INDOOR CLEARANCES

(Appearance may vary)
This picture is for reference only. Your product may look different.
More than 4 inches
Cut thermal insulation pipe to an
appropriate length and wrap it with tape,
making sure that no gap is left in the
insulation pipe's cut line.
SALTWATER COAST INSTALL
• The outdoor unit should be installed at least ½ mile away from the salt water, including seacoasts and inland
waterways. Please follow the installation instruction below if the unit installed from ½ mile to 5 miles away from
the salt water, including seacoasts and inland waterways.
• Install the outdoor unit in a place (such as near buildings etc.) where it can be protected from sea breeze which
can damage the outdoor unit.
Sea
Breeze
Sea
• Construct a protection wall around it to block the sea breeze if you cannot avoid installing the outdoor unit by
the seashore.
• A protection wall should be constructed with a solid material to block the sea breeze. The height and the width of
the wall should be 1.5 times larger than the size of the outdoor unit. Also, allow
at least 28" (700mm) between the protection wall and the outdoor unit for air
circulation to ventilate.
• Install the outdoor unit in a place where water can drain.
• Contact GEA Ductless for assistance if the above conditions cannot be met.
LOW AMBIENT INSTALL
- If the outdoor unit is installed in a region that is affected by strong wind or snow accumulation, it is recommended
to install wind baffle or/and snow hood accessories. Corresponding snow hood and wind baffle model number can
be found in product catalog. The installation instructions can be found in the manual shipped with each accessory
or on-line at GEAppliancesairandwater.com
12
More than 4 inches
Wrap the insulation pipe with
bottom to top.
ODU
ODU
Arrangement of
piping directions
Left
Condensate piping
must have a
downward slope of
at least 1/4" per foot
for proper drainage.
Sea
Breeze
Sea
Protection Walls
Sea Breeze
Sea
Rear Left
Rear Right
Right
Below
ODU
ODU
31-5000560 Rev. 5