PACH & COMPANY AeGIS SCR9 Installation And Operation Manual

Satellite card reader

Advertisement

Quick Links

AeGIS Satellite Card Reader (SCR9)
AeGIS Satellite Card Reader (SCR9)
Installation and Operation Manual
SYSTEM SPECIFICATIONS
Power Input: 12 VAC/DC 40VA UL Listed Transformer (12 VAC is supplied by Pach & Company) or 12 VDC Power Supply
(not supplied, power supply output voltage must be 13.5-14.5 VDC).
Current Consumption:350 mA Idle, 475 mA operation.
Emergency Battery: 12 VDC, 4 Ahr rechargeable with 12 VDC power supply (customer supplied).
Power Supply Output voltage must be 13.5-14.5 VDC.
Communication: RS-485 (maximum distance between the AeGIS 9000 Series and the SCR9 not exceeded 4000 Ft., a maximum 32
of SCR9 can be interfaced with the AeGIS 9000 Series).
Night Light: 14 VAC 200 mA Incandescent Lamp.
Operating Environment: Temp. 0
Relay Output: From C Dry Contact 120 VAC 10A/ 24 VDC 10 A/ 250 VAC 7A.
Mounting: Surface (accessories APM1, APM2, APM3, APM4 (indoor application only) and APM5).
Construction: 16 Gauge Cold Rolled Steel with Brushed Stainless Steel Faceplate.
Dimension: 6 3/4" (H) x 5 3/4 " (W), Depth 3 1/2" to 2 1/2" .
Shipping Weight: 4 Lbs.
UNPACKING THE SYSTEM
Check the serial number on the printed circuit board and cabinet, they must be matched. If they do not match, please contact Pach &
Company toll free number at 1-888-678-7224. All the items listed below come with the AeGIS SCR9.
Pach & Company
www.pach-co.com
0
0
F to +140
F. Relative Humidity 0% to 95%.
• AeGIS SCR9 Satellite Card Reader.
• 12 VAC Transformer.
• 6-pins, 5-pins and 3-pins terminal connector (inside the system).
• Key sets (2 keys per set).
• Installation and operation manual.
• Warranty Card with system's serial number.
• Two of 100 Ohm 1/4 Watt resistor.
• Allen wrench, inside the cabinet.
941 Calle Negocio
San Clemente, CA 92673
INTRODUCTION
Pach & Company thanks and congratulates you on the purchase of your AeGIS
Satellite Card Reader (SCR9).
The manual is designed to guide you through the proper installation and
operation of the SCR9. It is important for you to read and follow the manual
completely.
The AeGIS SCR9 comes with two years warranty, but we are so confident in
our product and our dealer's ability to install them properly, we will include
lightning and power surges in our two years warranty if Pach and Company
surge protection (ASP1) is installed with the systems.
SYSTEM DESCRIPTIONS
AeGIS SCR9 utilizes microprocessor technology to provide security as well as
convenience to you. The SCR9 must interface with the AeGIS 9000 Series via
an RS-485. The SCR9 only allows access to tenants or visitors via a 26-bit card
or keyfob code programmed on the AeGIS 9000 Series. There is no audio
intercom capability.
Phone: 1-888-678-7224
Fax: 949-498-6879

Advertisement

loading

Summary of Contents for PACH & COMPANY AeGIS SCR9

  • Page 1 Check the serial number on the printed circuit board and cabinet, they must be matched. If they do not match, please contact Pach & Company toll free number at 1-888-678-7224. All the items listed below come with the AeGIS SCR9.
  • Page 2: Warranty

    WARRANTY The AeGIS SCR9 comes with a two years warranty for parts and labor. We will include lightning strikes and power surge on our two years warranty if surge protector (ASP1) is installed with the system. • The serial number on the printed circuit board must match the serial number on the cabinet.
  • Page 3: Card Reader

    Follow the step number 1-5 on figure 1 to wire the system. CARD READER. The 26-bit wiegand card reader is factory prewired. The wiring connection shows on figure 1 in case the wires are disconnected. EARTH GROUND. Use 16-18 gauge solid wire for the earth ground. The best earth ground is the water pipe. RS-485.
  • Page 4: System's Operations

    Relay output is Form C Dry Contact, 125VAC/25A, 28VDC/10A or 250VAC/7A. Two conductors 16-18 gauge solid wires are recommended. See the door strike manufacturer wiring requirements. Figure 3 is Normally Opened DC Door Strike (polarity sensitive). Normally Opened Door Strike means the door is locked if the door strike is not energized/powered and the door is unlocked if the door is energized/powered.
  • Page 5: Troubleshooting Guide

    • JP3 = left position JP4= right position for wiegand card reader. Relay Output Duration Time (door open interval) always set for 5 seconds. Install an isolation relay with built-in timer or door strike with built-in timer if you need less or more output duration time. To Access Door or Gate using the Wiegand Proximity Card Reader.