TY - 2090 1 - Introduction 1.1 - Description The PRESYS TY-2090 Transmitter is a microprocessor-based instrument which receives any process variable found in industrial plants as: temperature, pressure, flow, level, etc. It has non-volatile internal memory (E2PROM) for storing calibration values.
Note - Ranges and input types, the use of relays as alarms and alarm points are, among others, items which the user can program through the MCY-20 Configuration Module (if desired, specify such information so the whole programming may be previously done by PRESYS). Note: Any other software or hardware characteristic desired may be available upon request.
TY - 2090 Code Example: 1) TY-2090 - 1 - 0 - 1 - 0 - 1 - 0 - 0 This code defines a TY-2090 Transmitter with channel 1 output of 4-20 mA, which does not use the channel 2 output, has a SPDT relay for alarming, power supply within the range of 90-240 Vac, does not use RS communication, to be used in sheltered place with surface mounting.
Page 6
PRESYS Instruments TY - 2090 Outputs: • Analog output of 4-20 mA, 1 to 5 Vdc, 0 to 10 Vdc, use of optional cards with fitting foreseen for up to two 300 Vac modules galvanically isolated from inputs and power supply.
Page 7
PRESYS Instruments TY - 2090 2 - Wire Transmitter Power Supply: 24 Vdc voltage and 50 mA maximum, isolated from outputs, with short-circuit protection. Operating ambient: 0 to 50ºC temperature and 90% maximum relative humidity. Dimensions: 140mm x 53mm x 156mm (height, width, depth).
2 - Installation 2.1 - Mechanical Installation The TY-2090 Transmitter can be mounted on a surface or on all types of existing DIN rail, as illustrated in the figure below. Fig. 2 - Dimensional drawing and detail of the adapter for DIN rail 2.2 - Electrical Installation...
PRESYS Instruments TY - 2090 2.3.1 - Thermocouple Connection Whenever using just one thermocouple, the user should preferably connect it to input 1 of the Transmitter, in order to obtain greater accuracy, since the cold junction sensor is solidly attached to the I/O terminal and closer to input 1.
PRESYS Instruments TY - 2090 A 4-wire RTD is connected to the Transmitter in the same way as a 3-wire RTD, except that the fourth wire is disregarded and left disconnected, see figure 5. A 3-wire RTD provides greater accuracy than a 2-wire RTD.
PRESYS Instruments TY - 2090 If the Transmitter internal voltage source of 24 Vdc is used to power a 2-wire transmitter, the current is received only by terminal 1 (+) in case of input 1, and it is received only by terminal 4 (+) in case of input 2. Figure 6 illustrates both possibilities of connection.
PRESYS Instruments TY - 2090 0 to 55mV 0 to 55mV 0 to 55mV 0 a 55mV Power supply should not to be grounded 0 to 5V 0 to 5V 0 to 5V 0 to 5V Note 2 Note 1...
Page 14
PRESYS Instruments TY - 2090 For outputs 3 and 4 there are three different output types: SPDT relay, open collector voltage and solid-state relay. Figure 8 shows the Transmitter outputs. Notice that the I/O terminals will only show output signals if the corresponding optional module is installed and the output is correctly configured.
Instruments TY - 2090 2.6 Communication The TY-2090 Transmitter can communicate with computers via RS-232 or RS- 422/485 provided the optional communication module is installed and the proper communication parameters are configured via software. Specific information about communication and signal connection can be found in the Communication Manual.
PRESYS Instruments TY - 2090 When the MCY-20 Configuration Module is connected to the Transmitter under normal operation, the instrument begins to function as a transmitter and as a process monitor as well, through the Module display. Under configuration time operation mode the user, through the MCY-20 Configuration Module, selects and assigns values to the parameters which regulate the Transmitter functioning, when in normal operation.
Page 18
PRESYS Instruments TY - 2090 GENERAL PASS RIGHT WRONG OPERATION GENERAL 0000 PASS RIGHT OPERATION WRONG Fig. 10 - Password system by key and by value In case of password by key, the user should press the UP, DOWN and ENTER keys in sequence to enter the configuration levels.
Page 19
PRESYS Instruments TY - 2090 The configuration parameters are distributed over six increasing hierarchical levels, as shown in figure 11. In order to go through those levels and access the corresponding parameters the user may use the Module front keys with the following functions:...
Page 20
PRESYS Instruments TY - 2090 Level 1 - General In level 1 we have the options: TAG, SOFT, PASSWORD and INDIC (see figure 12). TAG - Enables an alphanumeric identification for the instrument. The procedure used to enter a TAG or any other parameter is the same as for the previously described password (see the functions of ENTER, UP and DOWN keys under password by value).
Page 21
PRESYS Instruments TY - 2090 The adjustable parameter range shown in figure 12 is given below. Mnemonic Parameter Adjustable Factory Value Unit Range instrument P2090 identification SOFT software version T-2.21 VALUE user password -9999 to 99999 TIME 1 channel 1 1.0 to 3000.0...
Page 22
PRESYS Instruments TY - 2090 Level 2 - Inputs Inputs level allows wheter to enable or not (by means of the option ANNUL) the type of sensor for input 1 and input 2. For sensor types we have the linear options (0 to 5V, 0 to 10V, 0 to 55mV, 0 to 20mA) and temperature (option TEMP), as illustrated in figure 13.
Page 23
PRESYS Instruments TY - 2090 The adjustable parameter range shown in figure 13 is given below. Mnemonic Parameter Adjustable Factory Value Unit Range LIM LOW input signal 0.0 to 100.0 corresponding to Eng Low LIM HIGH input signal 0.0 to 100.0 100.0...
Page 24
PRESYS Instruments TY - 2090 SQRT - Shows the square root of the Transmitter input signal on display. The Cut- Off parameter, expressed as a % of the input signal, forces the lower value inputs (Lim Low + Cut Off) to behave as Lim Low. See illustration on figure 15.
Page 25
PRESYS Instruments TY - 2090 FILTER - This parameter provides the time constant of a first order digital filter coupled to the selected input. When no filtering of the measured signal is desired, zero should be assigned to this parameter.
Page 26
PRESYS Instruments TY - 2090 SAFE - Provides relay safety. Relay safety condition means that relay coils are energized when the instrument is powered and are de-energized under alarm condition or in the event of a power failure. (1) FOLLOW THE SAME OPTIONS FOR REL AY 1.
Page 27
PRESYS Instruments TY - 2090 Level 4 - Outputs Level 4 allows the configuration of two possible analog outputs (see figure 18). (1) FOLLOW THE SAME OPTIONS AS FOR RELAY 1. Fig. 18 - OUTPUT level options The adjustable parameter range shown in figure 18 is given below.
Page 28
PRESYS Instruments TY - 2090 IN - Associates analog output 1 or 2 with input 1 or 2 which will be retransmitted. Notice that outputs 1 and 2 can be retransmitting the same input (1 or 2). The analog output is enabled only after the retransmission output range is selected by the RANGE mnemonic.
Board, CPU Circuit Board and Power Source Circuit Board. The Display Circuit Board is located inside the MCY-20 Configuration Module. The CPU and Power Source Circuit Boards are located inside the TY-2090 Transmitter. To gain access to the CPU and Power Source Circuit Boards, follow the instructions...
PRESYS Instruments TY - 2090 ii) Slide the CPU and Power Source Circuit Boards out of the aluminum case, together with the DB-25 Terminal. Notice that both circuit boards are united by a screwed spacer between them. Remove the screw which fastens one of the holder sides and open the boards as illustrated in figure 21.
Page 31
PRESYS Instruments TY - 2090 Jumpers Locations 1 to 4 (Channel 2) Jumpers Locations 5 to 8 (Channel 1) Fig. 22 - Jumper Locations on CPU Circuit Board Table 2 shows the jumpers which should be installed for different types of inputs.
TY - 2090 4.3 - Optional Module Connections The TY-2090 Transmitter can be provided with up to four output signals plus communication. For that purpose, the corresponding optional modules should be installed inside the instrument. By opening the Transmitter as explained in section 4.1, access is gained to 4 fittings on the Power Source Board, plus one fitting on CPU Board (see figure 24).
Page 33
PRESYS Instruments TY - 2090 The fittings on Power Supply Board are called MOD 1, MOD 2, MOD 3 and MOD 4, and are, respectively, the signal counterparts for output 1, output 2, output 3 and output 4 on the Transmitter I/O terminals shown in figure 3. The fitting for the communication module is located on CPU Circuit Board and have no denomination.
Page 34
PRESYS Instruments TY - 2090 In order to configure the optional analog output module for retransmission output of 4 to 20 mA, 1 to 5 V or 0 to 10 V, just install the jumper as specified in Table 3.
Instruments TY - 2090 4.4 - Calibration The TY-2090 Transmitter is accurately calibrated in factory and does not require regular calibration under normal conditions. If, for any reason, a recalibration is required, follow the procedure described below. Disconnect process signals from the Transmitter I/O terminals.
Page 36
PRESYS Instruments TY - 2090 After running through all references of the table related to the input type to be calibrated, the calibration process will have been completed. It is possible to recalibrate only one point, without affecting the other points already calibrated, when the calibration of such point has not been properly carried out.
Page 37
PRESYS Instruments TY - 2090 Calibration of Voltage Input (0 to 55 mV) In order to calibrate a voltage input from 0 to 55 mV, connect an accurate DC power source to the channel to be calibrated (terminals 2 (+) and 3 (-) for channel 1, or 5 (+) and 6 (-) for channel 2).
Page 38
PRESYS Instruments TY - 2090 Reference Mnemonic 0.0000 V C.0V 2.0000 V C.2V 4.0000 V C.4V 6.0000 V C.6V 8.0000 V C.8V 10.0000 V C.10V Table 8 - Required voltages for the calibration of voltage inputs from 0 to 10 V...
Page 39
PRESYS Instruments TY - 2090 The user should then measure accurately the I/O terminal temperature and correct the value presented by the program in the manner usually employed to introduce parameter values, as explained in section 3.2, Configuration. After completing those two steps, the input calibration for any type of thermocouple is concluded.
PRESYS Instruments TY - 2090 Output type Output 1 with Input 1 Output 2 with Input 2 current (0 to 20 mA) terminal 13 (+) with 1 (+) terminal 15 (+) with 4 (+) voltage (0 to 10 V) terminal 14 (-) with 3 (-)
Page 41
PRESYS Instruments TY - 2090 Instrument indicating error on display of the MCY-20 Configuration Module After turning on the equipment start the test routine to check the RAM and E2PROM integrity. If one of these components presents problems, the Module display will show the following error codes: Err.
PRESYS Instruments TY - 2090 CPU BOARD POWER SUPPLY BOARD Flat-cable 1 Figure 28 - Transmitter Voltage Test Points In case the problem is not isolated, the Transmitter should be returned to factory for repairs. 4.6 - Parts Listing Power Supply Board...
Need help?
Do you have a question about the TY-2090 and is the answer not in the manual?
Questions and answers