Download Print this page

Hfct1-F100 Technical Specification - EA Technology HFCT1 Operating Manual

Advertisement

3534-MANUL-V01.00.03 HFCT1 Operating Manual
5.

HFCT1-F100 Technical Specification

Wideband Frequency Response and Range
Nominal Low Frequency -3dB Point
Nominal High Frequency -3dB Point
Nominal Sensitivity
Standalone Minimum Pulse Detection
Nominal Accuracy
Terminating impedance
Enclosure Insulation Rating
50Hz Response and Saturation
Saturation Current at 50Hz
50Hz Frequency Response
Hardware
Enclosure Aperture Diameter
Enclosure Diameter
Enclosure Depth
Clamping Mechanism
Connection
Mounting Capability
Enclosure Impact Rating
Environmental
Temperature
Humidity
IP Rating
12 August 2021
0.8 MHz
80 MHz
8.5 V/A
10pC
+/- 1V/A
50 Ohm
CAT IV (150V)
> 100 A
< -70 dB
94 mm
158 mm
33.5 mm
Metal Clamp / Cable Tie
Insulated BNC (female)
3x M5 Mounting Holes
IK08
-20 to 50°C
0-80%RH
IP2X