom function AHU Kit AO3 speed 1 * 30mPr/30mStop T naw function...
Page 34
Fireplace mode Allows you to work with the fireplace mode. Fireplace mode speed correction Sets the increase in the supply fan rpm relative to the exhaust fan by the value set in this parameter. Gear correction by sensors Enabling this option increases the speed of the supply and exhaust fans on detecting the exceedance of the permissible levels by the sensors.
Temp. of air intake corres. to outside temp When this function is activated, the temperature at the air intake is the same as the outside temperature, and this information is transmitted to other units in the C14 system. Function of relay 3 Configuration of R3 relay function: - GHE - CH...
The iNEXT internet module allows remote control of the air handling unit. The control can be performed via a web browser or by means of the free AWENTA PRO application (available for Android and iOS). The method of connecting the INEXT module is presented in the CONNECTION DIAGRAMS section.
5. WIRING DIAGRAMS 5.1 ELECTRICAL DIAGRAM OF THE AERO 4 CONTROLLER – version for operation scheme 1. Standard R1 – BY-PASS closing R2 – BY-PASS opening R3 – GHE, heat from thermostat or damper flag (depending on configuration) R4 – heating signal from NANO thermostat (room is cooled down in WINTER mode) R5 –...
NOTE: Connect the control panel, the INEXT module and the air quality or humidity sensors to the corresponding terminals marked “U-G-B-A” using a 4 x 0.5 300/300 V cable. The total length of the cables should not exceed 30 m. Route the communication cables at least 30 cm away from the 230 VAC supply cables.
5.5. CONNECTING THE NANO COLOR CONTROL PANEL WITH THE iNEXT VLAN INTERNET MODULE 5.6. CONNECTING THE NANO COLOR CONTROL PANEL WITH VACS-1 AIR QUALITY SENSOR Note! Only one VACS-1 sensor can be connected to the device. 5.7. CONNECTING THE NANO COLOR CONTROL PANEL WITH THE VSHC or VSHW SENSOR ________________________________________________________________ AUROS 415 / 605 Instruction Manual...
5.8. CONNECTING THE NANO COLOR CONTROL PANEL WITH VSHC or VSHW and VACS-1 SENSORS Note! Up to 4 VSHC or VSHW sensors and one VACS-1 sensor can be connected to the device. 5.9. CONNECTING THE VGER415/VGER605 PREHEATER Note! It is also possible to connect a secondary heater. In this case, use the PWM1 and + outputs instead of PWM2.
Need help?
Do you have a question about the PRO AUROS 415 and is the answer not in the manual?
Questions and answers