3.1.1 TCP_SERVER pattern

1.Open Google browser and enter 192.168.1.254 to login to the page configuration
interface:
Main nouns of configuration page Function description:
Baud rate:Serial port Baud rate, optional range 1200~115200bps, default 9600bps,
please set this parameter to be consistent with the device connected to the serial port.
Parity checking:No check, odd check, even check can be selected, default no check,
please set this parameter to the serial port.
Stop bits:1 t, 2 bit stop is optional, default is 1 bit stop. Set this parameter to match the
device to which the serial port is connected.
2. Network Settings: IP address 192.168.1.254, device port: 502, working mode: TCP
server.
Serial port Settings: Serial port parameters: 19200bps, N81. The Serial Port test tool
Serial Port Utility is used to simulate Serial Port devices.
Multi-master setting: Select Modbus TCP to RTU mode as the conversion protocol.
Click Submit when the Settings are completed.