Parameter Group P01.xx (continued)
Reset, Sensor Monitoring
Parameter No.
Meaning of Parameter
Setting Range of Parameter
P01.07
Reset necessary after power up
Range: 0 .. 1
P01.08
Sensor monitoring on/off
Range: 0 .. 2
P01.09
Mode of sensor monitoring
Range: 0 .. 7
P01.10
Fix value 001
Description of Parameters and their Settings
Depending on this setting, the Reset input must be actuated once after
power up of the Monitor to enable operation.
0 : Reset necessary (recommended setting for safety applications)
1 : Reset not necessary
Note: a positive edge of the Starter signal also acts as Reset
If the sensor is monitored, the fault alarm may be latched until it is reset.
Setting:
0 : off (sensor monitor disabled)
1 : on
2 : on, latched
Note: If P01.08 set to 0 , Step P01.09 is meaningless.
Setting:
0 : Without monitoring
1 : Checks sensor current drain
2 : Checks signal voltage level at standstill
3 : Current drain and voltage level (E16521D.1 with A5S sensors)
4 : Inductive sensor (E16521D.3 with MPU sensors)
5 : Reserved for future use
6 : Eddy Current sensor voltage level (E16521D.2 with
EC Sensors)
7 : Eddy Current sensor voltage level and current drain (E16521D.2 with
EC Sensors)
Note 1: The voltage level check is only possible with BRAUN-sensor type
A5S... . In this instance, even at a standstill a defective sensor or
supply cable can be detected.
Note 2: The signal voltage level (and current drain) is compared versus
max/min-values as set in P08.01 to P08.04.
Note 3: Selection of Setting 0 makes Step P01.08 meaningless.
E16521D-Manual_EN_Rev12
(see Note 3)
(see Note 1)
(see Note 2)
(see Note 2)
2021_JAN_14