Fujitsu ARXG12KHTAP Design & Technical Manual page 43

Air conditioner duct type
Hide thumbs Also See for ARXG12KHTAP:
Table of Contents

Advertisement

2) Static pressure
Select the appropriate static pressure according to the installation conditions.
Function number
26
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er's recommended value).
Function number
30
(For cooling)
9-2. Function settings by using remote controller
Setting value
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
31
32
Setting value
00
01
02
03
04
05
06
07
08
31
(For heating)
09
10
11
12
13
14
15
16
17
Setting description
30 Pa
40 Pa
50 Pa
60 Pa
70 Pa
80 Pa
90 Pa
100 Pa
110 Pa
120 Pa
130 Pa
140 Pa
150 Pa
160 Pa
170 Pa
180 Pa
190 Pa
200 Pa
Standard
(35 Pa)
Automatic airflow adjustment
Setting description
Standard setting
No correction 0.0 °C
-0.5 °C
-1.0 °C
-1.5 °C
-2.0 °C
-2.5 °C
-3.0 °C
-3.5 °C
-4.0 °C
+0.5 °C
+1.0 °C
+1.5 °C
+2.0 °C
+2.5 °C
+3.0 °C
+3.5 °C
+4.0 °C
- 39 -
Factory setting
Factory
setting
More cooling
Less heating
Less cooling
More heating
9. Function settings