I.
General
JTF-GDM-936E spot-type composite smoke-sensing and temperature-sensing fire detector (hereinafter
referred to as the detector) is a multi-element composite detector constituted jointly by a smoke sensor
and a semiconductor temperature sensor in respect of technological structure and circuit structure. It has
not only the performance of photoelectric smoke-sensing fire detectors but also the performance of
temperature-sensing fire detectors.
This detector uses a non-polarity two-wire bus system, and can be jointly used with the 9000 series
alarm controllers produced by our company.
I
I. Features
1.
Electronic encoding, to offer simple and reliable engineering adjustment;
2.
Non-polarity two-wire bus;
3.
Key device self-diagnosis function;
4.
Shift compensation function and contamination report function for dust accumulation.
III. Technical indices
1.
Operating voltage: 24 V (pulse modulation)
2.
Operating current: Monitoring current ≤ 0.5 mA; alarm current ≤ 1.5 mA
3.
Sensing technology: Double-sensing technology containing photoelectric sensor and temperature
sensor with temperature sensing type: A2
4.
Encoding mode: Electronic encoding with encoding range 1-324
5.
Wiring mode: Non-polarity two-wire system
6.
Indicator lamp: Red, flashing once per 12 seconds for polling, and constantly on for alarm
7.
Installation height: ≤ 8 m
8.
Protected area: For the specific protected area, see relevant provisions in the China national
standard GB 50116 Code for design of automatic fire alarm systems
9.
Operating environment: Temperature: -10 °C - +50 °C; relative humidity: ≤ 95%, non-condensing
10. Outside dimensions: Diameter: 100 mm; height: 55 mm (with base)
11. Weight: About 100 g
12. Housing material: ABS
13. Standards followed: GB 4715-2005, GB 4716-2005
IV. Appearance and outside dimensions of product (as shown in Fig. 1)
Version: 103000A170623
carefully
Fig. 1
1
V. Product use and engineering application
1.
Schematic diagram for installation of matched base, as shown in Fig. 2:
2.
Wiring mode: The detector is connected into a compatible fire alarm controller via a two-wire bus
system through non-polarity connection mode and the L1 and L2 of the two-wire bus system are
connected with the terminals 1 and 3 of the matched base. The schematic diagram for connection of
multiple detectors and a controller is shown in Fig. 3.
Intelligent
two-wire
bus
controller
3.
Address encoding: As shown in Fig. 4, connect the detector through a detector base on the encoder
with L1 and L2 connected in non-polarity mode; set the encoder to encoding function, compile a correct
address code, and press the "Run" key to complete the address encoding setup.
(Note: For the detailed operations, please refer to the encoder operation manual.)
Terminal definitions (Non-polarity
two-wire system):
1 - Signal terminal (L1)
2 - No pin
3 - Signal terminal (L2)
4 - No pin
Fig. 2
Fig. 3
Fig. 4
2

Advertisement

loading

Summary of Contents for SANJIANG JTF-GDM-936E

  • Page 1 4 - No pin General JTF-GDM-936E spot-type composite smoke-sensing and temperature-sensing fire detector (hereinafter referred to as the detector) is a multi-element composite detector constituted jointly by a smoke sensor and a semiconductor temperature sensor in respect of technological structure and circuit structure. It has Fig.
  • Page 2 Shenzhen Fanhai Sanjiang Electronics Co., Ltd. will be responsible for free repair or replacement. Any failure caused by artificial damage, improper use or unauthorized adjustment, alteration or dismantling is not covered by the warranty scope, and our company will assume no responsibility for all consequences caused by it.