Negative power values
If negative power values are measured on a circuit, please check whether the associated current
transformer circuit is connected correctly.
EL3453
• The voltage is measured via connections L1, L2, L3 and N.
• The current is measured via 4 current transformers (e.g. from the Beckhoff SCT series) and the
connections I
, I
, I
L1
L2
Fig. 31: EL3453, power measurement at a machine
Negative power values
If negative power values are measured on a circuit, please check whether the associated current
transformer circuit is connected correctly.
SCT6xxx
and I
(star point of the current transformers).
L3
N
Version: 1.3
Application example
49