Troubleshooting Guide - PACH & COMPANY AeGIS SCR9 Installation And Operation Manual

Satellite card reader

Advertisement

• JP3 = left position JP4= right position for wiegand card reader.
Relay Output Duration Time (door open interval) always set for 5 seconds. Install an isolation relay with built-in timer or door strike
with built-in timer if you need less or more output duration time.
To Access Door or Gate using the Wiegand Proximity Card Reader. The red LED on the card reader must be ON if the power is ON.
Place the card or keyfob about an inch from the RED LED. The LED will change status to flickering green and the SCR9 will make
one beep then
ONE LONG TONE if access is granted.
TWO LONG TONE if access is denied.
TROUBLE SHOOTING GUIDE
The red LED on Card reader is not ON.
Solution:
• Check the voltage across 12AC1 and 12AC2, it should read 12.5 - 13.5 VAC or 13.5 - 14.5 VDC.
• The power switch (S1) must be ON (up position).
The card reader does not communicate with the AeGIS 9000 Series.
Solution:
• Check the RS485 wiring, see figure 2 for wiring diagram.
• If more than one SCR9 involved on the installation, check the RS485 wiring as shown on figure 2.
Some SCR9 RS485 wiring may be fine but the others may be reversed.
• Check the voltage across 12AC1 and 12AC2, it should read 12.5 - 13.5 VAC or 13.5 - 14.5 VDC.