Installation - Ei Electronics Ei413 Instructions Manual

Radiolink panel module for use with rf smoke, heat and carbon monoxide alarms

Advertisement

Installation

The Ei413 can be installed in or next to the panel. If the panel
is in a metal case, then the module should be located on the
outside of the panel.
CAUTION!
Before connecting the Ei413 to a fire or security panel please
check with the panel manufacturer to determine if an End of Line
(EOL) device(s) and/or current limiting resistor is required and
how and where they should be fitted. Any clarification required on
these components should be directed to the Panel manufacturer.
A – Connecting an Ei413 with a Fire Panel
Important: For panels which are connected to multiple detection
circuits (or zones), each panel input (fire or security) requires
its own Ei413. In other words, a single Ei413 panel interface
should not be used for connecting multiple zones to the panel.
Each zone should be house coded separately.
A.1 Operating principles
Typically, conventional fire panels will monitor both fire and fault
conditions. The Ei413 may be configured to communicate both
6